Plan Review Notes
Plan Review Notes For Permit 05080679
Permit Number 05080679
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-10-14 00:00:00******DENIED******
  
 TOWER #3
  
 1) FOR REFERENCE, HIGHRISE IS DEFINED AS
 BUILDING GREATER THAN 75' IN HEIGHT.
  
 2) TWO FIRE DEPARTMENT CONNECTIONS ARE
 REQUIRED FOR HIGHRISE BUILDINGS. PLEASE
 SHOW LOCATIONS ON PLANS. LOCKING CAPS
 ARE REQUIRED.
  
 3) DOUBLE CHECK DETECTOR ASSEMBLY TO BE
 ELECTRONICALLY SUPERVISED AND BE SECURED
 WITH CHAIN AND LOCK.
  
 4) ELEVATORS TO COMPLY WITH ASME/ANSI A
 17.1. ELEVATOR WARNING SIGNS ARE
 REQUIRED.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 6) NOTE REGARDING ADDRESS HEIGHT
 ACKNOWLEDGED. PLEASE ILLUSTRATE ON
 ELEVATION SHEETS FOR FUTURE REFERENCE
 AND FURTHER PLAN REVIEWS.
  
 7) PLEASE INDICATE IF ELEVATORS ARE
 STRETCHER ACCESSIBLE.
  
 8) PLEASE INDICATE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A, B, OR C.
  
 9) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN BUILDING REACHES 3 STORIES OR 30'
 IN HEIGHT.
  
 10) STANDPIPE CONNECTIONS SHALL BE 2
 1/2"- 1 1/2" REDUCERS WITH CHAINS.
  
 11) FIRE SPRINKLER HEADS ARE MISSING IN
 ELECTRICAL/PHONE ROOMS.
  
 12) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS. HYDRAULIC CALC SHEETS
 WILL BE REQUIRED.
  
 13) FIRE PUMP SERVING A HIGHRISE
 BUILDING SHALL BE A MINIMUM OF 1250 GPM.
  
 14) FIRE ALARM MONITORING SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 15) FIRE ALARM SYSTEM TO MEET NFPA-72
 REQUIREMENTS FOR SURVIVABILITY.
  
 16) NFPA 13R IS REFERENCED ON SHT FS0.1.
 THAT CODE IS APPLICABLE TO BUILDINGS UP
 TO AND INCLUDING 4 STORIES IN HEIGHT.
  
 17) SMOKE DETECTOR IS MISSING IN FIRE
 COMMAND ROOM.
  
 18) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS WHERE
 PROVIDED SHALL BE WIRED TO THE FIRE
 ALARM SYSTEM TO CAUSE A GENERAL FIRE
 ALARM CONDITION WHEN ACTIVATED.
  
 19) FIRE ALARM SYSTEM SHALL BE CLASS A
 STYLE D, OR FULLY ADDRESSABLE.
  
 20) EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 21) NO CUTTING OR WELDING OPERATIONS ARE
 PERMITTED WITHOUT APPROVAL OF THE FIRE
 PREVENTION BUREAU AND COMPLIANCE WITH
 NFPA 51B.
  
 22) BUILDING IS TO MEET HIGHRISE
 REQUIREMENTS OF THE APPLICABLE BUILDING
 AND FIRE CODES.
  
 23) FIRE SPRINKLER HEADS APPEAR TO BE
 MISSING IN COVERED WALKWAYS. PLEASE
 INDICATE CODE REFERENCE WHERE THIS
 ARRANGEMENT IS ACCEPTABLE.
  
 24) EMERGENCY LIGHTING IS PROVIDED ON
 FIRST FLOOR ELECTRICAL/PHONE ROOM, BUT
 NOT ON UPPER FLOORS.
  
 25) PLEASE NOTE THAT THE FIRE PUMP IS
 SHOWN IN THE PARKING GARAGE THAT ISN'T
 PART OF THIS PHASE. ADDITIONAL
 INFORMATION REGARDING WHAT ARRANGEMENT
 BY THIS OFFICE HAS BEEN ACCEPTED IS
 REQUIRED. THE FIRE PUMP SHALL BE 1250
 GPM MINIMUM FOR A HIGHRISE BUILDING.
 PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 804-4724.
  
 26) FIRE HYDRANTS TO BE WET AND
 OPERATIONAL PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 27) THE ANTICIPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE
 MEACHANICAL DRAWINGS.
  
 28) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO BE IN COMPLIANCE WITH NFPA
 241.
  
 29) ALL SHAFTS LARGE ENOUGH FOR PERSONS
 TO FALL INTO MUST BE MARKED SHAFTWAY IN
 6" LETTERS.
  
 30) TACTILE SIGNAGE IS REQUIRED AT EXIT
 DOORS.
  
 31) SIGNS ARE REQUIRED IN STAIWELLS
 INDICATING TOP, BOTTOM, FLOOR
 IDENTIFICATION AND ROOF ACCESS.
  
 32) UL CERTIFICATION SHALL BE PROVIDED
 AT THE TIME OF THE FIRE ALARM ACCEPTANCE
 TEST FINAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  