Plan Review Notes
Plan Review Notes For Permit 05080679
Permit Number 05080679
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-20 00:00:00PERMIT: 05080679
 ADD: 719 EXECUTIVE CENTER DR
 (TOWER# 3)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE THRESHOLD INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE: SINCE THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) COMPLIED
  
 8) COMPLIED
  
 9) PROVISO
  
 10) PROVISO
  
 11) COMPLIED
  
 12A) COMPLIED
  
 12B) COMPLIED
  
 12C) 2ND REQUEST, PORTE COCHERE:
 THE PLANS DO NOT INDICATE AN ACCESSIBLE
 LOADING ZONE UNDER THE PORTE COCHERE.
 FAIR HOUSING ANSI 4.6
  
 12D) 2ND REQUEST, PROVIDE SIGNAGE FOR
 HANDICAPPED PARKING, AND HANDICAPPED VAN
 PARKING. RESPONCE SEE CIVEL, WHERE?
 SHEET 9 HAS HANDICAPPED ELEMENTS ON THIS
 SHEET BUT ONLY A STOP SIGN.
  
 12E) 2ND REQUEST,PLANS DO NOT INDICATE
 REACH RANGESFOR THE COMMON USE MAIL
 BOXES.
  
 12F) 2ND REQUEST, THERE ARE NO KITCHEN
 DETAILS INDICATING AN ACCESSIBLE SINK
 WITH FORWARD APPROACH. RESPONCE, SEE
 AC1.2 & AB1.1. THERE ARE NO SUCH SHEETS
 LISTED IN THE INDEX.
  
 12G) 2ND REQUEST, MISSING T-3 A4.1.14
 THE INDIVIDUAL UNITS WITH ENTRYS
 WITH 45 DEGREE WALLS MISSING THE
 REQUIRED 18" ON THE PULL SIDE OF DOOR.
 SEE ANSI 4.13.6, ONLY REQUIED ON THE
 EXTERIOR SIDE.
 THE UNIT ENTRY DOORS WITH 45 DEGREE
 WALLS ADJACENT TO THE FRONT ENTRY DOOR
 DO NOT MEET THE FAIR HOUSING GUIDELINE
 FOR AN ACCESSIBLE FRONT ENTRY, SEE
 ANSI 4.13FOR THE EXTERIOR SIDE LATCH
 SIDE OF DOOR ONLY.
  
 12H) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED.
  
 15A) COMPLIED.
  
 15B) COMPLIED.
  
 15C) 2ND REQUEST, UNIT B, UNIT C AND
 UNIT D ARE WITHIN A CORRIDOR NOT A
 BALCONY WALKWAY REQUIRING OPENING
 PROTECTIVES SEE TABLE 1016.1. SHEET FOR
 THE 3RD FLOOR BRIDGE MISSING THE RATED
 WINDOWS.A2.3.1.
  
 15D) 2ND REQUEST,
 15D) NOTE IF WINDOWS REQUIRES FIRE RATED
 GLASS, AS FAR AS I'M AWARE NO
 MANUFACTURER MAKES FIRE RATED AND LARGE
 MISSLE IMPACT RATED GLAZING!!!! SEE
 THE BUILDING OFFICIALS INTERPRETATION ON
 LARGE OR HIGH RISE BUILDINGS AS FAR AS
 SHUTTERS VS LARGE OR SMALL MISSLE RATED
 GLASS.
 *************************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY,
  
 SUBMIT: PRE-STORM PREPARATION:
  
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 15E) COMPLIED.
  
 16) COMPLIED.
  
 17A) COMPLIED.
  
 17B) COMPLIED.
  
 17C) 2ND REQUEST,ROOF TOP MECHANICAL
 UNITS AS SHOWN ON A6.1.3 DETAIL 8
 INDICATES A MINIMUM OF 18" FROM ROOF,
 SEE TABLE 1509.7 FOR MINIMUM VERTICAL
 HEIGHT.
  
 18) 2ND REQUEST, REWORD PHRASE
 "PEDESTRIAN BRIDGE TO GARAGE (UNDER
 SEPERATE PERMIT)" THIS APPEARS ON BOTH
 T3A3.1.2 AND T3A3.1.3.
  
 18B) PEDESTRIAN BRIDGE INTERFACE WILL
 REQUIRE A 1 1/2 HR RATED PROTECTIVE
 (706.7) SEE FIGURE 3104.5 CODE
 COMMENTARY.
 3104.5 FIRE BARRIERS BETWEEN PEDESTRIAN
 WALKWAYS AND BUILDINGS.
 WALKWAYS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE BUILDING BY FIRE BARRIER
 WALLS WITH A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS. THIS PROTECTION
 SHALL EXTEND VERTICALLY FROM A POINT 10
 FEET (3048 MM) ABOVE THE WALKWAY ROOF
 SURFACE OR THE CONNECTED BUILDING ROOF
 LINE, WHICHEVER IS LOWER, DOWN TO A
 POINT 10 FEET (3048 MM) BELOW THE
 WALKWAY AND HORIZONTALLY 10 FEET (3048
 MM) FROM EACH SIDE OF THE PEDESTRIAN
 WALKWAY. OPENINGS WITHIN THE L0-FOOT
 (3048 MM) HORIZONTAL EXTENSION OF THE
 PROTECTED WALLS BEYOND THE WALKWAY SHALL
 BE EQUIPPED WITH DEVICES PROVIDING A
 ?-HOUR FIRE PROTECTION RATING IN
 ACCORDANCE WITH SECTION 715 .
  
