 1) NOTE: THE LIGHTING LEVELS AT THE STAIRS ARE REQUIRED
 TO MEET 10FT CANDLES UNDER NORMAL AND ARE PERMITTED TO
 GO DOWN TO A MINIMUM OF 1FT CANDLE UNDER EMERGENCY.
 NFPA-101 2003, 7.8.1.3, 7.9.2.1, .2.2
 THE OWNER SUBMITTED SPEC SHEETS THAT BATTERY BACK UP
 BALLAST WILL BE ADDED TO EXISTING FIXTURES TO ACHIEVE
 LEVELS UNDER EMERGENCY CONDITIONS.
 THE PLANS WILL NEED TO BE REVISED BEFORE FINAL TO
 INDICATE THE ACTUAL FIXTURES WHICH THESE UNITS WERE
 ADDED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  