2005-09-02 00:00:00********* UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
 2)NOTE: PLEASE SEE PLANS REFERENCE SBC.
 PLEASE SEE WE ARE UNDER THE FBC,,2001
 WITH 2003 REVISIONS.
  
 3)NOTE: PLEASE MISSING BATH GFI RECEPT
 IN ADDITION.
 210.52, 210.8
  
 4)NOTE: PLEASE SEE 104.2.1, CITY WIDE
 ADMINISTRATIVE CODE, WHICH REQUIRES THE
 PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS/DESIGN.
  
 5)NOTE: PLEASE CORRELATE A/C HEAT LOADS
 SHOWN ON PLANS.
 PLEASE SEE ONE SHOWS 5KW, THE OTHER
 SHOWS 7KW?
  
 6)NOTE: PLEASE VERIFY #4 SHOWN FOR WATER
 HEATER CONDUCTORS.
 THIS IS ONLY A NOTE AS #4 IS OK, HOWEVER
 THIS SIZE AWG WILL MOST LIKELY NOT FIT
 INTO WATER HEATER.
  
 7)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDTIONS TO EXSITNG DWELLINGS OF MORE
 THAN 25%.
 PLEASE SHOW ALL RECEPTS AT LOCATION
 REQUIRED TO BE GFI UNDER 2002 NEC 210.8,
 IF EXSITING, PLEASE SHOW, IF NEW PLEASE
 INDICATE AS NEW TO BE INSTALLED.
 (KITCHENS, BATHS, OUTSIDE, TEC.
 PLEASE ALSO SHOW ALL SMOKE DETECTORS
 WHICH WILL BE REQUIRED TO BE INSTALLED
 INSIDE AND OUTSIDE ALL EXSITNG BEDROOMS.
 NFPA-72 11.5.1 2002 .
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSTALL NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  