Plan Review Notes
Plan Review Notes For Permit 05080679
Permit Number 05080679
Review Stop G
Sequence Number 2
Notes
Date Text
2006-05-10 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PLUMBING PLAN REVIEW:
  
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 ***RESPONSE NOTED, BUT THE LENGTHS OF
 EACH CUT SECTION HAVE NOT BEEN SUBMITTED
 AS REQUESTED.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***RESPONSE NOTED, BUT NO CALCULATION
 WERE SUBMITTED FOR THE CLOTHS DRYERS.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEET HAVE
 NOT BEEN FOUND.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL VOIDED SHEETS FROM SETS OF
 PLANS AND RESUBMIT ONE SET OF "OLD
 SHEETS" SEPARATELY FOR COMPARISON.
  
 **************NEW COMMENT***************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]