Plan Review Notes
Plan Review Notes For Permit 05080948
Permit Number 05080948
Review Stop E
Sequence Number 2
Notes
Date Text
2006-03-24 00:00:00ELEC FOR REVIEW
 *** UNSAT ***
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND NEW NOTE DUE TO NOTE ON
 PLANS.
  
  
  
 1) NOTE: PLEASE SEE NOTE #1, WHICH
 MENTIONED ALL SHEETS TO CONTAIN ALL
 LICENSING FOR TITLE BLOCKS , ALL
 INFORMATION AS REQUIRED PER FAC
 61G1-16.004,61G15-23.002,
 FS471.023,481.219,
 PLEASE SEE LANDSCAPE PLANS, NO
 FIRM/CERTIFICATE OF AUTHORIZATION
 NUMBER??
 PLEASE SEE SURVEY SHEETS ARE STILL
 SEALED "PHOTO-COPIES" OF SIGNED SURVEYS.
 NEITHER OF WHICH ARE NEEDED FOR
 ELECTRICALPLANS. THIS IS ONLY A NOTE
 AND WILL NOT AFFECT ELECTRICLA PLANS.
  
 ELEC NOTES.
  
 1)NOTE: PLEASE PROVIDE WIND LOAD
 CALCULATIONS FOR LIGHT POLES, INCLUDING
 FIXTURES.
 PLEASE KNOW, THESE CALCULATIONS ARE
 REQUIREDTO BE SIGNED, DATED AND SEALED
 BY A FL LICENSED PE.
 SHEET ATTACHED TO SITE PLAN DOES NOT
 MEET REQUIREMENTS.
  
 2) NOTE: PLEASE KNOW, ALL SIGNAGE SHALL
 CONTAIN "1-INCH" LETTERS ON CONTRASTING
 BACKGROUND. ELECTRICAL SHEETS CONTAINING
 THIS NOTE, CAN BE REDLINED, OR SHEETS
 MAY BE REVISED AT THIS TIME.
  
 3)NOTE: PLEASE SEE SPACES 5 AND 6 WILL
 BE REQUIRED TO HAVE A PERMANANT/
 UN-REMOVEABLE DEAD FRONT.
 230.71, 230.70
  
 4)NOTE: PLEASE SEE 225.31,225.31
 , A MCB WILL BE REQUIRED IN PANEL "L".
 THIS WAS NOT ON PREVIOUS REVIEW, HOWEVER
 AS THIS IS A SEPARATE BLDG THIS WILL BE
 REQUIRED.
  
 PLEASE SUBMIT THE ABOVE. PLANS ARE
 COMING BACK FOR "SITE-POLES COMMENT
 MAINLY AND THESE ITEMS SHOUDL BE
 ADDRESSED AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATIO FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ***********NOTE ADDED **********
  
  
 PLEASE HAVE ENGINEER TO CALL TO GO OVER
 ELECTRICAL.