| 2005-09-12 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 |
| | |
| | 3.)ADDITIONAL FEES DUE (RADON).SEE |
| | ATTACHED. |
| | |
| | 4.)SUBMIT SEPARATE PERMIT APPLICATIONS |
| | FOR THE SERVICE BUILDING AND DUMPSTER |
| | ENCLOSURE/RECYCLING BIN.SEPARATE |
| | PERMIT NUMBERS WILL BE ISSUED FOR |
| | INSPECTION AND RECORD KEEPING PURPOSES. |
| | |
| | 5.)THE PROPOSED IMPROVEMENT CROSSES |
| | OVER THE PROPERTY LINES.A UNITY OF |
| | TITLE IS REQUIRED. |
| | |
| | 6.)THE SURVEY IS NOT ENTIRELY LEGIBLE. |
| | ALSO PLEASE PROVIDE A SIGNATURE (NOT A |
| | STAMP).PLEASE PROVIDE NEW COPIES. |
| | |
| | 7.)PROVIDE A SOILS INVESTIGATION |
| | REPORT, FBC1804.2.2. |
| | |
| | 8.)ENERGY CALCS REQUIRED. |
| | |
| | 9.)SEE FAC61G1-16.004.THE |
| | ARCHITECT?S PRINTED NAME IS REQUIRED. |
| | |
| | 10.)THE SEAL FOR THE LANDSCAPE |
| | ARCHITECT IS TO BE DATED, FS481.306, |
| | FAC61G10-11.010. |
| | |
| | 11.)THE RECYCLING BIN GATE CANNOT |
| | SWING OVER THE PROPERTY LINE, |
| | FBC3206.1.1. |
| | |
| | 12.)THE WIND DESIGN CRITERIA T-1 IS |
| | NOT CLEAR.GOVERNING CODES SECTION |
| | GIVES A "BASIC" WIND SPEED OF 120, WIND |
| | EXPOSURE B, "DESIGN" WIND SPEED OF 140, |
| | AND GENERAL NOTES, STRUCTURAL DESIGN |
| | CRITERIA ITEM 3 AND BUILDING DATA SHEET |
| | A5 GIVE A WIND SPEED OF 140, EXPOSURE C. |
| | SEE FBC1606.1.6.PROVIDE ALL |
| | INFORMATION REQUIRED BY FBC1606.1.7. |
| | |
| | 13.)DESIGN LOADS, T1, IS LACKING THE |
| | DESIGN PRESSURES FOR ZONE 3 GROSS WIND |
| | UPLIFT LOADS, AND ROOF DEAD LOAD IS |
| | INCOMPLETE. |
| | |
| | 14.)STRUCTURAL NOTES, S3, DECLARES |
| | THIS AS A PARTIALLY ENCLOSED BUILDING. |
| | |
| | 15.)ACCESSIBLE ROUTE FBC11-4.1.2(1) IS |
| | NOT CLEAR.THERE IS A PEDESTRIAN |
| | WALKWAY ON SP1 WHICH REFERS TO SECTION |
| | 3-SP2.HOW DOES THIS LEAD TO THE LOBBY? |
| | |
| | 16.)THE TOWEL CLEANING ROOM 108 IS TO |
| | HAVE A DOOR TO COMPLY WITH FBC1012.1.2. |
| | |
| | 17.)SUBMIT FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVALS FAC9B72 ALONG WITH THE |
| | EVALUATION OR TEST REPORT FOR THE |
| | FOLLOWING: |
| | PAIR OF LOUVERED DOORS |
| | OVERHEAD DOORS |
| | STOREFRONT DOORS, WINDOWS AND MULLIONS |
| | ROOF |
| | IMPACT PROTECTION IF APPROVED (SEE |
| | FOLLOWING COMMENT) |
| | |
| | 18.)SEE ATTACHED POLICY FOR MISSILE |
| | IMPACT PROTECTION, ITEM NUMBER 13.USE |
| | OF REMOVABLE SHUTTERS ON COMMERCIAL |
| | BUILDINGS MUST BE APPROVED BY THE |
| | BUILDING OFFICIAL.IF THE GLAZING IS |
| | NOT IMPACT, SUBMIT A PLAN FOLLOWING THE |
| | GUIDELINES. |
| | |
| | 19.)THE AWNINGS ARE TO COMPLY WITH |
| | FBC3106.2(1) AND (3). |
| | |
| | 20.)A SEPARATE PERMIT IS REQUIRED FOR |
| | THE AWNINGS. |
| | |
| | 21.)ROOF ZONE KEY, SHEET S3, DOES NOT |
| | INCLUDE A ZONE 3. |
| | |
| | 22.)THE FOOTERS FOR THE PERIMETER |
| | WALLS CANNOT ENCROACH THE PROPERTY LINE. |
| | REVISE DETAIL 7-S6 TO SHOW THE PROPERTY |
| | LINE. |
| | |
| | 23.)SHEET M2.01 PROVIDES A BUILDING |
| | HEIGHT OF <15 FT.BOTH BUILDINGS ARE |
| | OVER 20FT. |
| | |