Plan Review Notes
Plan Review Notes For Permit 05080917
Permit Number 05080917
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- ENGINEER'S DRAWING AND SURVEY DON'T
 MATCH. ENGINEER DRAWING SHOWS A NOTCH
 AND SURVEY SHOWS A STRAIGHT ROOF LINE.
 CLARIFY/REVISE AS REQUIRED.
  
 3- CLARIFY WHY ARE THERE TWO DIFFERENT
 CONNECTIONS AT BOTTOM OF POSTS.
  
 4- PROVIDE UPLIFT CALCULATIONS FOR POST
 RESTING ON 2'X3' FOOTERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 5- DRAWINGS NEED:
 A) POST SPACING.
 B) POST CONNECTION AT TOP.
 C) DIMENSIONS FOR NOTCHED AREA.
 D) BRACING AT NOTCHED AREA END.
 E) SPACING OF TRUSSED MEMBERS.
 F) SPACING OF STEEL PLATES THAT ARE
 ATTACHED TO THE WALL.
 G) CORNER STEEL PLATE AT NOTCHED AREA.
 H) COMPLETE SPECIFICATIONS FOR COLUMNS.
 I) SPECIFY HOW MUCH EMBEDMENT IS REQ'D
 FOR THE 3/8" SLEEVE ANCHORS INTO THE
 CONCRETE BLOCK WALL.
  
 6- CLARIFY WHY SOME TRUSSED MEMBERS ARE
 SHOWN WITH VERTICAL WEBS AND SOME ARE
 WITH VERTICAL AND DIAGONAL WEBS.
  
 7- CLARIFY WHY END MEMBER AT NOTCHED
 AREA IS NOT BRACED.
  
 8- HOW IS 2ND MEMBER BY NOTCHED AREA
 BRACED.
  
 SECTION 104.2.1.2 CITY AMENDMENTS TO FBC
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.