 19) COMPLIED.
  
 20) 2ND REQUEST,
 20) THE ELEVATION SHEETS AND A6.1.1
 DEPICT DETAILS WITH CAST RESIN CORNICE
 AND BANDS ON THE EXTERIOR OF THE
 BUILDING. 1406.2.2 ARCHITECTURAL TRIM
 THAT EXCEEDS 40FT IN HEIGHT ABOVE GRADE
 PLANE SHALL BE CONSTRUCTED OF APPROVED
 NONCOMBUSTIBLE MATERIALS AND SHALL BE
 SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 21)COMPLIED.
  
 22) 2ND REQUEST,RESPONCE, SEE STRUCTURAL
 SHEETS, WHERE?
 T-3 A6.1.3 DETAIL# 11 ALSO INDICATES
 THE USE OF INTEGRAL ROOF DECK PROVIDE
 ADDITIONAL INFORMATION.
  
 23) 2ND REQUEST, RESPONCE ,SEE
 STRUCTURAL WHERE?
 SAME DETAIL AS ABOVE WHAT SPANS CAN
 THE GALVANIZED METAL FURRING SPAN @ 12"
 O. C. PROVIDE THE PSF APPLIED LOAD, AND
 THICKNESS OF HI HAT IN MIL. SPANS TO BE
 TAKEN AS MULTIPLE SPANS?
  
 24A) COMPLIED.
  
 24B) COMPLIED.
  
 24C) COMPLIED.
  
 24D) COMPLIED.
  
 25: T-3 A5.1.5
 25A) 2ND REQUEST,
 DETAILS SHOW A DROPPED CEILING OVER THE
 WALKWAYS WITH METAL FRAMING NO
 INDICATION AS TO ATTACHMENT TO THE DECK
 ABOVE, SPACING OF ATTACHMENT, GAUGE OR
 SIZE OF FRAMING, OR SPACING OF FRAMING.
  
 25B) COMPLIED.
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28) COMPLIED.
  
 29) COMPLIED.
  
 30) 2ND REQUEST,
 30)SHEET M2.5 HAS NO INDICATION OF A
 SMOKEPROOF EXIT ENCLOSURE, SEE 403.13
 ALSO SEE 1019.1.3 FOR REQUIRED
 VENTILATION, AND 909.20 FOR PRESSURIZED
 STAIRS.
 KAMM RESPONE: SMOKE PROOF ENCLOSURE NOT
 REQUIRED. PLEASE REFER TO ARCHITECTURAL
 DRAWINGS AND OR ARCHITECTS RESPONCE
 LETTER. NO ARCHITECTURAL RESPONCE.
 HIGH-RISE 403
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS
 MORE THAN 75 FEET (22 860 MM) ABOVE THE
 LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS SHALL COMPLY WITH SECTIONS 909.20
 AND 1019.1.8 .
 1019.1.8 SMOKEPROOF ENCLOSURES.
 IN BUILDINGS REQUIRED TO COMPLY WITH
 SECTION 403 OR 405, EACH OF THE EXITS OF
 A BUILDING THAT SERVES STORIES WHERE THE
 FLOOR SURFACE IS LOCATED MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL
 OF FIRE DEPARTMENT VEHICLE ACCESS OR
 MORE THAN 30 FEET (9144 MM) BELOW THE
 LEVEL OF EXIT DISCHARGE SERVING SUCH
 FLOOR LEVELS SHALL BE A SMOKEPROOF
 ENCLOSURE OR PRESSURIZED STAIRWAY IN
 ACCORDANCE WITH SECTION 909.20 .
  
 31) 2ND REQUEST,
 31) PRODUCT APPROVALS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 32) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXT LOUVER DOORS
 B) EXT SOLID DOORS
 C) EXT GLAZED DOORS SWING
 D) EXT GLAZED DOORS W/ TRANSOMS, SWING
 E) CASEMENT WINDOWS
 F) MULLIONS HORIZONTAL
 G) EXT RAILINGS
 H) LOUVERS
 I) TRUSS ANCHORS
 J) ROOFING ASSEMBLIES
 1) FLAT ROOF
 2) CEMENT TILE & TYPE OF INSTALATION
 NOTE THE FLAT ROOF INFORMATION SUBMITTED
 IS REDUCED TO 1/2 SHEET, NOT READABLE TO
 COPY FOR RECORD RETENTION.
 THE CONTRACTOR DID NOT HIGHLIGHT WHICH
 SUBSYSTEM TO BE USED NOR DID THEY
 HIGHLIGHT WHICH FASTENING OPTIONS TO BE
 USED.
  
 33) COMPLIED.
  
 34) COMPLIED.
  
 35) THE WIND TUNNEL TEST DOESN'T
 INDICATE ANY PRESSURES FOR THE FLAT
 ROOF?
  
 36)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026