Plan Review Notes
Plan Review Notes For Permit 05080948
Permit Number 05080948
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-23 00:00:00DENIED:
 1.PLAN SHEET A-6 INDICATES MECHANICAL
 EQUIPMENT LOCATED ON THE ROOF OF VARIOUS
 BUILDINGS.PLEASE NOTE PER 2001 FBC(M)
 306.5 EQUIPMENT LOCATED ON ELEVATED
 STRUCTURES AT A HEIGHT GREATER THAN 16
 FEET, A PERMANENT MEANS OF ACCESS IS
 REQUIRED.
  
 2.PLEASE PROVIDE ENERGY CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 400.
  
 3.ADDITIONAL PERMIT REQUIRED FOR
 WALK-IN COOLER.PLEASE PROVIDE
 MANUFACTURER'S INSTALLATION & SUBMITTAL
 DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.