Plan Review Notes
Plan Review Notes For Permit 05080727
Permit Number 05080727
Review Stop P
Sequence Number 2
Notes
Date Text
2006-04-29 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 UNSAT
 PREVIOUS COMMENT (1),(5) NOT ADDRESSED.
  
 (1)SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1 APPLICATION.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 ?11-4.1.1(1)(A) ALL AREAS OF NEWLY
 DESIGNED OR NEWLY CONSTRUCTED
 BUILDINGS AND FACILITIES REQUIRED
 TO BE ACCESSIBLE BY ?11-4.1.2 AND
 ?11-4.1.3 AND ALTERED PORTIONS OF
 EXISTING BUILDINGS AND FACILITIES
 REQUIRED TO BE ACCESSIBLE BY
 ?11-4.1.6 SHALL COMPLY WITH THIS CODE,
 ?11-4.1 THROUGH ?11-4.35, UNLESS
 OTHERWISE PROVIDED IN THIS
 SECTION OR AS MODIFIED IN A
 SPECIAL APPLICATION SECTION.
  
 (SPECIFICALY) BREAK ROOM SINK
 ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
  
 5) SHT A-5 WATER RISER DIAGRAM:
 SHOWS AIR CHAMBERS AT THE TOP OF WATER
 RISERS. COMPLY WITH SEC 604.9
  
 ?P604.9 WATER HAMMER. THE FLOW VELOCITY
 OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER.A WATER-
 HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED,
 UNLESS OTHERWISE APPROVED.THE ARRESTOR
 SHALL BE LOCATED WITHIN AN
 EFFECTIVE RANGE OF THE QUICK-CLOSING
 VALVE.WATER-HAMMER ARRESTORS SHALL
 CONFORM TO ASSE 1010.ACCESS SHALL BE
 PROVIDED TO WATER-HAMMER ARRESTORS.
  
 NEW COMMENTS
 SHT A-2,A-5 DELETED SHOWER
 ?P704.5 DEAD ENDS. IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED.
 WATER LINES FOR FUTURE SHOWER CAPED AT
 TEE.
 END OF COMMENTS QUESTIONS 561`-805-6692