Plan Review Notes
Plan Review Notes For Permit 05080727
Permit Number 05080727
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-16 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE CORRELATE PLANS WITH
 PERMIT APPLICATION AND PROPOSED WORK.
 PLEASE SEE PERMIT APPLICATION MENTIONS
 TO BUILD A NEW MEZZ STORAGE AREA,
 HOWEVER ELECTRICAL PLANS SHOWS NEW BATH,
 KITCHEN AREA, AND ALSO MENTIONS EXSITING
 TANKLESS WATER HEATERS?
 215.5
 PLEASE SEE OTHER COMMENTS FROM OTHER
 TRADES.
  
 2)NOTE: PLEASE CORRELATE INFORMATION
 SUBMITTED FOR TANKLESS WATER HEATERS.
 PLEASE SEE ELECTRICAL PLANS SHOWSTWO
 EXISTING (3KW) UNITS, PANEL SCHEDULE
 SHOWS A 6KW AND A 3KW AND PLAUMB PLANS
 INDICATE A 3KW AND 6KW?
 PLEASE ALSO INDICATE A DISCONNECTING
 MEANS FOR UNITS.
 215.5
  
 3)NOTE: PLEASE SEE 2002 NEC 210.8B3, IN
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
 PLEASE ADJUST.
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE PLANS .
  
 5)NOTE: PLEASE SEE ALLL RECEPTS WITHIN
 6' OF SINKS SHALL BE GFI/GFI PROTECTED.
 PLEASE ALSO SEE ALL RECEPTS SHALL ALSO
 BE GFI/GFI PROTECTED.
 210.8B1
  
 6)NOTE: PLEASE VERIFY OCP SHOWN FOR 10KW
 HEATSTRIP IN AHU.
 PLEASE SEE MIN OCP 125% 424.3B
 THIS IS ONLY A NOTE:.
  
 7)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES PANEL AS MLO, HOWEVER PARTIAL
 RISER DIAGRAM SHOWS PANEL AS 150 MCB?
 PLEASE CORRLELATE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE SET OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVEIW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  