Plan Review Notes
Plan Review Notes For Permit 05080948
Permit Number 05080948
Review Stop E
Sequence Number 1
Notes
Date Text
2005-09-04 00:00:00************* UNSAT **************
  
  
 GENERAL COMMENT FOR ALL.
  
 1)NOTE: PLEASE SEE ALL TITLE BLOCKS ON
 PLANS SHALL CONTAIN ALL INFORMATION AS
 REQUIRED UNDER FAC 61G15-23.002, FAC
 61G1-16.004
 PLEASE SEE MISSING FIRM LICENSE NUMBER
 FOR CIVIL PLANS.
 PLEASE SEE ARCHITECTURAL. FIRMS TITLE
 BLOCKS SHALL CONTAIN THE PRINTED NAME
 AND LICENSE NUMBER FOR ARCHITECT OF
 RECORD.
 PLEASE SEE BLDG REVIEW COMMENTS
 PERTAINING TO SURVEY. SURVEY ATTACHED
 SHALL CONTAIN AN ORIGINAL SIGNATURE FROM
 SURVEYOR OF RECORD AS REQUIRED UDNER FS
 472.025, FAC 61G17-7.002
  
 ** PLEASE SEE ABOVE INFORMATION IS
 REQUIRED OF ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
 ** PLEASE KNOW TITLE BLOCK FOR FORMICA &
 ASSCOIATES IS NOT INCLUDED IN NOTES
 ABOVE.
 PLEASE SEE TITLE BLOCK FOR ARCHITECTURAL
 FIRM ON E-SHEETS NEEDS ABOVE AS
 MENTIONED.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS C-STORE?? CONVENIENCE? PLEASE
 CLARIFY. COULD NOT LOCATE ANY PLANS FOR
 SUCH STORE.
  
 ***ELECTRICAL REVIEW NOTES ***
  
 1)NOTE: PLEASE PROVIDE WIND LOADING
 INFORMATION FOR SITE LIGHITNG POLES AND
 FIXTURES. CALCULATIONS FOR THESE ARE
 REQUUIRED AT THIS TIME. MUST MEET FBC
 140 MPH MIN.
 THIS WILL BE REVIEWED BY STRUCTURAL
 REVIEWER WHEN SUBMITTED.
  
 2)NOTE: PLEASE PROVIDE AN EMERGENCY
 BATTERY BACK-UP TYOE OF LT FIXTURE IN
 MAIN EQUIPMENT RM. A WALL MOUNTED
 FIXTURE IS ACCEPTABLE.
 700.16, NFPA-101 7-9
  
 3)NOTE: PLEASE PROVIDE A NOTE WHICH WILL
 REQUIRED "SIGNAGE" AT DOORS TO EQUIPMENT
 ROOM. THE SIGNAGE WILL BE REQUIRED TO
 DENOTE THE SERVCICE DISCONNECTING MEANS
 AND LOCATION.
 PLEASE ALSO THAT A "KNOX BOX" MAY BE
 REQUIRED BY THE FIRE DEPT, IF MAINS ARE
 TO BE LOCATED INSIDE A LOCKED ENCLOSURE
 WITHOUT READY ACCESS. 230.70
  
 4)NOTE: PLEASE SEE MDP SHOWN CONTAINS
 MORE THAN SIX SPACES AS PERMITTED IN
 230.71. PLEASE SEE THAT A NOTE WILL BE
 REQUIRED ON PLANS THAT EQUIPMENT SHALL
 HAVE THE ADDTIONAL SPACES MADE FROM
 MANUFACTURE WITH A PERMANANT DEAD FRONT
 IN ORDER TO ALLEAVIATE THE ADDTION OF
 ADDITIONAL SERVICE MEANS OF DISCONNECT.
 PLEASE SEE THE OTHER OPTION, WOULD BE A
 MCB IN MDP.
  
 5)NOTE: PLEASE CLARIFY OCP SHOWN FEEDING
 MCC. MDP SHOWS 500A OCP FEEDING 400A
 RATED MCC.?
 PLEASE CORRLEATE 282.2A'S SHOWN ON MCC
 WITH AMERAGE ON MDP.
 KVA ADDED ON MDP FOR MCC SEEMS TO BE
 HIGHER THAN 282A'S?
 PLEASE SEE MDP SCHEDULE SHOWS FEEDERS AS
 #2 AWG?
 PLEASE SEE RISER SHOWS FEEDERS AS
 PARALLEL 3/0'S. PLEASE SEE PARALLEL
 3/0'S ARE OK, DEPEDNING ON OCP FEEDING
 MCC.
 PLEASE SEE #2'S ARE NOT RATED FOR OCP AS
 SHOWN.
 PLEASE SEE 240.4,310.16,215.5 FOR ABOVE
 COMMENTS.
  
 6)NOTE: PLEASE SEE MDP PANEL SCHEDULE
 MENTIONS"EQUIPMENT GROUNDING
 CONDUCTORS" FROM METER/FPL TO FIRST
 MEANS OF DISCONNECT. PLEASE SEE 250.6,
 250.24, EQUIPMENT GROUNDING CONDUCTORS
 AREONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 7)NOTE: PLEASE SEE FEEDERS ON THE
 LINE-SIDE OF PANEL "L"; ALSO LOAD-SIDE
 OF DISCONNECT LOCATED FROM T-1.
 PLEASE SEE A 225A OCPIS SHOWN TO PANEL
 "L", HOWEVER FEEDERS ARE ONLY RATED FOR
 150A'S. (1/0'S) 310.16, 240.4
  
 8)NOTE: PLEASE SEE 450.3(TABLE), MAX OCP
 OF 125% FOR T-2. (15A'S). PLEASE SEE 20A
 OCP IS SHOWN.
  
 9)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDG.
 IT IS NOTED THAT GRND ROD IS SHOWN,
 HOWEVER PLEASE SEE ANY COLD WATER PIPES
 (METAL) AND NEW FOOTER STEEL OF DEATCHED
 BLDG WILL ALSO BE TO BE PART OF THE
 GROUNDING ELECTRODE SYSTEM AT THAT
 LOCATION.
 250.50
  
 10)NOTE: PLEASE SEE POSSIBLE MECHANICAL
 COMMENTS WHICH MAY REQUIRE "WALK-IN
 COOLER TO BE UNDER SEPARATE PERMIT.
 NO CORRECTION NEEDED FOR ELECTRICAL.
  
 11)NOTE: PLEASE INDICATE IF ALL
 CONTINUOUS LOADS AND LARGEST MOTORS
 LOADS ARE ALREADY SHOWN AT 125% ? IF
 NOT, PLEASE ADJUST CALCULATIONS.
 PLEASE CLARIFY IF THEY ARE.
 215.3,230.42 ETC.
  
 PLEASE SEE ANY POSSIBEL COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTIATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REWVIEW
 561-805-6717
 [email protected]