2005-10-11 00:00:00DENIED:2004 FBC / TOWER 3
 1.PLAN SHEET M2.1, PLEASE CLARIFY
 DUCTWORK IN THE COVERED WALKWAY.PLAN
 INDICATES RETURN AIR GRILLES IN THE
 COVERED WALKWAY AND ALSO SHOWS DUCT
 BRANCHING OF INTO THE INDIVIDUAL CONDO
 UNITS THAT ARE IDENTIFIED AS 'TX' OR
 'DX' WHICH ACCORDING TO THE SCHEDULE ARE
 TOILET & DRYER EXHAUST RISERS.ARE ALL
 THESE EXHAUST RISERS TIED IN TOGETHER?
  
 2.PLEASE CLARIFY IN THE KEY NOTES THE
 ACRONYM E/A (EXHAUST AIR)? THIS IS NOT
 INDICATED ON ON THE HVAC ABBREVIATIONS
 LISTED ON SHEET M0.1.
  
 3.PLAN SHEET M2.1, NOT ALL UNITS
 INDICATE DRYER EXHAUST DUCT LAYOUT.
 PLAN SHEET M5.1 & M5.2 INDICATES INTAKES
 ON THE EXHAUST SHAFTS.PLEASE CLARIFY,
 IT APPEARS ALL THESE SHAFTS ARE TIED IN
 TOGETHER?
  
 4.PLAN SHEET M7.1 DETAIL 2, AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION
 REQUIRED PER 2001 FMC 307.2.3.PLEASE
 INDICATE AUXILIARY DRAIN LINE OR WATER
 LEVEL DETECTOR.
  
 5.DETAIL 2 ON M7.1 ALSO INDICATES
 LOUVERED DOOR.PLEASE NOTE, NO
 COMBUSTIBLES ALLOWED IN THE RETURN AIR
 PLENUM.THIS ALSO INCLUDES THE DOOR.
 2004 FMC 602.2.1.
  
 6.PLAN SHEET M5.1 DETAIL 1 AND 2
 REFERENCES THE ARCH PLANS FOR SHAFT
 DETAIL.THIS IS NOT SHOWN IN THE ARCH.
  
 7.PIPING CHASE INDICATED ON PLAN M5.1
 SHALL COMPLY WITH 2004 FMC 1107.2.1,
 WHERE PIPING PASSES THROUGH CONCRETE
 FLOORS, THE PIPING SHALL BE PROVIDED
 WITH SLEEVES OR THIMBLES.
  
 8.REFRIGERANT PIPING PENETRATING
 FLOORS SHALL COMPLY WITH ASHRAE 15-2001
 SECTION 8.10.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.