| 2008-10-20 09:21:26 | | | | ** PROVISO** | | | | | | | | | | | | | | | 1) NOTE: THE LIGHTING LEVELS AT THE STAIRS ARE REQUIRED | | | TO MEET 10FT CANDLES UNDER NORMAL AND ARE PERMITTED TO | | | GO DOWN TO A MINIMUM OF 1FT CANDLE UNDER EMERGENCY. | | | NFPA-101 2003, 7.8.1.3, 7.9.2.1, .2.2 | | | THE OWNER SUBMITTED SPEC SHEETS THAT BATTERY BACK UP | | | BALLAST WILL BE ADDED TO EXISTING FIXTURES TO ACHIEVE | | | LEVELS UNDER EMERGENCY CONDITIONS. | | | THE PLANS WILL NEED TO BE REVISED BEFORE FINAL TO | | | INDICATE THE ACTUAL FIXTURES WHICH THESE UNITS WERE | | | ADDED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|