Plan Review Notes
Plan Review Notes For Permit 05081009
Permit Number 05081009
Review Stop E
Sequence Number 2
Notes
Date Text
2005-11-10 00:00:00*** UNSAT 2ND REVIEW ***
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS
 FOR NEW SERVICE EQUIPMENT.
 THIS IS FOR NEW MAIN AND MCB PANEL.
 PLEASE ALSO SHOW THE LOCATION OF THE MCB
 DISCONNECT AS SHOWN ON RISER.
 **PLEASE VERIFY USE OF "RIGID METALLIC"
 CONDUIT FOR SERVICE. THIS IS OK, HOWEVER
 PLEASE KNOW, IF SHOWN ON PLANS, THEN
 THIS WILL BE REQUIRED. (IS THIS RIGID
 PVC)?
  
 2)NOTE: PLEASE SEE A GFI RECEPT AHS NOW
 BEEN ADDED FOR BATH RM, HOWEVER PLEASE
 SEE 210.52D, WHICH REQUIRES THE GFI TO
 BE WITHIN 3' OF OF THE EDGE OF THE LAV
 WITH/OUT CROSSING OVER ONE LAV TO OBTAIN
 ACCESS TO THE GFI.
 PLEASE KNOW, THE EXSITING SHOWN MAY BE
 MOVED TO THE CENTER OF THE TWO LAV'S, OR
 ONE MAY BE ADDED.
  
 3)NOTE: PLEASE SEE PREVIOUS NOTE WITH
 RESPECT TO CHAPTER 34 OF THE FBC.
 PLEASE ALSO SEE 104.2.1 WHICH STATE THE
 TECHNICAL ASPECTS OF THE CODE MAY NOT BE
 REFERENCED IN WHOLE OR IN PART.
 PLEASE SHOW ALL EXISTING WHICH MAY MEET
 2002 NEC OR NEW TO BE INSTALLED WITH
 RESPECT TO GFI AND SMOKE DETECTOR
 LOCATIONS.
  
 4)NOTE: PLEASE SEE 210.11C3, WHICH
 PERMITS THE GFI RECEPT TO BE SHARED WITH
 OTHER BATH(S) GFI'S, HOWEVER MULTIPLE
 BATH RMS SHALL NOT BE SHARED (LTS AND
 RECEPTS) ON THE SAME BATH CIRCUIT.
 THIS MUST BE DEDICATED TO EACH BATH
 ROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]