2005-08-16 00:00:00***** UNSAT ******
  
 1)NOTE: PLEASE SEE BLDG AND FIRE REVIEW
 NOTES, NEW TELEPHONE/CELL EQUIPMENT MAY
 NOT BE LOCATED IN ELEVATOR EQUIPMENT
 ROOM. PLEASE SEE STATE OF FLORIDA
 ELEVATOR CODE. ONLY EQUIPMENT,
 ELECTRICAL OR OTHERWISE IS PERMITTED IN
 ELEVATOR EQUIPMENT ROOM. REQUIRED AT
 THIS TIME AND SUBMITTED WITH PLANS BY
 THE ENGINEER OF RECORD.
 215.5,220
  
 3)NOTE: PLEASE LOAD CALCULATIONS
 SUBMITTED FOR NEW 200A PANEL INDICATE A
 80A LOAD. PLEASE CLARIFY RECEPT AND
 PORTABLE GENERATORS MENTIONS 50A?
 215.5
  
 4)NOTE: PLEASE SUBMIT MANUFACTURE
 CUT/SPEC SHEETS FOR TRANSFER SWITCH.
 PLEASE ALSO SEE A DISCONNECTING MEANS
 WILL BE REQUIRED AT ELECTRICAL ROOM
 LOCATION GROUPED WITH EXISTING
 ELECTRICAL EQUIPMENT. PLEASE SEE DISC
 MEANS SHALL BE RATED AS "SERVICE
 EQUIPMENT".
 225.31, THRU 225.36
  
 PLEASE BE SURE TO SEE NOTES FROM OTHER
 REIVEWER(S) WHICH WILL AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  