| 2005-09-22 00:00:00 | DENIED: | | | 1.NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED WITH PERMIT APPLICATION. | | | | | | 2.PLEASE PROVIDE EQUIPMENT SCHEDULE. | | | | | | 3.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS IN ACCORDANCE WITH 2001 | | | FBC(M) TABLE 403.3. | | | | | | 4.PLEASE INDICATE LOCATION OF THE AHU | | | & CONDENSING UNIT. | | | | | | 5.INDICATE LINE SIZE & MATERIAL FOR | | | THE REFRIGERANT & CONDENSATE. | | | | | | 6.PROVIDE LOCATION OF TERMINATION FOR | | | THE CONDENSATE. | | | | | | 7.PLEASE INDICATE WHAT WILL BE STORED | | | IN THE WAREHOUSE AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|