2006-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW:
  
 1.)THE NOC IS EXPIRED, OVER 90 DAYS
 WITHOUT COMMENCING WORK, FS713.13(2).
 THIS CAN BE ADDRESSED PRIOR TO PERMIT
 PICKUP AND DOES NOT PREVENT THE PERMIT
 FROM BEING ISSUED.
  
 11.)THE DUMPSTER ENCLOSURE GATE CANNOT
 SWING OVER THE PROPERTY LINE,
 FBC3206.1.1.THE PLAN HAS BEEN REVISED
 AND SHOWS THE GATE ENDING AT THE
 PROPERTY LINE.HOWEVER, THE GATE IN THE
 OPEN POSITION WHEN SCALED IS 10', BUT
 THE GATE IN THE CLOSED POSITION IS SHOWN
 AS 13'.A2 DOOR SCHEDULE GIVES A
 DIMENSION OF 12' FOR THIS GATE, IN WHICH
 CASE IT WILL SWING OVER THE PROPERTY
 LINE AND WILL NOT FULLY ENCLOSE THE
 DUMPSTER.ADDRESS.
  
 L2 AND THE SL SHEETS HAVE NOT BEEN
 REVISED TO SHOW THE NEW DUMPSTER GATE
 DETAIL.
  
  
 17.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.THE SHEET
 PROVIDED FOR ARCH ALUMINUM PRODUCTS AND
 THE HURST AWNING ARE NOT THE PRODUCT
 APPROVALS, THEY ARE LISTS OF ALL
 PRODUCTS FOR THAT MANUFACTURER.PLEASE
 PRINT THE STATE PRODUCT APPROVAL AS YOU
 DID FOR THE GAF MODIFIED.
  
 18.)THE FIRST REVIEW STATED THAT A
 HURRICANE SHUTTER INSTALLATION PLAN
 WOULD BE REQUIRED AND MUST BE APPROVED
 BY THE BUILDING OFFICIAL IF REMOVABLE
 PANELS WERE USED.THE SECOND REVIEW
 STATED THAT SINCE ALL PRODUCT APPROVALS
 WERE FOR IMPACT GLASS, THE PLAN WAS NOT
 NECESSARY.NOW ON THE THIRD REVIEW
 THERE IS A NEW COMMENT ON A5 STATING
 THAT NON IMPACT OPENINGS WILL BE
 SHUTTERED AND STORM PANELS WILL BE
 STORED IN THE EQUIPMENT ROOM.THE PLAN
 CANNOT BE APPROVED UNTIL A HURRICANE
 INSTALLATION PLAN IS SUBMITTED AND
 APPROVED BY THE BUILDING OFFICIAL.ALL
 PRODUCT APPROVALS SUBMITTED ARE FOR
 IMPACT GLASS.
  
 IF YOU ARE GOING TO USE NONIMPACT
 PRODUCTS, PLEASE SUBMIT A PLAN AS
 REQUESTED IN THE FIRST REVIEW AND SUBMIT
 PRODUCT APPROVALS FOR THE NON IMPACT
 WINDOWS AND STORM PANELS.IF YOU ARE
 USING ALL IMPACT GLASS, REMOVE THE NOTE
 FROM THE PLAN.
  
 26.SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF COMMENT 11 ABOVE IS NOT
 ADDRESSED A THIRD TIME.
  
 NEW COMMENT:
  
 19.)SP-2, PROVIDE A DIMENSION OF
 ENCROACHMENT OVER THE PROPERTY LINE FOR
 THE MOULDING AT THE TOP OF THE WALL,
 FBC3206.1.1, EXCEPTION.
  
 20.)SEPARATE PERMITS REQUIRED FOR THE
 AWNINGS.THIS COMMENT DOES NOT NEED TO
 BE ADDRESSED AT THIS TIME; INFORMATIONAL
 ONLY.
  