Plan Review Notes
Plan Review Notes For Permit 05081029
Permit Number 05081029
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-24 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE NOTE #1 FROM
 PREVOUS REVIEW.
 THIS IS NOTED AS PENDING FROM FPL.
 PLEASE KNOW, AIC RATINGS CAN BE ADJUSTED
 AT A LATER DATE? PLEASE VERIFY DISTANCE
 AND KVA RATING OF EXISTING TRANSFORMER
 TO VERIFY OR COME TO A CONCLUSION BASED
 ON MIN CALCS.
 IF KVA RATING OF TRANSFORMER, DISTANCE,
 AND CONDUCTOR SIZES ARE KNOWN, THE
 RATING CAN BE FIGURED.
  
 2) NOTE: PLEASE SEE THAT A NEW ADDRESS
 OF 3810 WAS ISSUED BY THE CITY
 ADDRESSING DEPT AND PLANS SHOULD REFLECT
 NEW ADDRESS AS REQUIRED PER FAC
 61G1-16.004.
 PLEASE ADJUST FOR ALL SHEETS AND ALL
 REFERENCES TO THIS PERMIT.
  
 ** PLEASE KNOW, PLANS ARE COMING BACK
 FOR COMMENTS BY OTHER REVIEWER(S).
 PLEASE SUBMIT.
  
 ALL OTHER COMMENTS WERE ADDRESSED AND
 RESPONSES WERE ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]