| 2005-11-10 00:00:00 | *** UNSAT 2ND REVIEW *** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT THE AIC RATINGS |
| | FOR NEW SERVICE EQUIPMENT. |
| | THIS IS FOR NEW MAIN AND MCB PANEL. |
| | PLEASE ALSO SHOW THE LOCATION OF THE MCB |
| | DISCONNECT AS SHOWN ON RISER. |
| | **PLEASE VERIFY USE OF "RIGID METALLIC" |
| | CONDUIT FOR SERVICE. THIS IS OK, HOWEVER |
| | PLEASE KNOW, IF SHOWN ON PLANS, THEN |
| | THIS WILL BE REQUIRED. (IS THIS RIGID |
| | PVC)? |
| | |
| | 2)NOTE: PLEASE SEE A GFI RECEPT AHS NOW |
| | BEEN ADDED FOR BATH RM, HOWEVER PLEASE |
| | SEE 210.52D, WHICH REQUIRES THE GFI TO |
| | BE WITHIN 3' OF OF THE EDGE OF THE LAV |
| | WITH/OUT CROSSING OVER ONE LAV TO OBTAIN |
| | ACCESS TO THE GFI. |
| | PLEASE KNOW, THE EXSITING SHOWN MAY BE |
| | MOVED TO THE CENTER OF THE TWO LAV'S, OR |
| | ONE MAY BE ADDED. |
| | |
| | 3)NOTE: PLEASE SEE PREVIOUS NOTE WITH |
| | RESPECT TO CHAPTER 34 OF THE FBC. |
| | PLEASE ALSO SEE 104.2.1 WHICH STATE THE |
| | TECHNICAL ASPECTS OF THE CODE MAY NOT BE |
| | REFERENCED IN WHOLE OR IN PART. |
| | PLEASE SHOW ALL EXISTING WHICH MAY MEET |
| | 2002 NEC OR NEW TO BE INSTALLED WITH |
| | RESPECT TO GFI AND SMOKE DETECTOR |
| | LOCATIONS. |
| | |
| | 4)NOTE: PLEASE SEE 210.11C3, WHICH |
| | PERMITS THE GFI RECEPT TO BE SHARED WITH |
| | OTHER BATH(S) GFI'S, HOWEVER MULTIPLE |
| | BATH RMS SHALL NOT BE SHARED (LTS AND |
| | RECEPTS) ON THE SAME BATH CIRCUIT. |
| | THIS MUST BE DEDICATED TO EACH BATH |
| | ROOM. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW . IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |