Plan Review Notes
Plan Review Notes For Permit 05080679
Permit Number 05080679
Review Stop M
Sequence Number 2
Notes
Date Text
2006-04-18 00:00:00DENIED:TOWER #3
 RESPONSE TO COMMENTS DATED 10-11-05.
 COMMENT #1:
 PLAN SHEET M2.1, RESPONSE INDICATES
 THE INTAKE DUCT FOR THE TOILET & DRYER
 EXHAUST CHASE IS FOR THE MAKE-UP AIR.
 PLEASE CLARIFY THE FOLLOWING:
 1) SIZE OF THE BRANCH DUCT.
 2) PLEASE CLARIFY THE PENETRATION
 BETWEEN THE RESIDENCE AND THE WALKWAY.
 DOES THIS HAVE THE PENETRATION HAVE A
 FIRE, SMOKE OR BOTH RATING? SHOW
 COMPLIANCE WITH 2004 FBC 716.
  
 COMMENT #5:
 RESPONSE INDICATES ANNOTATION ON PLAN
 SHEET M0.1 "NO COMBUSTIBLES ALLOWED
 IN THE RETURN AIR PLENUM".PLEASE
 COORDINATE WITH THE ARCHITECT.
 ACCORDING TO THE DOOR SCHEDULE (PLAN
 SHEET A7.2.1 & A7.2.2), THE DOORS TO THE
 A/C CLOSET ARE CONSTRUCTED OF HOLLOW
 WOOD.DOES THIS MEET THE REQUIREMENT OF
 NON-COMBUSTIBLE?
  
 PLEASE ALSO REFERENCE THE NOTE ON PLAN
 SHEET M7.1, RETURN AIR THROUGH LOUVERED
 DOOR.THE DOOR TO THE A/C CLOSET OPENS
 INTO THE LAUNDRY ROOM WITH.RETURN AIR
 SHALL NOT BE LOCATED IN THE LAUNDRY
 ROOM, 2004 FMC 601.3 & 601.4 EXCEPTION
 #3.
  
  
 NEW COMMENTS:
 1.PLAN SHEET P6.4 INDICATES GAS
 APPLICANCES, SPECIFICALLY THE WATER
 HEATER.PLEASE CLARIFY THE VENTING OF
 THE GAS WATER HEATER.PLEASE NOTE, PER
 2004 FMC 602.1, FUEL FIRED APPLIANCES
 SHALL NOT BE INSTALLED WITHIN A PLENUM.
  
 2.PLEASE NOTE, PER 2004 FMC 504.5,
 INSTALLATIONS EXHAUSTING GREATER THAN
 200 CFM SHALL BE PROVIDED WITH MAKE-UP
 AIR.
  
 3.PROVIDE ADDITIONAL INFORMATION FOR
 THE VENTILATION/PRESSURIZATION OF THE
 EXIT STAIRWAY.SHOW COMPLIANCE WITH
 2004 FBC 909.20 & 1019.1.8.
  
 4.PER 2004 FBC 903.2.10.2 &
 903.2.12.1, SPRINKLER SYSTEMS RQUIRED
 FOR TRASH CHUTES & DRYER EXHAUST
 (SUB-DUCT).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.