| 2005-10-14 00:00:00 | ******DENIED****** |
| | |
| | TOWER #3 |
| | |
| | 1) FOR REFERENCE, HIGHRISE IS DEFINED AS |
| | BUILDING GREATER THAN 75' IN HEIGHT. |
| | |
| | 2) TWO FIRE DEPARTMENT CONNECTIONS ARE |
| | REQUIRED FOR HIGHRISE BUILDINGS. PLEASE |
| | SHOW LOCATIONS ON PLANS. LOCKING CAPS |
| | ARE REQUIRED. |
| | |
| | 3) DOUBLE CHECK DETECTOR ASSEMBLY TO BE |
| | ELECTRONICALLY SUPERVISED AND BE SECURED |
| | WITH CHAIN AND LOCK. |
| | |
| | 4) ELEVATORS TO COMPLY WITH ASME/ANSI A |
| | 17.1. ELEVATOR WARNING SIGNS ARE |
| | REQUIRED. |
| | |
| | 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH |
| | REQUIREMENT FOR HANDRAILS AND GUARDS. |
| | |
| | 6) NOTE REGARDING ADDRESS HEIGHT |
| | ACKNOWLEDGED. PLEASE ILLUSTRATE ON |
| | ELEVATION SHEETS FOR FUTURE REFERENCE |
| | AND FURTHER PLAN REVIEWS. |
| | |
| | 7) PLEASE INDICATE IF ELEVATORS ARE |
| | STRETCHER ACCESSIBLE. |
| | |
| | 8) PLEASE INDICATE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS IN TERMS OF CLASS A, B, OR C. |
| | |
| | 9) TEMPORARY STANDPIPES ARE REQUIRED |
| | WHEN BUILDING REACHES 3 STORIES OR 30' |
| | IN HEIGHT. |
| | |
| | 10) STANDPIPE CONNECTIONS SHALL BE 2 |
| | 1/2"- 1 1/2" REDUCERS WITH CHAINS. |
| | |
| | 11) FIRE SPRINKLER HEADS ARE MISSING IN |
| | ELECTRICAL/PHONE ROOMS. |
| | |
| | 12) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS. HYDRAULIC CALC SHEETS |
| | WILL BE REQUIRED. |
| | |
| | 13) FIRE PUMP SERVING A HIGHRISE |
| | BUILDING SHALL BE A MINIMUM OF 1250 GPM. |
| | |
| | 14) FIRE ALARM MONITORING SHALL BE UL |
| | CERTIFIED FOR CENTRAL STATION SERVICE. |
| | |
| | 15) FIRE ALARM SYSTEM TO MEET NFPA-72 |
| | REQUIREMENTS FOR SURVIVABILITY. |
| | |
| | 16) NFPA 13R IS REFERENCED ON SHT FS0.1. |
| | THAT CODE IS APPLICABLE TO BUILDINGS UP |
| | TO AND INCLUDING 4 STORIES IN HEIGHT. |
| | |
| | 17) SMOKE DETECTOR IS MISSING IN FIRE |
| | COMMAND ROOM. |
| | |
| | 18) IN ACCORDANCE WITH LOCAL |
| | REQUIREMENTS, DUCT SMOKE DETECTORS WHERE |
| | PROVIDED SHALL BE WIRED TO THE FIRE |
| | ALARM SYSTEM TO CAUSE A GENERAL FIRE |
| | ALARM CONDITION WHEN ACTIVATED. |
| | |
| | 19) FIRE ALARM SYSTEM SHALL BE CLASS A |
| | STYLE D, OR FULLY ADDRESSABLE. |
| | |
| | 20) EXIT STAIRS ARE TO BE KEPT UP WITH |
| | CONSTRUCTION. |
| | |
| | 21) NO CUTTING OR WELDING OPERATIONS ARE |
| | PERMITTED WITHOUT APPROVAL OF THE FIRE |
| | PREVENTION BUREAU AND COMPLIANCE WITH |
| | NFPA 51B. |
| | |
| | 22) BUILDING IS TO MEET HIGHRISE |
| | REQUIREMENTS OF THE APPLICABLE BUILDING |
| | AND FIRE CODES. |
| | |
| | 23) FIRE SPRINKLER HEADS APPEAR TO BE |
| | MISSING IN COVERED WALKWAYS. PLEASE |
| | INDICATE CODE REFERENCE WHERE THIS |
| | ARRANGEMENT IS ACCEPTABLE. |
| | |
| | 24) EMERGENCY LIGHTING IS PROVIDED ON |
| | FIRST FLOOR ELECTRICAL/PHONE ROOM, BUT |
| | NOT ON UPPER FLOORS. |
| | |
| | 25) PLEASE NOTE THAT THE FIRE PUMP IS |
| | SHOWN IN THE PARKING GARAGE THAT ISN'T |
| | PART OF THIS PHASE. ADDITIONAL |
| | INFORMATION REGARDING WHAT ARRANGEMENT |
| | BY THIS OFFICE HAS BEEN ACCEPTED IS |
| | REQUIRED. THE FIRE PUMP SHALL BE 1250 |
| | GPM MINIMUM FOR A HIGHRISE BUILDING. |
| | PLEASE CONTACT THE BUREAU OF FIRE |
| | PREVENTION AT (561) 804-4724. |
| | |
| | 26) FIRE HYDRANTS TO BE WET AND |
| | OPERATIONAL PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION. |
| | |
| | 27) THE ANTICIPATED STACK EFFECT NOTE |
| | WORDING SHALL BE ADDED TO THE |
| | MEACHANICAL DRAWINGS. |
| | |
| | 28) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION TO BE IN COMPLIANCE WITH NFPA |
| | 241. |
| | |
| | 29) ALL SHAFTS LARGE ENOUGH FOR PERSONS |
| | TO FALL INTO MUST BE MARKED SHAFTWAY IN |
| | 6" LETTERS. |
| | |
| | 30) TACTILE SIGNAGE IS REQUIRED AT EXIT |
| | DOORS. |
| | |
| | 31) SIGNS ARE REQUIRED IN STAIWELLS |
| | INDICATING TOP, BOTTOM, FLOOR |
| | IDENTIFICATION AND ROOF ACCESS. |
| | |
| | 32) UL CERTIFICATION SHALL BE PROVIDED |
| | AT THE TIME OF THE FIRE ALARM ACCEPTANCE |
| | TEST FINAL. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |