2005-09-08 00:00:00MECH. PLAN REVIEW:
  
 1. GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS, AND TEN
 FEET FROM ADJACENT BUILDING OPENINGS.
 2001 FBC/M 804.3.3 TERMINATION.
 2001 FBC/M SECTION 915 REQUIREMENT
 OF NFPA 378.2.3.2 EXHAUST SYSTEM
 TERMINATION.
  
 2. GENERATOR MANF. RECOMATIONS FOR
 SERVICE CLERANCES/VENELATIONS IN
 FEET/INCHES IN ALL DIRECTIONS MUST
 ACCOM. GENERATOR PERMIT APP.NEC 70
 110.3 B .
  
 3.INFORMATION ON TYPE OF FUEL.
 LP/NAT. GAS REQUIRE PERMIT, FROM LICEND
 GAS CONTRACTOR.
  
 4. CURRENT PROPERTY SERVEY WITH
 LOCATION OF GENERATOR REFLECTED ON
 SURVEY MUST ACCM. PERMIT APP.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  