2005-09-16 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- STRUCTURAL NOTE BELOW GRAVITY LOAD
 NEEDS TO BE MORE SPECIFIC. SPECIFY ALL
 DEAD LOADS. GENERAL SPECIFICATION SAYING
 "ALL DEAD LOADS PLUS 30PSF LIVE LOAD"
 DOESN'T PROVIDE CLEAR INFORMATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 3- UPDATE YEAR REFERENCED FOR ACI
 STANDARD. SEE CHAPTER 35 FBC 2001 FOR
 PROPER EDITION TO BE USED.
  
 4- PLANS NEED TO SPECIFY ROOF
 MATERIAL."NEW ROOF TO MATCH EXISTING"
 DOESN'T PROVIDE ANY INFORMATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ROOF TO BE INSTALLED.
  
 B) SIMPSON CONNECTORS SPECIFIED ON
 PLANS.
  
 6- CLARIFY IF USING PREFABRICATED ROOF
 TRUSSES OR CONVENTIONAL HAND FRAMING.
 SECTION #3 CALLS FOR TRUSSES WHILE
 FRAMING PLAN CALLS FOR 2X6 RAFTERS.
 REVISE PLANS AS REQUIRED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 7- DETAIL #1: FOOTING NEEDS TO BE 12"
 BELOW GRADE AS REQUIRED BY SEC. 1804.1.3
 FBC 2001. INDICATE LINE OF FINISH GRADE.
  
 8- PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS FOR TOP AND BOTTOM
 CONNECTIONS OF STEEL COLUMNS NEXT TO THE
 EXTERIOR WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.