| 2005-08-16 00:00:00 | ************* UNSAT ************** |
| | |
| | 1)NOTE: PLEASE CORRELATE PLANS WITH |
| | PERMIT APPLICATION AND PROPOSED WORK. |
| | PLEASE SEE PERMIT APPLICATION MENTIONS |
| | TO BUILD A NEW MEZZ STORAGE AREA, |
| | HOWEVER ELECTRICAL PLANS SHOWS NEW BATH, |
| | KITCHEN AREA, AND ALSO MENTIONS EXSITING |
| | TANKLESS WATER HEATERS? |
| | 215.5 |
| | PLEASE SEE OTHER COMMENTS FROM OTHER |
| | TRADES. |
| | |
| | 2)NOTE: PLEASE CORRELATE INFORMATION |
| | SUBMITTED FOR TANKLESS WATER HEATERS. |
| | PLEASE SEE ELECTRICAL PLANS SHOWSTWO |
| | EXISTING (3KW) UNITS, PANEL SCHEDULE |
| | SHOWS A 6KW AND A 3KW AND PLAUMB PLANS |
| | INDICATE A 3KW AND 6KW? |
| | PLEASE ALSO INDICATE A DISCONNECTING |
| | MEANS FOR UNITS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 2002 NEC 210.8B3, IN |
| | KITCHENS IN OTHER THAN DWELLING UNITS |
| | WHICH REQUIRES ALL 15- AND 20-AMPERE, |
| | 125-VOLT RECEPTACLES IN NONDWELLING-TYPE |
| | KITCHENS TO BE GFCI PROTECTED. THIS |
| | REQUIREMENT APPLIES TO EACH AND EVERY |
| | 15- AND 20-AMPERE, 125-VOLT KITCHEN |
| | RECEPTACLE, WHETHER OR NOT THE |
| | RECEPTACLE SERVES COUNTERTOP APPLIANCES. |
| | |
| | PLEASE ADJUST. |
| | |
| | 4)NOTE: PLEASE SEE 700.12E FOR |
| | CIRCUITING OF EM/EXT LTS. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | PLEASE SEE PLANS . |
| | |
| | 5)NOTE: PLEASE SEE ALLL RECEPTS WITHIN |
| | 6' OF SINKS SHALL BE GFI/GFI PROTECTED. |
| | PLEASE ALSO SEE ALL RECEPTS SHALL ALSO |
| | BE GFI/GFI PROTECTED. |
| | 210.8B1 |
| | |
| | 6)NOTE: PLEASE VERIFY OCP SHOWN FOR 10KW |
| | HEATSTRIP IN AHU. |
| | PLEASE SEE MIN OCP 125% 424.3B |
| | THIS IS ONLY A NOTE:. |
| | |
| | 7)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES PANEL AS MLO, HOWEVER PARTIAL |
| | RISER DIAGRAM SHOWS PANEL AS 150 MCB? |
| | PLEASE CORRLELATE. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE SET OF OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVEIW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |