Plan Review Notes
Plan Review Notes For Permit 05080948
Permit Number 05080948
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)ADDITIONAL FEES DUE (RADON).SEE
 ATTACHED.
  
 4.)SUBMIT SEPARATE PERMIT APPLICATIONS
 FOR THE SERVICE BUILDING AND DUMPSTER
 ENCLOSURE/RECYCLING BIN.SEPARATE
 PERMIT NUMBERS WILL BE ISSUED FOR
 INSPECTION AND RECORD KEEPING PURPOSES.
  
 5.)THE PROPOSED IMPROVEMENT CROSSES
 OVER THE PROPERTY LINES.A UNITY OF
 TITLE IS REQUIRED.
  
 6.)THE SURVEY IS NOT ENTIRELY LEGIBLE.
 ALSO PLEASE PROVIDE A SIGNATURE (NOT A
 STAMP).PLEASE PROVIDE NEW COPIES.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1804.2.2.
  
 8.)ENERGY CALCS REQUIRED.
  
 9.)SEE FAC61G1-16.004.THE
 ARCHITECT?S PRINTED NAME IS REQUIRED.
  
 10.)THE SEAL FOR THE LANDSCAPE
 ARCHITECT IS TO BE DATED, FS481.306,
 FAC61G10-11.010.
  
 11.)THE RECYCLING BIN GATE CANNOT
 SWING OVER THE PROPERTY LINE,
 FBC3206.1.1.
  
 12.)THE WIND DESIGN CRITERIA T-1 IS
 NOT CLEAR.GOVERNING CODES SECTION
 GIVES A "BASIC" WIND SPEED OF 120, WIND
 EXPOSURE B, "DESIGN" WIND SPEED OF 140,
 AND GENERAL NOTES, STRUCTURAL DESIGN
 CRITERIA ITEM 3 AND BUILDING DATA SHEET
 A5 GIVE A WIND SPEED OF 140, EXPOSURE C.
 SEE FBC1606.1.6.PROVIDE ALL
 INFORMATION REQUIRED BY FBC1606.1.7.
  
 13.)DESIGN LOADS, T1, IS LACKING THE
 DESIGN PRESSURES FOR ZONE 3 GROSS WIND
 UPLIFT LOADS, AND ROOF DEAD LOAD IS
 INCOMPLETE.
  
 14.)STRUCTURAL NOTES, S3, DECLARES
 THIS AS A PARTIALLY ENCLOSED BUILDING.
  
 15.)ACCESSIBLE ROUTE FBC11-4.1.2(1) IS
 NOT CLEAR.THERE IS A PEDESTRIAN
 WALKWAY ON SP1 WHICH REFERS TO SECTION
 3-SP2.HOW DOES THIS LEAD TO THE LOBBY?
  
 16.)THE TOWEL CLEANING ROOM 108 IS TO
 HAVE A DOOR TO COMPLY WITH FBC1012.1.2.
  
 17.)SUBMIT FLORIDA STATE OR LOCAL
 PRODUCT APPROVALS FAC9B72 ALONG WITH THE
 EVALUATION OR TEST REPORT FOR THE
 FOLLOWING:
 PAIR OF LOUVERED DOORS
 OVERHEAD DOORS
 STOREFRONT DOORS, WINDOWS AND MULLIONS
 ROOF
 IMPACT PROTECTION IF APPROVED (SEE
 FOLLOWING COMMENT)
  
 18.)SEE ATTACHED POLICY FOR MISSILE
 IMPACT PROTECTION, ITEM NUMBER 13.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.IF THE GLAZING IS
 NOT IMPACT, SUBMIT A PLAN FOLLOWING THE
 GUIDELINES.
  
 19.)THE AWNINGS ARE TO COMPLY WITH
 FBC3106.2(1) AND (3).
  
 20.)A SEPARATE PERMIT IS REQUIRED FOR
 THE AWNINGS.
  
 21.)ROOF ZONE KEY, SHEET S3, DOES NOT
 INCLUDE A ZONE 3.
  
 22.)THE FOOTERS FOR THE PERIMETER
 WALLS CANNOT ENCROACH THE PROPERTY LINE.
 REVISE DETAIL 7-S6 TO SHOW THE PROPERTY
 LINE.
  
 23.)SHEET M2.01 PROVIDES A BUILDING
 HEIGHT OF <15 FT.BOTH BUILDINGS ARE
 OVER 20FT.
  