| Plan Review Notes For Permit 05080699 |
| Permit Number |
05080699 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-08-29 00:00:00 | MECH. PLAN REVIEW: | | | PROVISO: | | | | | | 1. GENERATOR MANF. RECOMATIONS FOR | | | SERVICE CLEARANCE/VENELATION IN | | | FEET/INCHES IN ALL DIRECTIONS MUST | | | ACCOM. GENERATOR PERMIT APP. NEC 70 | | | 110.3 B . | | | 2. GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENING, AND TEN | | | FEET AWAY FROM ADJECENT BUILDING | | | OPENINGS. 2001 FBC/M 804.3.3 | | | TERMINATION. | | | 2001 FBC/M SECTION 915 REQUIREMENT OF | | | NFPA 37 8.2.3.2 EXHAUST SYSTEM | | | TERMINATION. | | | .3 INFORMATION ON TYPE OF FUEL. | | | 4. LP/NAT GAS REQUIRE PERMIT, FROM | | | LICENED GAS CONTRACTOR. | | | | | | PAT RAFTER 561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. | | | |
|