| Date |
Text |
| 2006-04-29 00:00:00 | PAUL SCHMITZ |
| | [email protected] |
| | FBC2001 FUEL GAS CODEPLAN REVIEW |
| | FBC 2001 PLUMBING CODEPLAN REVIEW |
| | FBC 2001 FL ACESSIBILITY CODE PLAN |
| | REVIEW |
| | UNSAT |
| | PREVIOUS COMMENT (1),(5) NOT ADDRESSED. |
| | |
| | (1)SECTION 11-4 |
| | ACCESSIBLE ELEMENTS AND |
| | SPACES:SCOPE AND TECHNICAL REQUIREMENTS |
| | ?11-4.1 MINIMUM REQUIREMENTS. |
| | ?11-4.1.1 APPLICATION. |
| | ?11-4.1.1(1) GENERAL. THIS CODE |
| | ESTABLISHES THE MINIMUM STANDARDS FOR |
| | THE ACCESSIBILITY OF BUILDINGS AND |
| | FACILITIES BUILT OR ALTERED WITHIN |
| | THE STATE. |
| | ?11-4.1.1(1)(A) ALL AREAS OF NEWLY |
| | DESIGNED OR NEWLY CONSTRUCTED |
| | BUILDINGS AND FACILITIES REQUIRED |
| | TO BE ACCESSIBLE BY ?11-4.1.2 AND |
| | ?11-4.1.3 AND ALTERED PORTIONS OF |
| | EXISTING BUILDINGS AND FACILITIES |
| | REQUIRED TO BE ACCESSIBLE BY |
| | ?11-4.1.6 SHALL COMPLY WITH THIS CODE, |
| | ?11-4.1 THROUGH ?11-4.35, UNLESS |
| | OTHERWISE PROVIDED IN THIS |
| | SECTION OR AS MODIFIED IN A |
| | SPECIAL APPLICATION SECTION. |
| | |
| | (SPECIFICALY) BREAK ROOM SINK |
| | ?11-4.24 SINKS. |
| | ?11-4.24.1 GENERAL. SINKS REQUIRED TO |
| | BE ACCESSIBLE BY ?11-4.1 SHALL |
| | COMPLY WITH ?11-4.24. |
| | ?11-4.24.2 HEIGHT. SINKS SHALL BE |
| | MOUNTED WITH THE COUNTER OR RIM NO |
| | HIGHER THAN 34 IN. (865 MM) ABOVE THE |
| | FINISH FLOOR. |
| | ?11-4.24.3 KNEE CLEARANCE. KNEE |
| | CLEARANCE THAT IS AT LEAST 27 IN. (685 |
| | MM) HIGH, 30 IN. (760 MM) WIDE, AND 19 |
| | IN (485 MM) DEEP SHALL BE |
| | PROVIDED UNDERNEATH SINKS. |
| | ?11-4.24.4 DEPTH. EACH SINK SHALL BE A |
| | MAXIMUM OF 6-1/2 IN (165 MM) |
| | DEEP. |
| | ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE AT LEAST 30 IN. BY 48 |
| | IN. (760 MM BY 1220 MM) COMPLYING WITH |
| | 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH.THE CLEAR FLOOR SPACE SHALL |
| | BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 IN. (485 MM) |
| | UNDERNEATH THE SINK (SEE FIGURE |
| | 11-32). |
| | ?11-4.24.6 EXPOSED PIPES AND SURFACES. |
| | HOT WATER AND DRAIN PIPES EXPOSED |
| | UNDER SINKS SHALL BE INSULATED OR |
| | OTHERWISE CONFIGURED SO AS TO PROTECT |
| | AGAINST CONTACT.THERE SHALL BE NO |
| | SHARP OR ABRASIVE SURFACES UNDER |
| | SINKS. |
| | ?11-4.24.7 FAUCETS. FAUCETS SHALL |
| | COMPLY WITH ?11-4.27.4.LEVER- |
| | OPERATED, PUSH-TYPE, TOUCH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED MECHANISMS |
| | ARE ACCEPTABLE DESIGNS. |
| | |
| | |
| | 5) SHT A-5 WATER RISER DIAGRAM: |
| | SHOWS AIR CHAMBERS AT THE TOP OF WATER |
| | RISERS. COMPLY WITH SEC 604.9 |
| | |
| | ?P604.9 WATER HAMMER. THE FLOW VELOCITY |
| | OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE |
| | POSSIBILITY OF WATER HAMMER.A WATER- |
| | HAMMER ARRESTOR SHALL BE INSTALLED WHERE |
| | QUICK-CLOSING VALVES ARE UTILIZED, |
| | UNLESS OTHERWISE APPROVED.THE ARRESTOR |
| | SHALL BE LOCATED WITHIN AN |
| | EFFECTIVE RANGE OF THE QUICK-CLOSING |
| | VALVE.WATER-HAMMER ARRESTORS SHALL |
| | CONFORM TO ASSE 1010.ACCESS SHALL BE |
| | PROVIDED TO WATER-HAMMER ARRESTORS. |
| | |
| | NEW COMMENTS |
| | SHT A-2,A-5 DELETED SHOWER |
| | ?P704.5 DEAD ENDS. IN THE INSTALLATION |
| | OR REMOVAL OF ANY PART OF A |
| | DRAINAGE SYSTEM, DEAD ENDS SHALL BE |
| | PROHIBITED. |
| | WATER LINES FOR FUTURE SHOWER CAPED AT |
| | TEE. |
| | END OF COMMENTS QUESTIONS 561`-805-6692 |