| 2008-04-29 08:44:26 | ** DENIEDREVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW DATED |
| | 9/22/07 ARE STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS WITH RESPECT TO |
| | PHOTO-METRICS FROM SEPTEMBER 22ND, 2007 HAVE NOT BEEN |
| | ADDRESSED. |
| | PLEASE SUBMIT PHOTO-METRICS FOR STAIR WAY UNDER NORMAL |
| | CONDITIONS SHOWING A MINIMUM OF 10FT CANDLES AND TO A |
| | MINIMUM OF 1FT CANDLES UNDER EMERGENCY. |
| | PLEASE SEE LS CODE, NFPA-101 7.8.1.3, 7.9.2.2. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |