Plan Review Notes
Plan Review Notes For Permit 05080948
Permit Number 05080948
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 SECOND REVIEW; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THE NOC IS EXPIRED, 90 DAYS WITHOUT
 COMMENCING WORK, FS713.13(2).REFILE TO
 GET A NEW DATE.
  
 2.)ADDRESSED.
  
 3-6.)ADDRESSED.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 SIGNATURE TO BE A WET SIGNATURE, NOT A
 PHOTOCOPY PER FBPE.
  
 8.)ENERGY CALCS REQUIRED.
  
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC PROVIDED.
  
 9-10.) ADDRESSED.
  
 11.)THE RECYCLING BIN GATE CANNOT
 SWING OVER THE PROPERTY LINE,
 FBC3206.1.1.
  
 MY APOLOGIES, BUT THIS COMMENT SHOULD
 HAVE REFERRED TO THE BIN AND THE
 DUMPSTER ENCLOSURE.YOU HAVE CHANGED
 THE BIN AS REQUESTED BUT THE DUMPSTER IS
 NOT COMPLIANT.
  
 12-13.) ADDRESSED.
  
 14.)STRUCTURAL NOTES, S3, DECLARES
 THIS AS A PARTIALLY ENCLOSED BUILDING.
  
 THE NOTE STATING THAT THE CAR WAS BAY IS
 OPEN IS ACKNOWLEDGED. PLEASE PROVIDE
 CALCULATIONS AS PER DEFINITION OF
 PARTIALLY ENCLOSED.
  
 ALSO NOTE THAT THE ARCHITECT ON A5
 DECLARES AN INTERNAL COEFFICIENT OF
 -.18, WHICH INDICATES AN ENCLOSED
 BUILDING.IF THE ENGINEER IS CORRECT IN
 DETERMINING THAT THIS IS A PARTIALLY
 ENCLOSED BUILDING, REVISE A5.THE TWO
 DESIGN PROFESSIONALS SHOULD BE USING THE
 SAME DESIGN ASSUMPTIONS.
  
 THE ARCHITECT INDICATES ON A5 THAT ALL
 OPENINGS INCLUDING THE ENTRY/EXIT OF THE
 CAR WASH TUNNEL ARE TO BE PROTECTED.
 THE ELEVATION STATES THAT WINDOW F WILL
 NOT HAVE GLASS BUT IT IS LISTED ON THE
 SCHEDULE A5 AS HAVING POSITIVE AND
 NEGATIVE PRESSURES.S4 SHOWS THESE
 WINDOWS AS IMPACT GLASS.WINDOW C, THE
 WINDOWS BETWEEN THE A/C SPACE AND THE
 CAR WASH TUNNEL, ARE NOT SHOWN ON THE
 WALL OPENING SCHEDULE.IF THE TUNNEL IS
 PARTIALLY ENCLOSED, THESE WINDOWS WILL
 BE SUBJECT TO PRESSURES AND POSSIBLY
 IMPACT.IF THE TUNNEL IS FULLY
 ENCLOSED, WINDOW F SHOULD HAVE GLASS AND
 THE ENGINEER SHOULD DECLARE AN ENCLOSED
 BUILDING.PLEASE MAKE THE VARIOUS
 SPECIFICATIONS CONSISTENT AND THE DESIGN
 CONSISTENT WITH THE ENCLOSURE CATEGORY.
  
 15-16.) ADDRESSED.
  
 17.)SUBMIT FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS FAC9B72 ALONG WITH THE
 EVALUATION OR TEST REPORT FOR THE
 FOLLOWING:
 PAIR OF LOUVERED DOORS
 OVERHEAD DOORS
 STOREFRONT DOORS, WINDOWS AND MULLIONS
 ROOF
 IMPACT PROTECTION IF APPROVED (SEE
 FOLLOWING COMMENT)
  
 PROVIDE FLORIDA STATE PRODUCT APPROVALS
 FOR ALL PRODUCTS, FAC9B72,
 WWW.FLORIDABUILDING.ORG.IF A STATE
 PRODUCT APPROVAL IS NOT AVAILABLE,
 PLEASE ADVISE AND A LOCAL PA WILL BE
 ISSUED.
  
 FOR THE GAF MODIFIED, THE PRODUCT
 APPROVAL IS INCOMPLETE.INCLUDE THE
 LAST PAGES.
  
 FOR THE GAF MODIFIED, CHOOSE THE
 APPROVED ASSEMBLY YOU ARE USING.
  
 IF ALL GLASS PRODUCTS ARE IMPACT, WHAT
 IS THE ROLL UP SHUTTER FOR?
  
 A6 AND A5 REQUIRE PRODUCT APPROVALS FOR
 THE OVERHEAD DOOR.A SHOP DRAWING
 STATING THAT PRODUCT APPROVALS ARE NOT
 REQUIRED WAS SUBMITTED.ADDRESS AND
 CLARIFY WITH A RESPONSE LETTER IF
 NECESSARY.
  
 18.)SEE ATTACHED POLICY FOR MISSILE
 IMPACT PROTECTION, ITEM NUMBER 13.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.IF THE GLAZING IS
 NOT IMPACT, SUBMIT A PLAN FOLLOWING THE
 GUIDELINES.
  
 NOTE - ADDRESSED, ALL
 COMPONENTS & CLADDING IMPACT RESISTANT.
  
 19-23.)ADDRESSED.
  
 NEW COMMENTS:
  
 24.)PARKING IS TO COMPLY WITH CITY OF
 WEST PALM BEACH STANDARD, SEE ATTACHED.
  
 25.)SEPARATE PERMIT REQUIRED FOR THE
 WALL AT THE PROPERTY LINE.
  
 26.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED.