| 2006-05-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | FROM PLUMBING PLAN REVIEW: |
| | |
| | 26. THE FOLLOWING INFORMATION REQUIRED |
| | FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. CUT SECTIONS NOT SHOWN |
| | AND MOST RISERS NOT SHOWN. |
| | ***RESPONSE NOTED, BUT THE LENGTHS OF |
| | EACH CUT SECTION HAVE NOT BEEN SUBMITTED |
| | AS REQUESTED. |
| | |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | ***RESPONSE NOTED, BUT NO CALCULATION |
| | WERE SUBMITTED FOR THE CLOTHS DRYERS. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***RESPONSE NOTED, BUT MANUF. SHEET HAVE |
| | NOT BEEN FOUND. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REMOVE ALL VOIDED SHEETS FROM SETS OF |
| | PLANS AND RESUBMIT ONE SET OF "OLD |
| | SHEETS" SEPARATELY FOR COMPARISON. |
| | |
| | **************NEW COMMENT*************** |
| | 1B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL AND FS 553.80(2)(B). |
| | |
| | REVIEW BY KEN STEVENS |