2005-08-29 00:00:00MECH. PLAN REVIEW:
 PROVISO:
  
 1. GENERATOR MANF. RECOMATIONS FOR
 SERVICE CLEARANCE/VENELATION IN
 FEET/INCHES IN ALL DIRECTIONS MUST
 ACCOM. GENERATOR PERMIT APP. NEC 70
 110.3 B .
 2. GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENING, AND TEN
 FEET AWAY FROM ADJECENT BUILDING
 OPENINGS. 2001 FBC/M 804.3.3
 TERMINATION.
 2001 FBC/M SECTION 915 REQUIREMENT OF
 NFPA 37 8.2.3.2 EXHAUST SYSTEM
 TERMINATION.
 .3 INFORMATION ON TYPE OF FUEL.
 4. LP/NAT GAS REQUIRE PERMIT, FROM
 LICENED GAS CONTRACTOR.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  