| Plan Review Notes For Permit 05080948 |
| Permit Number |
05080948 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-10-01 00:00:00 | PAUL SCHMITZ | | | FBC 2001 PLUMBING CODE PLAN REVIEW | | | FBC 2001 CH 11, FL ACESSIBILITY CODE | | | DENIED | | | 1) SHT L-2 IRRIGATION NOTE #11, BACK | | | FLOW PREVENTER SHALL BE INSTALLED BY | | | LICENSED PLUMBING CONTRACTOR. | | | 2)SHOW LOCATION OF CONTROLLER. | | | 3)CLARIFY WATER SUPPLY, WELL OR CITY | | | WATER. | | | 4)SEC 314.1 SPRINKLER HEADS SHALL BE ONE | | | FOOT FROM BUILDING WALL. | | | 5)SHT A-1, TAB 403.1 MINIMUM FACILITIES, | | | SHOW NUMBER OF EMPLOYEES AND CUSTOMERS | | | FOR REST ROOM FACILITIES. | | | 6) CONTACT W P BEACH,WATERPLANT LAB | | | SUPERVISORINDUSTRIAL COORDINATOR, | | | LYNN MASSON OFFICE 561-822-2271 | | | E-MAIL [email protected] | | | REQUIRMENTS FOE OIL AND WATER SEPERATOR. | | | 7)SHT P2.1SEC608 WATER SUPPLY TO CAR | | | WASH EQUIPMENT, REQUIRES A BACK FLOW | | | PREVENTER. (RPZV) | | | 8)PLUMBING NOTE #15, DISSIMULAR METALS | | | SEPERATION. DIELETRIC COUPLING OR NIPPLE | | | 9)WATER RISER:WATER SHOCK ARRESTORS,TO | | | BE LOCATED AT THE END OF EACH RUN OR | | | BETWEEN THE LAST TWO FIXTURES. | | | " NOT IN THE CEILING" | | | END OF COMMENTS, QUESTIONS 561- 805-6692 |
|