| 2005-11-12 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A001 INDEX SHEET. ALL SHEETS ON |
| | INDEX SHEET NOT SUBMITTED. PLEASE SUBMIT |
| | ALL SHEETS. PLANS NOT COMPLETE. SECTION |
| | 104.2.1. |
| | 2. SHTS I-1 & I-2 INFORMATION REQUIRED |
| | ON IMPRESSION SEAL OF LANDSCAPE |
| | ARCHITECT IS NOT IMPRESSED ON THE PLANS. |
| | PLEASE RESEAL SHEETS. FAC 61G1-16.002(1) |
| | AND FS 481.321 |
| | 3. SHT A101 URINAL REQUIRED IN THE MENS |
| | TOILET ROOM FOR THE SWIMMING POOL PER |
| | TABLE 424.1.6.1. |
| | 4. SHT A101 TOILET ROOMS SHALL COMPLY |
| | WITH SECTIONS 11-4.16, 11-4.18, 11-4.19, |
| | AND 11-4.22 AND ALL SUBSECTIONS. PLEASE |
| | PROVIDE A DETAIL SHOWING ALL |
| | REQUIREMENTS. |
| | 5. SHT A102 TOILET ROOM FOR GUARD HOUSE |
| | TO COMPLY WITH SECTIONS 11-4.16, |
| | 11-4.19, AND 11-4.22 WITH ALL |
| | SUBSECTIONS. PLEASE PROVIDE A DETAIL |
| | SHOWING ALL REQUIREMENTS. |
| | 6. SUBMIT A SANITARY & A WATER RISER |
| | DIAGRAM FOR THE GUARD HOUSE. SHOW ALL |
| | PIPE SIZES, TRAPS, VENTS ECT. FOR THE |
| | SANT. SHOW ALL PIPE SIZES, VALVES, AND, |
| | IF REQUIRED, WATER HAMMER ARRESTORS PER |
| | SECTION 604.9. |
| | 7. PLUMBING PLANS FOR SWIMMING POOL |
| | TOILET ROOMS WERE NOT SUBMITTED. PLEASE |
| | SUBMIT THE PLUMBING PLANS ALONG WITH THE |
| | SANT. AND WATER RISER DIAGRAMS. SECTIONS |
| | 104.2.1 & 104.3.1.1. |
| | |