| Date |
Text |
| 2005-08-20 00:00:00 | PAUL SCHMITZ, |
| | PLUMBING PLAN REVIEW EXAMINER |
| | [email protected] |
| | |
| | FBC 2001 DENIED |
| | |
| | (1)SECTION 11-4 |
| | ACCESSIBLE ELEMENTS AND |
| | SPACES:SCOPE AND TECHNICAL REQUIREMENTS |
| | ?11-4.1 MINIMUM REQUIREMENTS. |
| | ?11-4.1.1 APPLICATION. |
| | ?11-4.1.1(1) GENERAL. THIS CODE |
| | ESTABLISHES THE MINIMUM STANDARDS FOR |
| | THE ACCESSIBILITY OF BUILDINGS AND |
| | FACILITIES BUILT OR ALTERED WITHIN |
| | THE STATE. |
| | ?11-4.1.1(1)(A) ALL AREAS OF NEWLY |
| | DESIGNED OR NEWLY CONSTRUCTED |
| | BUILDINGS AND FACILITIES REQUIRED |
| | TO BE ACCESSIBLE BY ?11-4.1.2 AND |
| | ?11-4.1.3 AND ALTERED PORTIONS OF |
| | EXISTING BUILDINGS AND FACILITIES |
| | REQUIRED TO BE ACCESSIBLE BY |
| | ?11-4.1.6 SHALL COMPLY WITH THIS CODE, |
| | ?11-4.1 THROUGH ?11-4.35, UNLESS |
| | OTHERWISE PROVIDED IN THIS |
| | SECTION OR AS MODIFIED IN A |
| | SPECIAL APPLICATION SECTION. |
| | |
| | (2) 11-4.22 TOILET ROOMS. |
| | ?11-4.22.1 MINIMUM NUMBER. TOILET |
| | FACILITIES REQUIRED TO BE ACCESSIBLE |
| | BY ?11-4.1 SHALL COMPLY WITH ?11-4.22. |
| | ACCESSIBLE TOILET ROOMS SHALL BE |
| | ON AN ACCESSIBLE ROUTE. |
| | ?11-4.22.2 DOORS. |
| | ?11-4.22.2(1) ALL DOORS TO |
| | ACCESSIBLE TOILET ROOMS SHALL COMPLY |
| | WITH |
| | ?11-4.13.DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE REQUIRED |
| | FOR ANY FIXTURE. |
| | |
| | (3) ?11-4.23.3 CLEAR FLOOR SPACE. THE |
| | ACCESSIBLE FIXTURES AND CONTROLS |
| | REQUIRED IN ?11-4.23.4, ?11-4.23.5, |
| | ?11-4.23.6, ?11-4.23.7, ?11-4.23.8, |
| | AND ?11-4.23.9 SHALL BE ON AN |
| | ACCESSIBLE ROUTE.AN UNOBSTRUCTED |
| | TURNING |
| | SPACE COMPLYING WITH ?11-4.2.3 SHALL |
| | BE PROVIDED WITHIN AN ACCESSIBLE |
| | BATHROOM.THE CLEAR FLOOR SPACES AT |
| | FIXTURES AND CONTROLS, THE |
| | ACCESSIBLE ROUTE, AND THE TURNING |
| | SPACE MAY OVERLAP. |
| | |
| | (4)?11-4.21 SHOWER STALLS. |
| | ?11-4.21.1 GENERAL. ACCESSIBLE SHOWER |
| | STALLS SHALL COMPLY WITH ?11-4.21. |
| | ?11-4.21.2 SIZE AND CLEARANCES. EXCEPT |
| | AS SPECIFIED IN ?11-9.1.2, SHOWER |
| | STALL SIZE AND CLEAR FLOOR SPACE SHALL |
| | COMPLY WITH FIGURE 11-35(A) OR |
| | FIGURE 11-35(B).THE SHOWER STALL IN |
| | FIGURE 11-35(A) SHALL BE 36 |
| | INCHES BY 36 INCHES (915 MM BY 915 |
| | MM).SHOWER STALLS REQUIRED BY |
| | ?11-9.1.2 SHALL COMPLY WITH FIGURE |
| | 11-57(A) OR FIGURE 11-57(B).THE |
| | SHOWER STALL IN FIGURE 11-35(B) WILL |
| | FIT INTO THE SPACE REQUIRED FOR A |
| | BATHTUB. |
| | (5) SHT A-5 WATER RISER DIAGRAM: |
| | SHOWS AIR CHAMBERS AT THE TOP OF WATER |
| | RISERS. COMPLY WITH SEC 604.9 |
| | |
| | ?P604.9 WATER HAMMER. THE FLOW VELOCITY |
| | OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE |
| | POSSIBILITY OF WATER HAMMER.A WATER- |
| | HAMMER ARRESTOR SHALL BE INSTALLED WHERE |
| | QUICK-CLOSING VALVES ARE UTILIZED, |
| | UNLESS OTHERWISE APPROVED.THE ARRESTOR |
| | SHALL BE LOCATED WITHIN AN |
| | EFFECTIVE RANGE OF THE QUICK-CLOSING |
| | VALVE.WATER-HAMMER ARRESTORS SHALL |
| | CONFORM TO ASSE 1010.ACCESS SHALL BE |
| | PROVIDED TO WATER-HAMMER ARRESTORS. |
| | END OF COMMENTS |