Plan Review Notes
Plan Review Notes For Permit 05081029
Permit Number 05081029
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-22 00:00:00DENIED:
 1.NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 2.PLEASE PROVIDE EQUIPMENT SCHEDULE.
  
 3.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001
 FBC(M) TABLE 403.3.
  
 4.PLEASE INDICATE LOCATION OF THE AHU
 & CONDENSING UNIT.
  
 5.INDICATE LINE SIZE & MATERIAL FOR
 THE REFRIGERANT & CONDENSATE.
  
 6.PROVIDE LOCATION OF TERMINATION FOR
 THE CONDENSATE.
  
 7.PLEASE INDICATE WHAT WILL BE STORED
 IN THE WAREHOUSE AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  