| 2005-09-02 00:00:00 | ********* UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | |
| | 2)NOTE: PLEASE SEE PLANS REFERENCE SBC. |
| | PLEASE SEE WE ARE UNDER THE FBC,,2001 |
| | WITH 2003 REVISIONS. |
| | |
| | 3)NOTE: PLEASE MISSING BATH GFI RECEPT |
| | IN ADDITION. |
| | 210.52, 210.8 |
| | |
| | 4)NOTE: PLEASE SEE 104.2.1, CITY WIDE |
| | ADMINISTRATIVE CODE, WHICH REQUIRES THE |
| | PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS/DESIGN. |
| | |
| | 5)NOTE: PLEASE CORRELATE A/C HEAT LOADS |
| | SHOWN ON PLANS. |
| | PLEASE SEE ONE SHOWS 5KW, THE OTHER |
| | SHOWS 7KW? |
| | |
| | 6)NOTE: PLEASE VERIFY #4 SHOWN FOR WATER |
| | HEATER CONDUCTORS. |
| | THIS IS ONLY A NOTE AS #4 IS OK, HOWEVER |
| | THIS SIZE AWG WILL MOST LIKELY NOT FIT |
| | INTO WATER HEATER. |
| | |
| | 7)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDTIONS TO EXSITNG DWELLINGS OF MORE |
| | THAN 25%. |
| | PLEASE SHOW ALL RECEPTS AT LOCATION |
| | REQUIRED TO BE GFI UNDER 2002 NEC 210.8, |
| | IF EXSITING, PLEASE SHOW, IF NEW PLEASE |
| | INDICATE AS NEW TO BE INSTALLED. |
| | (KITCHENS, BATHS, OUTSIDE, TEC. |
| | PLEASE ALSO SHOW ALL SMOKE DETECTORS |
| | WHICH WILL BE REQUIRED TO BE INSTALLED |
| | INSIDE AND OUTSIDE ALL EXSITNG BEDROOMS. |
| | NFPA-72 11.5.1 2002 . |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSTALL NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |