 FBC 2001 PLUMBING CODE PLAN REVIEW
 FBC 2001 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) SHT L-2 IRRIGATION NOTE #11, BACK
 FLOW PREVENTER SHALL BE INSTALLED BY
 LICENSED PLUMBING CONTRACTOR.
 2)SHOW LOCATION OF CONTROLLER.
 3)CLARIFY WATER SUPPLY, WELL OR CITY
 WATER.
 4)SEC 314.1 SPRINKLER HEADS SHALL BE ONE
 FOOT FROM BUILDING WALL.
 5)SHT A-1, TAB 403.1 MINIMUM FACILITIES,
 SHOW NUMBER OF EMPLOYEES AND CUSTOMERS
 FOR REST ROOM FACILITIES.
 6) CONTACT W P BEACH,WATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON OFFICE 561-822-2271
 E-MAIL [email protected]
 REQUIRMENTS FOE OIL AND WATER SEPERATOR.
 7)SHT P2.1SEC608 WATER SUPPLY TO CAR
 WASH EQUIPMENT, REQUIRES A BACK FLOW
 PREVENTER. (RPZV)
 8)PLUMBING NOTE #15, DISSIMULAR METALS
 SEPERATION. DIELETRIC COUPLING OR NIPPLE
 9)WATER RISER:WATER SHOCK ARRESTORS,TO
 BE LOCATED AT THE END OF EACH RUN OR
 BETWEEN THE LAST TWO FIXTURES.
 " NOT IN THE CEILING"
 END OF COMMENTS, QUESTIONS 561- 805-6692