| Plan Review Notes For Permit 05080718 |
| Permit Number |
05080718 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-09-08 00:00:00 | MECH. PLAN REVIEW: | | | | | | 1. GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS, AND TEN | | | FEET FROM ADJACENT BUILDING OPENINGS. | | | 2001 FBC/M 804.3.3 TERMINATION. | | | 2001 FBC/M SECTION 915 REQUIREMENT | | | OF NFPA 378.2.3.2 EXHAUST SYSTEM | | | TERMINATION. | | | | | | 2. GENERATOR MANF. RECOMATIONS FOR | | | SERVICE CLERANCES/VENELATIONS IN | | | FEET/INCHES IN ALL DIRECTIONS MUST | | | ACCOM. GENERATOR PERMIT APP.NEC 70 | | | 110.3 B . | | | | | | 3.INFORMATION ON TYPE OF FUEL. | | | LP/NAT. GAS REQUIRE PERMIT, FROM LICEND | | | GAS CONTRACTOR. | | | | | | 4. CURRENT PROPERTY SERVEY WITH | | | LOCATION OF GENERATOR REFLECTED ON | | | SURVEY MUST ACCM. PERMIT APP. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | |
|