| Plan Review Notes For Permit 05080948 |
| Permit Number |
05080948 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-14 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE PROVIDE MORE DETAILS AND | | | LOCATION OF REMOTE FUEL FILL STATION. | | | | | | 2) PLANS SHOW NEW PROPOSED UNDERGROUND | | | TANKS. MORE INFORMATION AND CUT SHEETS | | | ARE REQUIRED. | | | | | | 3) PLEASE PROVIDE FLAME SPREAD | | | INFORMATION FOR FABRIC SHELTER. | | | | | | 4) PLEASE ILLUSTRATE EXISTING FIRE | | | HYDRANT LOCATIONS CLOSEST TO PROPERTY. | | | | | | 5) ADDRESS NUMBER ON THE BUILDING IS | | | REQUIRED, AND SHALL BE A MINIMUM OF 6" | | | IN HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. | | | | | | 6) PLEASE SEE OTHER COMMENTS REGARDING | | | FS AND FAC REQUIREMENTS. | | | | | | 7) PLEASE CONTACT THE BUREAU OF FIRE | | | PREVENTION REGARDING KNOX BOX | | | APPLICATIONS. A KNOX BOX MAY BE REQUIRED | | | IF ACCESS BECOMES PROBLEMATIC, | | | PARTICULARLY AFTER NORMAL BUSINESS | | | HOURS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|