Plan Review Notes
Plan Review Notes For Permit 05080713
Permit Number 05080713
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SINGLE HUNG WINDOWS IN THE SIZES
 SHOWN ON THE FLOOR PLAN FOR THE ROOMS
 LABELED "ROOM", WHICH I BELIEVE ARE
 BEDROOMS, DO NOT COMPLY WITH EMERGENCY
 EGRESS REQUIREMENTS FBC1005.4.
  
  
 ?1005.4.4 MINIMUM SIZE. THE MINIMUM NET
 CLEAR OPENING HEIGHT DIMENSION
 SHALL BE 24 INCHES (610 MM).THE
 MINIMUM NET CLEAR OPENING WIDTH
 DIMENSION SHALL BE 20 INCHES (508 MM).
 THE MINIMUM NET CLEAR OPENING
 AREA SHALL BE 5.7 SQ FT (0.53 M^2).
  
 EXCEPTION: GROUND FLOOR OPENINGS
 SHALL BE PERMITTED TO HAVE A MINIMUM
 NET CLEAR OPENING OF 5.0 SQ FT.
  
  