| Plan Review Notes For Permit 05080713 |
| Permit Number |
05080713 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-09-08 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)SINGLE HUNG WINDOWS IN THE SIZES | | | SHOWN ON THE FLOOR PLAN FOR THE ROOMS | | | LABELED "ROOM", WHICH I BELIEVE ARE | | | BEDROOMS, DO NOT COMPLY WITH EMERGENCY | | | EGRESS REQUIREMENTS FBC1005.4. | | | | | | | | | ?1005.4.4 MINIMUM SIZE. THE MINIMUM NET | | | CLEAR OPENING HEIGHT DIMENSION | | | SHALL BE 24 INCHES (610 MM).THE | | | MINIMUM NET CLEAR OPENING WIDTH | | | DIMENSION SHALL BE 20 INCHES (508 MM). | | | THE MINIMUM NET CLEAR OPENING | | | AREA SHALL BE 5.7 SQ FT (0.53 M^2). | | | | | | EXCEPTION: GROUND FLOOR OPENINGS | | | SHALL BE PERMITTED TO HAVE A MINIMUM | | | NET CLEAR OPENING OF 5.0 SQ FT. | | | | | | |
|