| Plan Review Notes For Permit 05080680 |
| Permit Number |
05080680 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-03-18 00:00:00 | ******** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE SIGNATURE AND SEAL ON | | | PLANS IS NOT THAT OF THE ORIGINAL | | | ENGINEER OF RECORD. PLEASE KNOW, AS PER | | | FS THE NEW ENGINEER PART OF THE SAME | | | ENGINEERING FIRM MAY SIGN, DATE AND SEAL | | | PLANS, HOWEVER PLANS MUST BE SIGNED WITH | | | A LEGAL SIGNATURE. PLANS APPEAR TO BE | | | INITIALS? IF INDEED THIS IS THE LEGAL | | | SIGNATURE OF ENGINEER, PLEASE HAVE | | | ENGINEER PROVIDE A SIGNED, DATED, SEALED | | | AND NOTORIZED LETTER FOR LEGAL SIGNATURE | | | CONFORMATION AND THIS LETTER WILL BE | | | PLACED IN OUR SIGNATURE FILE FOR ANY | | | FUTURE REFERENCE. | | | PLEASE KNOW, THE LETTER MUST BE PROPERLY | | | NOTORIZED AS REQUIRED UNDER FS117.05. | | | | | | 2)NOTE: PLEASE PROVIDE INFORMATION | | | REQUARDING TAP ON THE LOAD SIDE OF 800A | | | MAIN. PLEASE CLARIFY LUGS AND/OR HOW TAP | | | IS BEING MADE. | | | | | | BOTH OF THE ABOVE CAN BE ADDRESSED IN | | | LTR FORM. | | | | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|