| 2005-09-04 00:00:00 | ************* UNSAT ************** |
| | |
| | |
| | GENERAL COMMENT FOR ALL. |
| | |
| | 1)NOTE: PLEASE SEE ALL TITLE BLOCKS ON |
| | PLANS SHALL CONTAIN ALL INFORMATION AS |
| | REQUIRED UNDER FAC 61G15-23.002, FAC |
| | 61G1-16.004 |
| | PLEASE SEE MISSING FIRM LICENSE NUMBER |
| | FOR CIVIL PLANS. |
| | PLEASE SEE ARCHITECTURAL. FIRMS TITLE |
| | BLOCKS SHALL CONTAIN THE PRINTED NAME |
| | AND LICENSE NUMBER FOR ARCHITECT OF |
| | RECORD. |
| | PLEASE SEE BLDG REVIEW COMMENTS |
| | PERTAINING TO SURVEY. SURVEY ATTACHED |
| | SHALL CONTAIN AN ORIGINAL SIGNATURE FROM |
| | SURVEYOR OF RECORD AS REQUIRED UDNER FS |
| | 472.025, FAC 61G17-7.002 |
| | |
| | ** PLEASE SEE ABOVE INFORMATION IS |
| | REQUIRED OF ALL SHEETS AND FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | ** PLEASE KNOW TITLE BLOCK FOR FORMICA & |
| | ASSCOIATES IS NOT INCLUDED IN NOTES |
| | ABOVE. |
| | PLEASE SEE TITLE BLOCK FOR ARCHITECTURAL |
| | FIRM ON E-SHEETS NEEDS ABOVE AS |
| | MENTIONED. |
| | |
| | 2)NOTE: PLEASE SEE PERMIT APPLICATION |
| | MENTIONS C-STORE?? CONVENIENCE? PLEASE |
| | CLARIFY. COULD NOT LOCATE ANY PLANS FOR |
| | SUCH STORE. |
| | |
| | ***ELECTRICAL REVIEW NOTES *** |
| | |
| | 1)NOTE: PLEASE PROVIDE WIND LOADING |
| | INFORMATION FOR SITE LIGHITNG POLES AND |
| | FIXTURES. CALCULATIONS FOR THESE ARE |
| | REQUUIRED AT THIS TIME. MUST MEET FBC |
| | 140 MPH MIN. |
| | THIS WILL BE REVIEWED BY STRUCTURAL |
| | REVIEWER WHEN SUBMITTED. |
| | |
| | 2)NOTE: PLEASE PROVIDE AN EMERGENCY |
| | BATTERY BACK-UP TYOE OF LT FIXTURE IN |
| | MAIN EQUIPMENT RM. A WALL MOUNTED |
| | FIXTURE IS ACCEPTABLE. |
| | 700.16, NFPA-101 7-9 |
| | |
| | 3)NOTE: PLEASE PROVIDE A NOTE WHICH WILL |
| | REQUIRED "SIGNAGE" AT DOORS TO EQUIPMENT |
| | ROOM. THE SIGNAGE WILL BE REQUIRED TO |
| | DENOTE THE SERVCICE DISCONNECTING MEANS |
| | AND LOCATION. |
| | PLEASE ALSO THAT A "KNOX BOX" MAY BE |
| | REQUIRED BY THE FIRE DEPT, IF MAINS ARE |
| | TO BE LOCATED INSIDE A LOCKED ENCLOSURE |
| | WITHOUT READY ACCESS. 230.70 |
| | |
| | 4)NOTE: PLEASE SEE MDP SHOWN CONTAINS |
| | MORE THAN SIX SPACES AS PERMITTED IN |
| | 230.71. PLEASE SEE THAT A NOTE WILL BE |
| | REQUIRED ON PLANS THAT EQUIPMENT SHALL |
| | HAVE THE ADDTIONAL SPACES MADE FROM |
| | MANUFACTURE WITH A PERMANANT DEAD FRONT |
| | IN ORDER TO ALLEAVIATE THE ADDTION OF |
| | ADDITIONAL SERVICE MEANS OF DISCONNECT. |
| | PLEASE SEE THE OTHER OPTION, WOULD BE A |
| | MCB IN MDP. |
| | |
| | 5)NOTE: PLEASE CLARIFY OCP SHOWN FEEDING |
| | MCC. MDP SHOWS 500A OCP FEEDING 400A |
| | RATED MCC.? |
| | PLEASE CORRLEATE 282.2A'S SHOWN ON MCC |
| | WITH AMERAGE ON MDP. |
| | KVA ADDED ON MDP FOR MCC SEEMS TO BE |
| | HIGHER THAN 282A'S? |
| | PLEASE SEE MDP SCHEDULE SHOWS FEEDERS AS |
| | #2 AWG? |
| | PLEASE SEE RISER SHOWS FEEDERS AS |
| | PARALLEL 3/0'S. PLEASE SEE PARALLEL |
| | 3/0'S ARE OK, DEPEDNING ON OCP FEEDING |
| | MCC. |
| | PLEASE SEE #2'S ARE NOT RATED FOR OCP AS |
| | SHOWN. |
| | PLEASE SEE 240.4,310.16,215.5 FOR ABOVE |
| | COMMENTS. |
| | |
| | 6)NOTE: PLEASE SEE MDP PANEL SCHEDULE |
| | MENTIONS"EQUIPMENT GROUNDING |
| | CONDUCTORS" FROM METER/FPL TO FIRST |
| | MEANS OF DISCONNECT. PLEASE SEE 250.6, |
| | 250.24, EQUIPMENT GROUNDING CONDUCTORS |
| | AREONLY INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 7)NOTE: PLEASE SEE FEEDERS ON THE |
| | LINE-SIDE OF PANEL "L"; ALSO LOAD-SIDE |
| | OF DISCONNECT LOCATED FROM T-1. |
| | PLEASE SEE A 225A OCPIS SHOWN TO PANEL |
| | "L", HOWEVER FEEDERS ARE ONLY RATED FOR |
| | 150A'S. (1/0'S) 310.16, 240.4 |
| | |
| | 8)NOTE: PLEASE SEE 450.3(TABLE), MAX OCP |
| | OF 125% FOR T-2. (15A'S). PLEASE SEE 20A |
| | OCP IS SHOWN. |
| | |
| | 9)NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDG. |
| | IT IS NOTED THAT GRND ROD IS SHOWN, |
| | HOWEVER PLEASE SEE ANY COLD WATER PIPES |
| | (METAL) AND NEW FOOTER STEEL OF DEATCHED |
| | BLDG WILL ALSO BE TO BE PART OF THE |
| | GROUNDING ELECTRODE SYSTEM AT THAT |
| | LOCATION. |
| | 250.50 |
| | |
| | 10)NOTE: PLEASE SEE POSSIBLE MECHANICAL |
| | COMMENTS WHICH MAY REQUIRE "WALK-IN |
| | COOLER TO BE UNDER SEPARATE PERMIT. |
| | NO CORRECTION NEEDED FOR ELECTRICAL. |
| | |
| | 11)NOTE: PLEASE INDICATE IF ALL |
| | CONTINUOUS LOADS AND LARGEST MOTORS |
| | LOADS ARE ALREADY SHOWN AT 125% ? IF |
| | NOT, PLEASE ADJUST CALCULATIONS. |
| | PLEASE CLARIFY IF THEY ARE. |
| | 215.3,230.42 ETC. |
| | |
| | PLEASE SEE ANY POSSIBEL COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM |
| | SETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | ONE SET OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESTIATE IN CONTACTING |
| | THIS OFFICE. |
| | |