| Plan Review Notes For Permit 05081029 |
| Permit Number |
05081029 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-24 00:00:00 | ** UNSAT ** | | | | | | 1)NOTE: PLEASE SEE NOTE #1 FROM | | | PREVOUS REVIEW. | | | THIS IS NOTED AS PENDING FROM FPL. | | | PLEASE KNOW, AIC RATINGS CAN BE ADJUSTED | | | AT A LATER DATE? PLEASE VERIFY DISTANCE | | | AND KVA RATING OF EXISTING TRANSFORMER | | | TO VERIFY OR COME TO A CONCLUSION BASED | | | ON MIN CALCS. | | | IF KVA RATING OF TRANSFORMER, DISTANCE, | | | AND CONDUCTOR SIZES ARE KNOWN, THE | | | RATING CAN BE FIGURED. | | | | | | 2) NOTE: PLEASE SEE THAT A NEW ADDRESS | | | OF 3810 WAS ISSUED BY THE CITY | | | ADDRESSING DEPT AND PLANS SHOULD REFLECT | | | NEW ADDRESS AS REQUIRED PER FAC | | | 61G1-16.004. | | | PLEASE ADJUST FOR ALL SHEETS AND ALL | | | REFERENCES TO THIS PERMIT. | | | | | | ** PLEASE KNOW, PLANS ARE COMING BACK | | | FOR COMMENTS BY OTHER REVIEWER(S). | | | PLEASE SUBMIT. | | | | | | ALL OTHER COMMENTS WERE ADDRESSED AND | | | RESPONSES WERE ADDRESSED. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|