| Plan Review Notes For Permit 05080948 |
| Permit Number |
05080948 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-12-26 07:59:48 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THE TAPS ON THE SECONDARY SIDE OF | | | THE NEW TRANSFORMER FEEDING THE RTU DOES NOT CONTAIN | | | OCP WITHIN THE PERMITTED DISTANCES AS STATED IN | | | 240.21C. | | | PLEASE SEE MAX LENGTHS PERMITTED. SHALL TERMINATE IN | | | OCP. | | | PLEASE KNOW BASED ON THE PLANS ON FILE THE RTU IS TOO | | | FAR AWAY. | | | | | | 2) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OCP FOR THE | | | SAME TRANSFORMER SHALL BE 125%. PLEASE SEE ONLY IF THE | | | TRANSFORMER MEETS THE EXCEPTION #3 CAN THE OCP BE SET | | | HIGHER. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|