| 2006-04-18 00:00:00 | DENIED:TOWER #3 |
| | RESPONSE TO COMMENTS DATED 10-11-05. |
| | COMMENT #1: |
| | PLAN SHEET M2.1, RESPONSE INDICATES |
| | THE INTAKE DUCT FOR THE TOILET & DRYER |
| | EXHAUST CHASE IS FOR THE MAKE-UP AIR. |
| | PLEASE CLARIFY THE FOLLOWING: |
| | 1) SIZE OF THE BRANCH DUCT. |
| | 2) PLEASE CLARIFY THE PENETRATION |
| | BETWEEN THE RESIDENCE AND THE WALKWAY. |
| | DOES THIS HAVE THE PENETRATION HAVE A |
| | FIRE, SMOKE OR BOTH RATING? SHOW |
| | COMPLIANCE WITH 2004 FBC 716. |
| | |
| | COMMENT #5: |
| | RESPONSE INDICATES ANNOTATION ON PLAN |
| | SHEET M0.1 "NO COMBUSTIBLES ALLOWED |
| | IN THE RETURN AIR PLENUM".PLEASE |
| | COORDINATE WITH THE ARCHITECT. |
| | ACCORDING TO THE DOOR SCHEDULE (PLAN |
| | SHEET A7.2.1 & A7.2.2), THE DOORS TO THE |
| | A/C CLOSET ARE CONSTRUCTED OF HOLLOW |
| | WOOD.DOES THIS MEET THE REQUIREMENT OF |
| | NON-COMBUSTIBLE? |
| | |
| | PLEASE ALSO REFERENCE THE NOTE ON PLAN |
| | SHEET M7.1, RETURN AIR THROUGH LOUVERED |
| | DOOR.THE DOOR TO THE A/C CLOSET OPENS |
| | INTO THE LAUNDRY ROOM WITH.RETURN AIR |
| | SHALL NOT BE LOCATED IN THE LAUNDRY |
| | ROOM, 2004 FMC 601.3 & 601.4 EXCEPTION |
| | #3. |
| | |
| | |
| | NEW COMMENTS: |
| | 1.PLAN SHEET P6.4 INDICATES GAS |
| | APPLICANCES, SPECIFICALLY THE WATER |
| | HEATER.PLEASE CLARIFY THE VENTING OF |
| | THE GAS WATER HEATER.PLEASE NOTE, PER |
| | 2004 FMC 602.1, FUEL FIRED APPLIANCES |
| | SHALL NOT BE INSTALLED WITHIN A PLENUM. |
| | |
| | 2.PLEASE NOTE, PER 2004 FMC 504.5, |
| | INSTALLATIONS EXHAUSTING GREATER THAN |
| | 200 CFM SHALL BE PROVIDED WITH MAKE-UP |
| | AIR. |
| | |
| | 3.PROVIDE ADDITIONAL INFORMATION FOR |
| | THE VENTILATION/PRESSURIZATION OF THE |
| | EXIT STAIRWAY.SHOW COMPLIANCE WITH |
| | 2004 FBC 909.20 & 1019.1.8. |
| | |
| | 4.PER 2004 FBC 903.2.10.2 & |
| | 903.2.12.1, SPRINKLER SYSTEMS RQUIRED |
| | FOR TRASH CHUTES & DRYER EXHAUST |
| | (SUB-DUCT). |
| | |