| 2005-08-31 00:00:00 | *********** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | PLEASE SEE AIC RATING IS INDICATED FOR |
| | SUB PANEL, HOWEVER NOT FOR MAIN. |
| | |
| | 2)NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE |
| | SUBMITTED PANEL SCHEDULE. |
| | PLEASE SEE A COUPLE MISSING AND REDLINED |
| | ON PLANS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS WHICH REQUIRES |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 4)NOTE: PLEASE SEE 210.62,220.12, FOR |
| | SHOW WINDOW RECEPT REQUIREMENTS. PLEASE |
| | SEE NO OTHER ELECTRICLA CAN BE ON THIS |
| | CIRCUIT. (PLEASE SEE NEXT COMMENT). |
| | PLEASE SEE WINDOW ON EAST ELEVATION |
| | WHICH DO NOT INDICATE AN RECEPT. |
| | |
| | 5)NOTE: PLEASE SEE 600.5, WHICH REQUIRES |
| | A DEDICATED CIRCUIT FOR SIGNAGE. |
| | |
| | 6)NOTE: PLEASE SEE POSSIBLE FIRE AND |
| | BLDG REVIEW COMMENTS. THERE SEEMS TO BE |
| | AN EGRESS/EXIT DOOR WHICH EXITS INTO AN |
| | AREA WHERE ELECTRICAL PLANS INDICATE |
| | MOTORIZED "DOORS"? PLEASE VERIFY THIS. |
| | |
| | 7)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | WHICH REQUIURES THE PRINTED NAME OF |
| | ENGINEER ON TITLE BLOCK. |
| | |
| | |
| | PLEASE SEE POSSIBLE COMMENS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |