| 2006-04-17 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | SECOND REVIEW; NUMBERING REMAINING THE |
| | SAME FOR CONSISTENCY |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | THE NOC IS EXPIRED, 90 DAYS WITHOUT |
| | COMMENCING WORK, FS713.13(2).REFILE TO |
| | GET A NEW DATE. |
| | |
| | 2.)ADDRESSED. |
| | |
| | 3-6.)ADDRESSED. |
| | |
| | 7.)PROVIDE A SOILS INVESTIGATION |
| | REPORT, FBC1804.2.2. |
| | |
| | SIGNATURE TO BE A WET SIGNATURE, NOT A |
| | PHOTOCOPY PER FBPE. |
| | |
| | 8.)ENERGY CALCS REQUIRED. |
| | |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC PROVIDED. |
| | |
| | 9-10.) ADDRESSED. |
| | |
| | 11.)THE RECYCLING BIN GATE CANNOT |
| | SWING OVER THE PROPERTY LINE, |
| | FBC3206.1.1. |
| | |
| | MY APOLOGIES, BUT THIS COMMENT SHOULD |
| | HAVE REFERRED TO THE BIN AND THE |
| | DUMPSTER ENCLOSURE.YOU HAVE CHANGED |
| | THE BIN AS REQUESTED BUT THE DUMPSTER IS |
| | NOT COMPLIANT. |
| | |
| | 12-13.) ADDRESSED. |
| | |
| | 14.)STRUCTURAL NOTES, S3, DECLARES |
| | THIS AS A PARTIALLY ENCLOSED BUILDING. |
| | |
| | THE NOTE STATING THAT THE CAR WAS BAY IS |
| | OPEN IS ACKNOWLEDGED. PLEASE PROVIDE |
| | CALCULATIONS AS PER DEFINITION OF |
| | PARTIALLY ENCLOSED. |
| | |
| | ALSO NOTE THAT THE ARCHITECT ON A5 |
| | DECLARES AN INTERNAL COEFFICIENT OF |
| | -.18, WHICH INDICATES AN ENCLOSED |
| | BUILDING.IF THE ENGINEER IS CORRECT IN |
| | DETERMINING THAT THIS IS A PARTIALLY |
| | ENCLOSED BUILDING, REVISE A5.THE TWO |
| | DESIGN PROFESSIONALS SHOULD BE USING THE |
| | SAME DESIGN ASSUMPTIONS. |
| | |
| | THE ARCHITECT INDICATES ON A5 THAT ALL |
| | OPENINGS INCLUDING THE ENTRY/EXIT OF THE |
| | CAR WASH TUNNEL ARE TO BE PROTECTED. |
| | THE ELEVATION STATES THAT WINDOW F WILL |
| | NOT HAVE GLASS BUT IT IS LISTED ON THE |
| | SCHEDULE A5 AS HAVING POSITIVE AND |
| | NEGATIVE PRESSURES.S4 SHOWS THESE |
| | WINDOWS AS IMPACT GLASS.WINDOW C, THE |
| | WINDOWS BETWEEN THE A/C SPACE AND THE |
| | CAR WASH TUNNEL, ARE NOT SHOWN ON THE |
| | WALL OPENING SCHEDULE.IF THE TUNNEL IS |
| | PARTIALLY ENCLOSED, THESE WINDOWS WILL |
| | BE SUBJECT TO PRESSURES AND POSSIBLY |
| | IMPACT.IF THE TUNNEL IS FULLY |
| | ENCLOSED, WINDOW F SHOULD HAVE GLASS AND |
| | THE ENGINEER SHOULD DECLARE AN ENCLOSED |
| | BUILDING.PLEASE MAKE THE VARIOUS |
| | SPECIFICATIONS CONSISTENT AND THE DESIGN |
| | CONSISTENT WITH THE ENCLOSURE CATEGORY. |
| | |
| | 15-16.) ADDRESSED. |
| | |
| | 17.)SUBMIT FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVALS FAC9B72 ALONG WITH THE |
| | EVALUATION OR TEST REPORT FOR THE |
| | FOLLOWING: |
| | PAIR OF LOUVERED DOORS |
| | OVERHEAD DOORS |
| | STOREFRONT DOORS, WINDOWS AND MULLIONS |
| | ROOF |
| | IMPACT PROTECTION IF APPROVED (SEE |
| | FOLLOWING COMMENT) |
| | |
| | PROVIDE FLORIDA STATE PRODUCT APPROVALS |
| | FOR ALL PRODUCTS, FAC9B72, |
| | WWW.FLORIDABUILDING.ORG.IF A STATE |
| | PRODUCT APPROVAL IS NOT AVAILABLE, |
| | PLEASE ADVISE AND A LOCAL PA WILL BE |
| | ISSUED. |
| | |
| | FOR THE GAF MODIFIED, THE PRODUCT |
| | APPROVAL IS INCOMPLETE.INCLUDE THE |
| | LAST PAGES. |
| | |
| | FOR THE GAF MODIFIED, CHOOSE THE |
| | APPROVED ASSEMBLY YOU ARE USING. |
| | |
| | IF ALL GLASS PRODUCTS ARE IMPACT, WHAT |
| | IS THE ROLL UP SHUTTER FOR? |
| | |
| | A6 AND A5 REQUIRE PRODUCT APPROVALS FOR |
| | THE OVERHEAD DOOR.A SHOP DRAWING |
| | STATING THAT PRODUCT APPROVALS ARE NOT |
| | REQUIRED WAS SUBMITTED.ADDRESS AND |
| | CLARIFY WITH A RESPONSE LETTER IF |
| | NECESSARY. |
| | |
| | 18.)SEE ATTACHED POLICY FOR MISSILE |
| | IMPACT PROTECTION, ITEM NUMBER 13.USE |
| | OF REMOVABLE SHUTTERS ON COMMERCIAL |
| | BUILDINGS MUST BE APPROVED BY THE |
| | BUILDING OFFICIAL.IF THE GLAZING IS |
| | NOT IMPACT, SUBMIT A PLAN FOLLOWING THE |
| | GUIDELINES. |
| | |
| | NOTE - ADDRESSED, ALL |
| | COMPONENTS & CLADDING IMPACT RESISTANT. |
| | |
| | 19-23.)ADDRESSED. |
| | |
| | NEW COMMENTS: |
| | |
| | 24.)PARKING IS TO COMPLY WITH CITY OF |
| | WEST PALM BEACH STANDARD, SEE ATTACHED. |
| | |
| | 25.)SEPARATE PERMIT REQUIRED FOR THE |
| | WALL AT THE PROPERTY LINE. |
| | |
| | 26.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED. |