Plan Review Notes
Plan Review Notes For Permit 05080679
Permit Number 05080679
Review Stop P
Sequence Number 1
Notes
Date Text
2005-11-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2005 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED & DATED AS
 REQUIRED BY FS. SECTION 106.1
 2. SHTS LA-POOL 3 & LA-POOL 4 PLANS &
 PERMIT ARE REQUIRED. PLANS SHALL BE
 REVIEWED & STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPT. PRIOR TO SUBMITTING
 FOR REVIEW.
 3. SHT T-3 A2.4.1 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW THE SQUARE FOOTAGE FOR EACH AREA &
 SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ALONG WITH THE AREA
 OF ROOF THAT DRAINS ONTO THE ROOF FROM
 ABOVE FOR EACH AREA IN CALCLATIONS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS.
 4. SHTS T-3 A4.1.1 THRU T-3 A4.1.8 UNITS
 A, B, C, D, E, H, F, G & K SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FHA-98
 DESIGN MANUAL. INDICATE SPECIFICATION
 "A" OR "B" FOR EACH UNIT. SHOW THE W/C
 OPENING, (MINIMUM 33"), SHOW THE W/C AT
 18" OFF THE WALL TO THE CENTER OF THE
 FIXTURE WHERE APPLICABLE, AND 18"
 MINIMUM OFF AN ADJACENT FIXTURE. SEE
 PAGES 6.7 7.43 & 7.44. - SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES. -
 SUBMIT A DETAIL FOR BACKING FOR W/C'S,
 TUBS, SHOWERS ECT. PER REQUIREMENT 6. -
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO SHOWER & FLUSH WITH CONTROL
 WALL. INDICATE CONTROL WALL ON UNIT
 FLOOR PLAN. (SEE PAGE 7.56).
 5. SHT T-3 A4.1.9 MEN'S & WOMEN'S TOILET
 ROOMS SHALL COMPLY WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.22 WITH ALL
 SUBSECTIONS. SUBMIT A DETAIL SHOWING
 COMPLIANCE.
 6. SUBMIT CALCULATIONS FOR ALL
 AMENITITES AREAS FOR MINIMUM FACILITIES
 PER TABLES 1004.2 (BLDG) AND 403.1
 (PLMG). SHOW THE SQUARE FOOTAGE FOR ALL
 COMMON USE AREAS ALONG WITH THE
 OCCUPANCY LOAD OF EACH AREA. INDICATE
 THE LOCATION OF THE SANITARY FACILITIES
 FOR THE POOL AREA.
 7. SHT T-3 A7.1.1 FLOORS AND WALLS IN
 TOILET ROOM SHALL BE NONABSORBENT PER
 SECTIONS 1210.1 & 1210.2. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED
 WITH EXPOSED CONCRETE, GYP. BOARD AND NO
 BASE AS SHOWN IN GROUND LEVEL ROOM
 FINISH SCHEDULE.
 8. SHT T-3 A4.19 SINK IN CATERING
 KITCHEN SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. PROVIDE A
 DETAIL.
 9. SHTS T-3 A4.1.13 THRU T-3 A4.1.17
 SHALL COMPLY WITH FHA-98 DESIGN MANUAL
 REQUIREMENTS 1 THRU 7. INDICATE
 SPECIFICATION "A" OR "B". SHOW CLEAR
 FLOOR SPACE FOR ALL USABLE FIXTURES.
 SHOW ALL W/C'S TO BE 18" OFF THE WALL TO
 THE CENTER OF THE FIXTURE . SHOW ALL
 OPENINGS TO BE MINIMUM 33". INDICATE
 MEASUREMENT FROM THE CENTER LINE OF THE
 W/C'S TO THE ADJONINING FIXTURES.
 10. SHT T-3 A6.1.1 DETAIL #4 TRASH CHUTE
 WATER SUPPLY SHALL HAVE BACKFLOW
 PROTECTION. INDICATE THE METHOD OF
 BACKFLOW PROTECTION REQUIRED IN SECTION
 608 AND TABLE 608.1.
 11. SHT T-3 A6.1.3 DETAIL #10 ROOF DRAIN
 DETAIL, INDICATE MEASUREMENT FROM THE
 ROOF TO THE TOP OF THE SECONDARY ROOF
 DRAIN PIPI, (EMERGENCY OVERFLOW PIPE).
 12. SHT T-3 A8.1.1 SHOW THE BACKING FOR
 THE W/C'S PER FHA DESIGN MANUAL PAGES
 6.3 & 6.4. SHOW BACKING FOR THE TUBS PER
 PAGE 6.9.
 13. SHT P0.1 PLUMBING NOTES #1 & #24
 REFER TO FBC-2001, CODE ADOPTED FOR THIS
 JOB IS FBC-2004. PLEASE CHANGE REFERENCE
 14. SUBMIT A STORM BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM. SHOW ALL SQUARE
 FOOTAGE AS IT ACCUMULATES. INDICATE THE
 RISER NUMBER CONNECTING TO STORM DRAIN.
 INDICATE ALL PIPE SIZES AND SLOPE OF
 PIPE.
 15. SHT P2.1 NO SANITARY BRANCH LINE
 SHOWN TO RISERS S/6, S/9, S/10 OR S/46
 FROM THE BUILDING SANT. DRAIN. PLEASE
 SHOW ALL PIPING ON FLOOR PLAN. SECTION
 106.1.1.
 16. SHT P2.3 6" RWL (2200SF) SHOWN IN
 THE HALLWAY. PLEASE CLARIFY. SECTION
 106.1.1.
 17. SHT P2.4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #3).
 18. SHT P4.1 AN RPZV BACKFLOW IS
 REQUIRED ON THE WATER SERVICE TO EACH
 BUILDING.
 19. SHT P4.1 SHOWS 3" WATER SERVICE TO
 EACH TOWER, BUT CIVIL PLANS, SHTS P3.1,
 AND P6.4 SHOW 4" WATER SERVICE. PLEASE
 CORRELATE PLANS. SECTION 106.1.1.
 20. SHTS P5.1 & P5.2 SUBMIT SOVENT
 DESIGN MANUAL FOR THE SOVENT SYSTEM. THE
 SOVENT SYSTEM SHALL BE APPROVED. SECTION
 106.1.1.
 21. SHT P5.3 BLDG DRAIN ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
 THE TUB IS MISSING DOWNTREAM OF RISER
 S/33 AND TUB IS NOT VENTED AS SHOWN.
 SECTIONS 106.1.1 & 901.2.1. - W/C, LAV &
 SHOWER ARE NOT SHOWN DOWNSTREAM OF RISER
 S/34 (ROOM G 110). - MEN'S & WOMEN'S
 TOILET ROOMS , (108 & 109), ARE NOT
 SHOWN ON RISER. - THE TUB DOWNSTREAM OF
 RISER S/43 IS NOT VENTED AS SHOWN.
 SECTION 901.2.1. - LAUNDRY (103) IS NOT
 SHOWN DOWNSTREAM OF RISER S/42. - PIPING
 TO STUDIO K W/M & BATHROOM (105)
 DOWNSTREAM OF RISER S/23 NOT SHOWN.
 SECTION 106.1.1.
 22. SHT P5.3 SHOW DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM. TABLE 710.1(1)
 23. SHTS P6.1, P6.2, & P6.3 WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN 'EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 24. SUBMIT A CONDENSATE BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TERMINATION POINTS FOR THE
 CONDENSATE DRAIN AND VENT. SECTION
 106.3.5.1.3. - SUBMIT CONDENSATE RISER
 DIAGRAMS. SHOW ALL PIPE SIZES.
 25. SUBMIT STORM RISER DIAGRAMS AND A
 BUILDING DRAIN ISOMETRIC RISER DIAGRAM.
 SHOW ALL PIPE SIZES, LOCATION OF ALL
 RISER CONNECTIONS, SQUARE FOOTAGE AS IT
 ACCUMULATES IN THE SYSTEM, TERMINATION
 POINT OF STORM WATER ECT. SECTION
 106.3.5.1.3.
 26. THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CUT SECTIONS NOT SHOWN
 AND MOST RISERS NOT SHOWN.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 E. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 F. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS