Plan Review Notes
Plan Review Notes For Permit 05080679
Permit Number 05080679
Review Stop P
Sequence Number 2
Notes
Date Text
2006-05-10 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2005 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1
 ***NO RESPONSE FROM ARCHITECT NOTED, BUT
 SEE THE FOLLOWING SHEETS: BOUNDARY
 SURVEY, PP1 OF 9 THRU PP9 OF 9, ALL
 LA-POOL AND LA-FW SHEETS HAVE NOT
 ADDRESSED THE COMMENT.
  
 3. SHT T-3 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 ***RESPONSE NOTED, BUT NO REFERENCE TO
 THE AREAS OF ROOFS DRAINING ON TO THE
 ROOF AREAS FROM ABOVE. SEE STAIR ROOF,
 MECHANICAL ROOM ROOF, HIP ROOFS, AND
 OCTAGON ROOF.
  
 4. SHTS T-3 A4.1.1 THRU T-3 A4.1.8 UNITS
 A, B, C, D, E, H, F, G & K SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FHA-98
 DESIGN MANUAL. INDICATE SPECIFICATION
 "A" OR "B" FOR EACH UNIT. SHOW THE W/C
 OPENING, (MINIMUM 33"), SHOW THE W/C AT
 18" OFF THE WALL TO THE CENTER OF THE
 FIXTURE WHERE APPLICABLE, AND 18"
 MINIMUM OFF AN ADJACENT FIXTURE. SEE
 PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 5. SHT T-3 A4.1.9 MEN'S & WOMEN'S TOILET
 ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 8. SHT T-3 A4.19 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
 9. SHTS T-3 A4.1.13 THRU T-3 A4.1.17
 SHALL COMPLY WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS 1 THRU 7. INDICATE
 SPECIFICATION "A" OR "B". SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES.
 SHOW ALL W/C'S TO BE 18" OFF THE WALL TO
 THE CENTER OF THE FIXTURE . SHOW ALL
 OPENINGS TO BE MINIMUM 33". INDICATE
 MEASUREMENT FROM THE CENTER LINE OF THE
 W/C'S TO THE ADJONINING FIXTURES.
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 10. SHT T-3 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 ***RESPONSE NOTED, BUT NO REFERENCE TO
 BACKFLOW PROTECTION WAS LOCATED ON SHT
 P3.3
  
 11. SHT T-3 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 ***NO RESPONSE FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED.
  
 12. SHT T-3 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 ***NO RESPONSED FROM ARCHITECT, AND
 COMMENT NOT ADDRESSED. NO INFORMATION
 SHOWN AS REQUIRED BY DESIGN MANUAL. NO
 MEASUREMENTS INDICATED.
  
 13. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 ***RESPONSE NOTED, BUT PLUMBING NOTE
  
 17. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 ***RESPONSE NOTED, BUT R0OFS THAT DRAIN
 ON TO ROOF FROM ABOVE HAVE NOT BEEN
 SHOWN IN THE CALCULATIONS. (SEE COMMENT
 NUMBER 3).
  
 20. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 ***RESPONSE NOTED, BUT THIS SYSTEM AND
 FITTINGS ARE NOT APPROVED.
  
 21. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE TUB IS MISSING DOWNTREAM OF RISER
 S/33 AND TUB IS NOT VENTED AS SHOWN.
 SECTIONS 106.1.1 & 901.2.1. - W/C, LAV &
 SHOWER ARE NOT SHOWN DOWNSTREAM OF RISER
 S/34 (ROOM G 110). - MEN'S & WOMEN'S
 TOILET ROOMS , (108 & 109), ARE NOT
 SHOWN ON RISER. - THE TUB DOWNSTREAM OF
 RISER S/43 IS NOT VENTED AS SHOWN.
 SECTION 901.2.1. - LAUNDRY (103) IS NOT
 SHOWN DOWNSTREAM OF RISER S/42. - PIPING
 TO STUDIO K W/M & BATHROOM (105)
 DOWNSTREAM OF RISER S/23 NOT SHOWN.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT MEN'S AND WOMEN'S
 TOILET ROOMS ARE STILL NOT SHOWN ON THE
 RISER, NOR IS THE LAUNDRY ROOM PIPING
 SHOWN.
  
 22. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 ***RESPONSE NOTED, BUT SOME PIPE SIZES
 ARE NOT CORRECT AND SOME DFU'S ARE NOT
 CORRECT. (SEE RED LINE CORRECTIONS ON
 ONE SET OF PLANS).
  
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT THE LENGTHS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED
 AS REQUESTED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT NO CALCULATION
 WERE SUBMITTED FOR THE CLOTHS DRYERS.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEET HAVE
 NOT BEEN FOUND.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL VOIDED SHEETS FROM SETS OF
 PLANS AND RESUBMIT ONE SET OF "OLD
 SHEETS" SEPARATELY FOR COMPARISON.
  
 **************NEW COMMENT***************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved