| 2006-05-04 00:00:00 | ****** UNSAT 2ND REVIEW ******** |
| | |
| | |
| | SAIL CLUB TOWER 3. |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW AND SOME NEW COMMENTS |
| | DUE TO CHANGES IN PLANS. |
| | |
| | ** PLEASE SEE NOTE BELOW ARE TAKEN |
| | DIRECTLY FROM THE PREVIOUS REVIEW AND |
| | NEW COMMENTS ARE AT THE END. |
| | |
| | ** PLEASE SEE COMMENT WITH RESPECT TO |
| | THE REMOVAL OF ALL OLD/VOIDED SHEETS |
| | FROM SETS. |
| | |
| | 1)NOTE:NOTE #1, NO, PLEASE SEE SCOVER |
| | SHEET STILL REFLECTS THE 1999 NEC AND |
| | PLEASE SEE REVISED SHEET E.1 SHOULD |
| | INDICATE THE CURRENT CODES IN EFFECT FOR |
| | DESIGN. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE CODE REFERENCED ON PLANS |
| | LIST THE 1999 NEC. PLEASE KNOW, AS OF |
| | JULY 1ST 2003, THE STATE ADOPTED THE |
| | 2002 NEC. |
| | PLEASE ALSO SEE WE ARE UNDER THE 2003 |
| | NFPA-101 AND 2002 NFPA-72 |
| | PLEASE ADJUST. |
| | |
| | 2)NOTE: NOTE #2 OK, HOWEVER PLEASE SEE |
| | NEW NOTE WITH RESPECT TO VAULT AREA. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE BLDG /FIRE REVIEW COMMENTS |
| | FOR STAIR TOWER EXITING WHICH WILL |
| | AFFECT ELECTRICAL LAYOUT. |
| | EXITS BACK INTO HALL WAY AREAS IN FRONT |
| | OF UNITS. |
| | |
| | 3)NOTE:NOTE #3 OK, THIS SEE TO BE |
| | DONE, PLEASE SEE OTHER NOTES FOR A |
| | COUPLE ITEMS MISSING FOR RECEPTSETC. |
| | |
| | |
| | ** PREVISOU NOTE ** |
| | PLEASE SHOW ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULES. |
| | PLEASE SEE SOME AREAS WHICH ELECTRICAL |
| | FIXTURES SEEM TO BE MISSINGTHIS. |
| | PLEASE ALSO SEE CIRCUITING FOR UNITS. |
| | PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY |
| | BE PROVIDED, HOWEVER A LAYOUT WOULD BE |
| | REQUIRED FOR EACH UNIT TYPE, INCLUDING |
| | STUDIO UNIT. |
| | CIRCUITING FOR SOME UNITS/ITEMS CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | |
| | 4)NOTE: NOTE #4 NO/YES, SOME |
| | PHOTOMETRICS WERE SUBMITTED, HOWEVER |
| | PLEASE SEE SOME OF THESE ARE NOT CLEAR |
| | AND VISABLE FOR STAIRS FOR VERIFICATION. |
| | PLEASE ALSO SEE NONE COULD BE LOCATED |
| | FOR EGRESS PATHS INCLUDING |
| | HALLS/CORRIDORS? |
| | PLEASE SEE A MIN OF 10FT CANDLES AVG IS |
| | REQUIRED UNDER NORMAL FOR STAIRS WHICH |
| | DOES NOT SEEM TO BE THE AVG AS SHOWN? |
| | PLEASE SEE NOT INDICATION FOR MINS UNDER |
| | EM LIGHTING CONDITIONS COOULD BE |
| | LOCATED. |
| | |
| | ** PREVIOUS ** |
| | PLEASE PROVIDE PHOTO-METRICS FOR |
| | STAIR TOWERS ON NORMAL PWR AND STAND-BY. |
| | ALONG WITH WALK AREAS. |
| | PLEASE SEE STAIR TOWERS UNDER NORMAL PWR |
| | SHALL MEET A MIN OF 10FT CANDLES. PLEASE |
| | SEE ARES FOR HALLS ETC ARE PERMITTED TO |
| | BE LESS. . |
| | PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1 |
| | |
| | 5)NOTE: NOTE #5 YES/ NO, PLEASE SEE A |
| | MIN OF ONE FIXTURE CONTAINING A BATTERY |
| | BACK UP WILL BE REQUIRED AT EVERY OTHER |
| | LEVEL IN STAIR TOWERS AND EGRESS PATHS |
| | TO THE PUBLIC RIGHT OF WAY. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE ONE STAIR TOWER SHOWS |
| | CIRCUITING FOR LTS FROM NORMAL POWER |
| | PANEL AND CIRCUTING. |
| | PLEASE SEE THESE ARE REQUIRED TO BE ON |
| | EM POWER PANEL. |
| | PLEASE KNOW, BATTERY BACK FIXTURES WILL |
| | BE REQUIRED AT EVERY OTHER LEVEL(MIN). |
| | PLEASE SEE LS 101 WHICH MENTIONS THE |
| | TRIPPING/THROW OF A SINGLE BRKR SAHLL |
| | NOT LEAVE ANY EGRESS AREA IN TOTAL |
| | DARKNESS. PLEASE CALL ELECTRICAL PLAN |
| | REVIEW AND FIRE MARSHALS OFFICE TO GO |
| | OVER OPTIONS PERMITTED. |
| | A BATTERY BACK-UP FIXTURE AT EVERY OTHER |
| | LEVEL WILL SATISFY THIS OFFICE AND AHJ. |
| | PLEASE BE SURE TO MEET THE MIN OF 1 |
| | FT/CANDLE UNDER EM. |
| | PLEASE BE SURE TO SEE PREVIOUS NOTE #4 |
| | FOR LIGHTING LEVELS.(MIN) |
| | |
| | 6)NOTE:NOTE #6 YES/NO, PLEASE SEE MOST |
| | ROOMS WERE DONE, HOWEVER THE ELEVATOR RM |
| | DOES NOT INCLUDE A BATTERY BACK UP |
| | FIXTURE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE BATTERY BACK-UP |
| | FIXTURES IN MAIN ELECTRICAL RMS AND |
| | ELEVATOR ROOM(S), GENERATOR AND FIRE |
| | PUMP ROOM. PLEASE ALSO PROVIDE |
| | CIRCUITING FOR THESE |
| | RMS. |
| | |
| | 7)NOTE: NOTE #7 NO, ? RESPONSE MENTIONS |
| | TO SEE 5.1, HOWEVER NO CURB DETAIL WAS |
| | LOCATED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE CURB DETAIL FOR |
| | BUS-DUCT RISER AND FLOOR PENATRATIONS. |
| | 368.6 |
| | |
| | 8)NOTE: NOTE #8 , PLEASE EXPAND NOTE FOR |
| | ALL CLEARENCES TO BE MET PER 110.26. |
| | PLEASE KNOW, THE NOTE ADDDED WAS OK AND |
| | SHOULD REMAIN ALSO. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE NOTES ON RISER AND |
| | ELECTRICAL ROOM SHEETS FOR REQUIREMENTS |
| | OF 110.26 FOR PANIC HARDWARE AND DOOR |
| | SWINGS. |
| | PLEASE SEE MIN CLEARENCE PER 110.26 |
| | |
| | 9)NOTE:NOTE # 9 OK, PLEASE SEE |
| | RESPONSE MENTIONS "ALREADY CHNGED PER |
| | REV#1", HOWEVER WE ARE NOT AWARE OF ANY |
| | "REV#1" SUBMITTED FOR REVIEW? |
| | OK, AS CHANGED ON RISER. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE RISER INDICATES ALL BUS-DUCT |
| | FROM FPL VAULT TO MAIN ELECTRICAL ROOM |
| | AS OVER-HEAD. PLEASE SEE 230.70, 230.6, |
| | NO MORE THAN 8' OF UNPROTECTED |
| | CONDUCTORS/ OR BUS DUCT |
| | PERMITTED "INSIDE THE BLDG. |
| | PLEASE SEE ROUTING OF BUS-DUCT APPEARS |
| | TO SHOW INSTALLATION INSIDE CONDO |
| | UNITS?? |
| | |
| | 10)NOTE:NOTE #10 OK,? PLEASE CLARIFY |
| | IF THE EQUIPMENT WHICH IS NOTED IN |
| | RESPONSE CONTAINS A MANUAL MEANS OF |
| | DISCONNECT LOCATED ON THE OUTSIDE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE INFORMATION ON BUS -DUCT |
| | RISER MAINS. APPEARS TO SHOW THESE AS |
| | "SHUNT-TRIP" AND NOT CONTAINING A MANUAL |
| | MEANS OF DISCONNECT LOCATED ON |
| | THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE |
| | MAIN PANEL SCHEDULE(S), THESE DO NOT |
| | SEEM TO INDICATE A MCB. |
| | 230.76,230.79 |
| | |
| | 11)NOTE:NOTE #11 NO, PLEASE SEE RISER |
| | HAS BEEN REVISED, HOWEVER PLEASE SEE 5.2 |
| | AS BUS-DUCT RISER IS STILL SHOWN AS 2500 |
| | A'S WITH 5.1 SHOWING 3000A'S. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE CORRELATE ALL MAINS ETC FOR |
| | SIZING. PLEASE SEE KEY NOTES MENTIONS |
| | 2500A AND PLANS ALSO INDICATE 3000A.? |
| | |
| | 12)NOTE: NOTE #12 NO, PLEASE SEE NOTES |
| | ON E.01 HAVE BEEN REVISED TO INDICATE |
| | ALL COPPER BUS-DUCT, HOWEVER NO SPEC |
| | BOOKS, AND RISER STILL SHOWS ALUMINUM. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE SPECIFIC INFORMATION ON |
| | BUS-DUCT, PLEASE SEE AN ALUM EQUIPMENT |
| | GROUNDING CONDUCTOR/ MATERIAL IS NOT |
| | PERMITED. 310.2. LOCAL AMENDMENTS. |
| | |
| | 13)NOTE:NOTE #13 NO. |
| | PLEASE KNOW, REVIEW AND PERMITTING OF |
| | TOWERS SHALL NOT PASSED UNITLA REVIEW |
| | OF ALL SPECS ARE DONE. IF THIS EQUIPMENT |
| | IS BEING DONE UNDER THE GARAGE PERMITS, |
| | ALL WILL DEPEND ON THE REVIEW, PASSING |
| | AND ISSUANCE OF THE GARAGE BUIDLINGS. |
| | PLEASE KNOW, NO PERMITS FOR TOWERS WILL |
| | BE GRANTED UNTIL ALL ABOVE FOR GARAGES |
| | ARE MET. |
| | THE SPECIFICA INFORMATION FOR FIRE PUMPS |
| | , GENERATORS ETC SHOULD BE REFERENCE ON |
| | EACH SET OF TOWER PLANS AND PERHAPS NOTE |
| | FOR "SCOPE UNDER SEPARATE PERMIT". |
| | |
| | ** PREVIOUS NOTE: |
| | PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS AND CUT SHEETS FOR GENERATOR, ATS, |
| | FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE ALSO SUBMIT THE SAME FOR ANYSUB |
| | BASE FUEL TANK. |
| | PLEASE KNOW, DUE TO THE INFORMATION NOT |
| | BEING SUBMITTED AT THIS TIME, REVIEW FOR |
| | SOME ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE DONE. |
| | UNABLE TO VERIFY CODE COMPLIANCE FOR |
| | MANY ITEMS UNDER NFPA, 20,70,101,110 |
| | ETC. |
| | |
| | 14)NOTE:NOTE #14 NO , AS NOTED ABOVE |
| | ONNOTE #13. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE ELECTRICAL RISER DIAGRAM DOES |
| | NOT CONTIAN ANY INFORMATION FOR FIRE |
| | PUMP OR FIRE PUMP CONTROLLER, |
| | SERVICE, SIZING , CONDUCTORS ETC. |
| | PLEASE COMPLETE. |
| | ENCASEMENT IN CONCRETE, OUTSIDE THE |
| | BLDGS, ETC |
| | |
| | 15)NOTE: NOTE #15 NO, PLEASE SEE NOTE |
| | UNDER TOWER #4, THESE ROOMS AND MIN |
| | REQUIRMENTS SHOULD BE DETAILED IN EACH |
| | SET. GEN RM WS SEEN ON TOWER #4, HOWEVER |
| | SEE NOTES FOR FP RM ETC. |
| | PHOTO-METRICS FOR 30 FT CANDLES MIN ETC. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE AREA FOR GARAGE CONTAINING |
| | THE LOCATION OF FIRE PUMP AND GENERATOR |
| | WILL BE REQUIRED TO BE SUBMITTED FOR |
| | PERMIT AND REVIEW. |
| | PLEASE SEE LOCATIONS FOR FIRE |
| | SEPARATIONS, ACCESS, LIGHTING, ETC CAN |
| | NOT BE REVIEWED AT THIS TIME. |
| | |
| | 16)NOTE: NOTE #16 OK, SO NOTED IN OTHER |
| | COMMENTS AND PLANS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE VERIFY LOCATION OF GENERATOR. |
| | PLEASE SEE PLANS SEEM TO INDICATE FIRE |
| | PUMP AND GEN RM LOCATED AT FIRST FLR |
| | LEVEL, HOWEVER RISER SEEMS TO SHOW THESE |
| | AT 2ND FLR LEVEL? |
| | PLEASE CLARIFY. |
| | |
| | 17)NOTE: NOTE #17 YES/ NO, PLEASE SEE |
| | THE FIRST PART OF THE NOTE WAS |
| | ADDRESSED, HOWEVER CORRELATION OF A/C |
| | EQUIPMENT FOR 2ND PART OF NOTE DID NOT |
| | SEEM CORRRECTED AS MECHNICAL PLANS |
| | INDICATE DIFFERENT LOADS THAN ELECTRICAL |
| | PLANS. |
| | PLEASE SEE NOTE #40 |
| | PLEASE SEE NEW NOTES FOR LOADS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE DISCONNECTING MEANS FOR |
| | ALL A/C EQUIPMENT AT ROOF TOP LEVEL. A |
| | "TYPICAL" DETAIL MAY BE GIVEN FOR |
| | THESE.440.11 |
| | PLEASE ALSO INDICATE ALL ROOF TOP GFI |
| | RECEPTS PER 210.63 |
| | PLEASE CORRELATE ALL A/ KW RATINGS AND |
| | LOADS WITH MECHANICNAL PLANS . (KW |
| | RATINGS ETC). |
| | |
| | 18)NOTE:NOTE #18? NO, PLEASE SEE FIRE |
| | COMMAND ROOM AND ALL EQUIPMENT ETC |
| | REQUIRED PER HIGH-RISES AS NOTED. PLEASE |
| | LIST ACCORDINGLY. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE FIRE REVIEW NOTES |
| | ALSO: PLEASE PROVIDE A LAYOUT FOR |
| | CENTRAL STATION RM(FIRE COMMAND RM) |
| | SHOWING ALL DEVICES/ PANELS/ STATUS |
| | PANELS ETC. |
| | PLEASE LIST ALL ITEMS AS SPECIFIED IN |
| | NFPA- 101 11.8.5, |
| | |
| | 19)NOTE:NOTE #19 OK. |
| | |
| | 20)NOTE: NOTE #20 OK. |
| | |
| | 21)NOTE: NOTE #21 OK. |
| | |
| | 22)NOTE:NOTE #22 NO, ? COULD NOT |
| | LOCATE THE NOTE AND INSTALLATION |
| | REQUIREMENTS/NOTE. |
| | RESPONSE MENTIONS TO SEE REVISED E.01 |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE NOTE ON PLANS FOR SMOKE |
| | DETECTOR PLACEMENT PER REQUIREMENTS OF |
| | NFPA -72 11.8.3.5. |
| | |
| | 23)NOTE: NOTE #23 OK. |
| | |
| | 24)NOTE: NOTE #24 OK, HOWEVER SEE ISLAND |
| | FOR UNIT "E". THIS IS SHOWN ON THE THE |
| | TYPICAL DETAIL AND CAN BE REDLINED. |
| | |
| | 25)NOTE: NOTE #25 OK, SEE RESPONSE |
| | MENTIONS GAS APPLIANCES, HOWEVER PLEASE |
| | INDICATE ON PLANS/PANEL SCHEDULE WHICH |
| | APPLIANCES ARE GOING TO BE GAS. |
| | PLEASE SEE NEW COMMENT WITH RESPECT TO |
| | WH. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE A 70A BRKR IS BEING SHOWN FOR |
| | RANGE?? PLEASE SEE 210.23,422.11B |
| | 50A RANGE RECEPT, 50A BRKR MAX. |
| | |
| | 26)NOTE: NOTE #26 ? UNCLEAR HOW THE |
| | SINGLE PHASE IS"A" AND "C" PHASE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE PANEL SCHEDULES SEEM TO SHOW |
| | "A" AND "C" PHASE FOR SINLGLE PHASE |
| | SERVICE AND UNITS?? |
| | PLEASE CLARIFY / ADJSUT.215.5 |
| | |
| | 27)NOTE: NOTE #27 NO, PLEASE SEE AREAS |
| | SHOUDL BE CLEAR FOR DINING ROOM/AREA AND |
| | LIVING RM. PLEASE SEE THE LR/DR |
| | NOTTATIONS ON PLANS ARE CROSSED ON SOME |
| | UNITS .PLEASE SEPARATE FOR CLARITY |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE LABEL AND /OR CLARIFY "DINING" |
| | AREAS IN ALL UNITS. |
| | UNABLE TO VERIFY CIRCUITING AS DINING |
| | /LIVING ARE SEEMED TO BE COMBINED.' |
| | PLEASE SEE 210.52B1 |
| | |
| | 28)NOTE: NOTE #28 OK, PLEASE SEE MMOST |
| | WERE DONE, HOVER PLEASE SEE REDLINED |
| | PLANS AS THERE A FEW. |
| | PLEASE KNOW, AS SOME RECEPTS MAY BE |
| | MISSING FOR HALL AREAS AND 210.52C ON |
| | THE SMAE SHEET PLEASE REVISE AT THIS |
| | TIME. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 210.52D FOR SOME UNITS |
| | MISSING GFI'S WITH IN 3' OF LAV'S. |
| | PLEASE ALSO SEE A GFI MAY NOT PERMITTED |
| | ON THE OTHER SIDE OF A LAV TO MEET |
| | 210.52D (3'). |
| | GFI 'S MAY BE MOVED IN BETWEEN BOTH |
| | LAV'S OR AN ADDITIONALRECEPT MAY BE |
| | ADDED. |
| | |
| | 29)NOTE: NOTE #29, NO, PLEASE SEE SOME |
| | STILL REDLINED AT LOCATIONS AS NOTED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE MISSING RECEPTS IN HALLWAY |
| | AREAS, 10' OR MORE OF CONTINUOUS |
| | WALL. 210.52H. |
| | |
| | 30)NOTE: NOTE #30 ?? PLEASE SEE RISER |
| | SHOWS PANEL, HOWEVER NOT NOTED AS FUTURE |
| | OR ?? 2MD FLR COULD NOT LOCATE THIS |
| | PANEL. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE RISER SEEMS TO INDICATE A |
| | POOL PANEL, HOWEVER NO OTHER INFORMATION |
| | WAS SUBMITTED AND PANEL COULD NOT |
| | LOCATED ON PLANS. |
| | LOADS ETC. |
| | 215.5, 220 |
| | |
| | 31)NOTE: NOTE #31 OK |
| | |
| | 32)NOTE: NOTE #32 N, HOWEVER PLEASE |
| | KNOW, NOTE WAS NOT COMPLETE WHEN TYPED |
| | FROM PREVIOUS REVIEW IN ERROR. PLEASE |
| | KNOW, THE COMMENT SHOULD HAVE READ. " |
| | PLEASE PROVIDE A NOTE ON ROOF TOP PLANS; |
| | " ANY AND ALL LIGHTNING PROTECTION |
| | SYSTEM PROPOSED OR INSTALLED SAHLL BE |
| | UNDER A SEPARATE PERMIT AND SHALL BE |
| | INSTALLED PER NFPA-780" OR WORDS TO THAT |
| | AFFECT. |
| | IT IS KNOWN TO THIS OFFICE THATTHE |
| | CODE DOES NOT REQUIRE LP ON THIS TYOE OF |
| | BUILDING AS LP IS REQUIRED ON SOME OTHER |
| | STRUCTURS PER THE FBC. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PLACE NOTE ON "ROOF |
| | PLANS" WHICH WILL REQUIRE ALL LIGHTNING |
| | PROTECTION |
| | |
| | |
| | 33)NOTE: NOTE #33 OK. |
| | |
| | 34)NOTE: NOTE #34 NO, PLEASE SEE SOME |
| | PANELS ARE NOTED AS CONTAINING |
| | "FEED-THRU LUGS" , HOWEVER SOME ARE ALSO |
| | SHOWING A MAIN W/ FEED THRU LUGS.CIRCUIT |
| | BREAKER? |
| | PLEASE SEE NEW COMMENTS FOR SOME PANELS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE INDICATE IF PANELS EH2A- |
| | EH12A ARE FEED THRU LUGS OR DOES EACH |
| | PANEL CONTAIN OCP FOR EACH.? |
| | PLEASE ALSO SEE PANELS H5A-9, 12 ETC. |
| | 215.5 |
| | |
| | 35)NOTE: NOTE # 35 OK, HOWEVER SEE NEW |
| | NOTE. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PROVIDE PANEL SCHEDULE FOR PANEL |
| | H2AA ON RISER. 215.5 |
| | |
| | 36) NOTE:NOTE # 36 OK, HOVER SEE NEW |
| | NOTE FOR 16B |
| | |
| | ** PREVIOUS NOTE ** PLEASE SEE PANEL |
| | H16A INDICATES H12A AND H12B ON LOAD |
| | CALCS?? RISER APPEARS TO SHOW H16A BEING |
| | FED FROM SBA AND SHOWS H12A FROM H9A |
| | ETC. 215.5 |
| | |
| | 37)NOTE: NOTE #37 OK. |
| | |
| | 38)NOTE: NOTE #38 OK. |
| | |
| | 39)NOTE: NOTE #39 NO. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SUBMIT "SPEC BOOKS' FORREVIEW OF |
| | PROJECT. THESE WOULD CONTAIN JOBSITE |
| | SPECS. |
| | |
| | 40)NOTE: NOTE # 40 OK. |
| | |
| | 41)NOTE: NOTE #41 ? NO, PLEASE SEE NOTE |
| | WITH RESPECT TO CORRELATTION OF KW FOR |
| | AHU'S. ONCE THIS IS DONE, VERIFICATION |
| | OF THE OCP CAN BE DONE. |
| | SEE NEW NOTES FOR LOADS. |
| | |
| | ** PREVIOUS NOTE ** |
| | NOTE ADDED AFTER REVIEW OF TOWER #4, |
| | PLEASE SEE MIN OCP FOR AHU HEAT TO BE |
| | 125%. 424.3B SHOWS 50A OCP. |
| | |
| | |
| | *************** NEW NOTES ********** |
| | |
| | 1) NOTE: PLEASE PROVIDE A LETTER FROM |
| | FPL REPRESENITIVE FOR VAULT AND VAULT |
| | LOCATION SINCE REVISED PLANS. |
| | PLEASE SEE VAULT IN UNCLEAR AS ONCE |
| | SHEET APPEARS TO LABEL IN A SMALLER ROOM |
| | WITH SOEM OTHER EQUIPMENT/ ELECTRICAL IN |
| | THE VAULT. PLEASE KNOW, FPL DOES NOT |
| | PERMIT ANY ITEMS, ELECTRICAL FIRE |
| | SPRINKLER ETC IN VAULT. |
| | PLEASE ALSO SEE IS OUTSIDE AS SHOWN ON |
| | ANOTHER SHEET, PLEASE VERIFY LOCATION AS |
| | THIS SEEMS TO BE LOCATED IN THE TRASH |
| | DRAIN,A ND ACCESS AREA? |
| | |
| | 2) NOTE: PLEASE SEE PANEL SCHEDULES FOR |
| | UNITSDO NOT APPEAR TO INDICATE ANY |
| | WATER HEATERS?? PLEASE SEE PANEL |
| | SCHEDULES DO SHOW TWO AHU'S BRANCH |
| | CIRCUITS? |
| | PLEASE KNOW THIS WAS MISSED ON FIRST |
| | REVIEW AS ORIGINAL PLANS INDICATE THE |
| | SAME. |
| | PLEASE ADJUST LOADS AS NEEDED. |
| | 215,220,422 |
| | |
| | 3) NOTE: PLEASE SEE ONCE LOADS FOR AHU'S |
| | ARE CORRELATED, PLEASE ADJUST AS NEEDED. |
| | ** PLEASE KNOW, THE PLANS HAVE BEEN |
| | REVISED TO NOW ONLY INCLUDE ONE |
| | BUS-RISER, AND PLEASE SEE LOADS SHOWN |
| | NOW AFTER ALL DERATING HAS BEEN TAKEN |
| | STANDS AT 2936A'S ON A 3000A RATED BUS |
| | AND MAIN. PLEASE SEE IF LOADS FOR AHU'S |
| | ARE INDEED HIGHER, THIS WILL NEW |
| | ADJUSTED LOAD MAY CERTAINLY TAKE LOAD |
| | OVER THE 3000A RATING OF EQUIPMENT. |
| | PLEASE KNOW, THESE UNITS ARE GOING TO |
| | HAVE OWNERSHIP AS "CONDOS" AND |
| | REMODELING ETC ALMOST ALWAYS TAKES |
| | PLACE. |
| | PLEASE SEE SERVICE IS BEING SIZED WITH |
| | NO ALLOTMENT FOR FUTURE EXPANSION. |
| | **ELECTRICAL APPLIANCES, JACUZZI TUBS |
| | ETC' |
| | PLEASE SEE 90.8A "DISTRIBUTION CENTERS |
| | SHOULD CONTAIN ADDITIONAL SPACE AND |
| | "CAPACITY" FOR FUTURE ADDITIONS AND |
| | SHOULD BE CONVENIENTLY LOCATED FOR EASY |
| | ACCESSIBILITY." |
| | THIS EXCERPT IS TAKEN FROM THE 2002 |
| | HANDBOOK. |
| | |
| | 4) NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| | 16A DOES NOT INDICATE "FEED THRU LUGS" |
| | AND RISER DOES NOT SHOWN "16B" BEING FED |
| | FROM 16A? |
| | PLEASE SHOW. |
| | |
| | 5) NOTE: PLEASE SEE MISSING DOOR |
| | "OVERLAY" ON 3.2. |
| | |
| | 6) NOTE: PLEASE SEE NEW NOTE #19 AS |
| | NOTED ON GENERATOR RISER WHICH MENTIONS |
| | TO SEE NOTE #19 ON "KEYNOTES", HOWEVER |
| | KEY NOTE #19 IS BLANK? |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE |
| | COMPLIANCE. THIS IS ONLY A NOTE: |
| | |
| | ** PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| | ARE "REDLINED" AT LOCATIONS ON PLANS FOR |
| | NOTES. |
| | |
| | ** PLEASE KNOW, A RESPONSE LETTER IN |
| | TYPE WRITTEN FORM WILL HELP IN RESPONSES |
| | TO ELECTRICAL COMMENTS. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE KNOW, ALL OLD/OR VOIDED SHEETS |
| | MUST BE COMPLETELY REMOVED FROM SETS |
| | BEFORE RSUBMITTING PLANS. |
| | PLEASE ONLY SUBMIT ONE SET OF ALL |
| | OLD/VOIDED SHEETS FOR REFERENCE ONLY. |
| | ONLY THE NEW REVISED SHEETS SHOULD BE |
| | INSERTED INTO THE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SEE THIS WAS NOT DONE AS |
| | REQUESTED FROM PREVIOUS REVIEW |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |