Plan Review Notes For Permit 05081029
Permit Number 05081029
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-31 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE AIC RATING IS INDICATED FOR
 SUB PANEL, HOWEVER NOT FOR MAIN.
  
 2)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE A COUPLE MISSING AND REDLINED
 ON PLANS.
 215.5
  
 3)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS WHICH REQUIRES
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 4)NOTE: PLEASE SEE 210.62,220.12, FOR
 SHOW WINDOW RECEPT REQUIREMENTS. PLEASE
 SEE NO OTHER ELECTRICLA CAN BE ON THIS
 CIRCUIT. (PLEASE SEE NEXT COMMENT).
 PLEASE SEE WINDOW ON EAST ELEVATION
 WHICH DO NOT INDICATE AN RECEPT.
  
 5)NOTE: PLEASE SEE 600.5, WHICH REQUIRES
 A DEDICATED CIRCUIT FOR SIGNAGE.
  
 6)NOTE: PLEASE SEE POSSIBLE FIRE AND
 BLDG REVIEW COMMENTS. THERE SEEMS TO BE
 AN EGRESS/EXIT DOOR WHICH EXITS INTO AN
 AREA WHERE ELECTRICAL PLANS INDICATE
 MOTORIZED "DOORS"? PLEASE VERIFY THIS.
  
 7)NOTE: PLEASE SEE FAC 61G15-23.002,
 WHICH REQUIURES THE PRINTED NAME OF
 ENGINEER ON TITLE BLOCK.
  
  
 PLEASE SEE POSSIBLE COMMENS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW