Plan Review Notes
Plan Review Notes For Permit 05080948
Permit Number 05080948
Review Stop E
Sequence Number 4
Notes
Date Text
2006-12-26 07:59:48** UNSAT **
  
 1) NOTE: PLEASE SEE THE TAPS ON THE SECONDARY SIDE OF
 THE NEW TRANSFORMER FEEDING THE RTU DOES NOT CONTAIN
 OCP WITHIN THE PERMITTED DISTANCES AS STATED IN
 240.21C.
 PLEASE SEE MAX LENGTHS PERMITTED. SHALL TERMINATE IN
 OCP.
 PLEASE KNOW BASED ON THE PLANS ON FILE THE RTU IS TOO
 FAR AWAY.
  
 2) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OCP FOR THE
 SAME TRANSFORMER SHALL BE 125%. PLEASE SEE ONLY IF THE
 TRANSFORMER MEETS THE EXCEPTION #3 CAN THE OCP BE SET
 HIGHER.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  