| Plan Review Notes For Permit 05080948 |
| Permit Number |
05080948 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-12 00:00:00 | PROVISO: | | | RTU CURB SHALL BE A MINIMUM OF 8" ABOVE | | | THE ROOF SURFACE PER 2001 FBC 1511.7. | | | | | | PLEASE NOTE, CUT SHEET FOR THE WALK-IN | | | COOLER DOES NOT INDICATE LOCATION OF THE | | | CONDENSOR.SHOULD CONDENSOR BE REMOTE | | | AND MOUNTED ON A STAND LOCATED ON THE | | | ROOF, THE HEIGHT FROM THE ROOF SURFACE | | | TO THE BOTTOM OF THE SUPPORT RAIL SHALL | | | COMPLY WITH 2001 FBC TABLE 1511.7 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|