| 2005-09-26 00:00:00 | SAIL CLUB TOWER #3 |
| | |
| | **** UNSAT **** |
| | |
| | |
| | 1)NOTE: PLEASE SEE CODE REFERENCED ON |
| | PLANS LIST THE 1999 NEC. PLEASE KNOW, AS |
| | OF JULY 1ST 2003, THE STATE ADOPTE DTHE |
| | 2002 NEC. |
| | PLEASE ALSO SEE WE ARE UNDER THE 2003 |
| | NFPA-101 AND 2002 NFPA-72 |
| | PLEASE ADJUST. |
| | |
| | 2)NOTE: PLEASE SEE BLDG /FIRE REVIEW |
| | COMMENTS FOR STAIR TOWER EXITING WHICH |
| | WILL AFFECT ELECTRICAL LAYOUT. |
| | EXITS BACK INTO HALL WAY AREAS IN FRONT |
| | OF UNITS. |
| | |
| | 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. |
| | PLEASE SEE SOME AREAS WHICH ELECTRICAL |
| | FIXTURES SEEM TO BE MISSINGTHIS. |
| | PLEASE ALSO SEE CIRCUITING FOR UNITS. |
| | PLEASE KNOW, A "TYPICAL" UNIT LAYOUT MAY |
| | BE PROVIDED, HOWEVER A LAYOUT WOULD BE |
| | REQUIRED FOR EACH UNIT TYPE, INCLUDING |
| | STUDIO UNIT. |
| | CIRCUITING FOR SOME UNITS/ITEMS CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | |
| | 4)NOTE: PLEASE PROVIDE PHOTO-METRICS FOR |
| | STAIR TOWERS ON NORMAL PWR AND STAND-BY. |
| | ALONG WITH WALK AREAS. |
| | PLEASE SEE STAIR TOWERS UNDER NORMAL PWR |
| | SHALL MEET A MIN OF 10FT CANDLES. PLEASE |
| | SEE ARES FOR HALLS ETC ARE PERMITTED TO |
| | BE LESS. . |
| | PLEASE SEE NFPA-101 7.8.1.3,7.9.2.1 |
| | |
| | 5)NOTE: PLEASE SEE ONE STAIR TOWER SHOWS |
| | CIRCUITING FOR LTS FROM NORMAL POWER |
| | PANEL AND CIRCUTING. |
| | PLEASE SEE THESE ARE REQUIRED TO BE ON |
| | EM POWER PANEL. |
| | PLEASE KNOW, BATTERY BACK FIXTURES WILL |
| | BE REQUIRED AT EVERY OTHER LEVEL(MIN). |
| | PLEASE SEE LS 101 WHICH MENTIONS THE |
| | TRIPPING/THROW OF A SINGLE BRKR SAHLL |
| | NOT LEAVE ANY EGRESS AREA IN TOTAL |
| | DARKNESS. PLEASE CALL ELECTRICAL PLAN |
| | REVIEW AND FIRE MARSHALS OFFICE TO GO |
| | OVER OPTIONS PERMITTED. |
| | A BATTERY BACK-UP FIXTURE AT EVERY OTHER |
| | LEVEL WILL SATISFY THIS OFFICE AND AHJ. |
| | PLEASE BE SURE TO MEET THE MIN OF 1 |
| | FT/CANDLE UNDER EM. |
| | PLEASE BE SURE TO SEE PREVIOUS NOTE #4 |
| | FOR LIGHTING LEVELS.(MIN) |
| | |
| | 6)NOTE: PLEASE PROVIDE BATTERY BACK-UP |
| | FIXTURES IN MAIN ELECTRICAL RMS AND |
| | ELEVATOR ROOM(S), GENERATOR AND FIRE |
| | PUMP ROOM. PLEASE ALSO PROVIDE |
| | CIRCUITING FOR THESE |
| | RMS. |
| | |
| | 7)NOTE: PLEASE PROVIDE CURB DETAIL FOR |
| | BUS-DUCT RISER AND FLOOR PENATRATIONS. |
| | 368.6 |
| | |
| | 8)NOTE: PLEASE PROVIDE NOTES ON RISER |
| | AND ELECTRICAL ROOM SHEETS FOR |
| | REQUIREMENTS OF 110.26 FOR PANIC |
| | HARDWARE AND DOOR SWINGS. |
| | PLEASE SEE MIN CLEARENCE PER 110.26 |
| | |
| | 9)NOTE: PLEASE SEE RISER INDICATES ALL |
| | BUS-DUCT FROM FPL VAULT TO MAIN |
| | ELECTRICAL ROOM AS OVER-HEAD. PLEASE SEE |
| | 230.70, 230.6, NO MORE THAN 8' OF |
| | UNPROTECTED CONDUCTORS/ OR BUS DUCT |
| | PERMITTED "INSIDE THE BLDG. |
| | PLEASE SEE ROUTING OF BUS-DUCT APPEARS |
| | TO SHOW INSTALLATION INSIDE CONDO |
| | UNITS?? |
| | |
| | 10)NOTE: PLEASE PROVIDE INFORMATION ON |
| | BUS -DUCT RISER MAINS. APPEARS TO SHOW |
| | THESE AS "SHUNT-TRIP" AND NOT CONTAINING |
| | A MANUAL MEANS OF DISCONNECT LOCATED ON |
| | THE OUTSIDE OF THE EQUIPMENT. PLEASE SEE |
| | MAIN PANEL SCHEDULE(S), THESE DO NOT |
| | SEEM TO INDICATE A MCB. |
| | 230.76,230.79 |
| | |
| | 11)NOTE: PLEASE CORRELATE ALL MAINS ETC |
| | FOR SIZING. PLEASE SEE KEY NOTES |
| | MENTIONS 2500A AND PLANS ALSO INDICATE |
| | 3000A.? |
| | |
| | 12)NOTE: PLEASE PROVIDE SPECIFIC |
| | INFORMATION ON BUS-DUCT, PLEASE SEE AN |
| | ALUM EQUIPMENT GROUNDING CONDUCTOR/ |
| | MATERIAL IS NOT PERMITED. |
| | 310.2. LOCAL AMENDMENTS. |
| | |
| | 13)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| | SPECS AND CUT SHEETS FOR GENERATOR, ATS, |
| | FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE ALSO SUBMIT THE SAME FOR ANYSUB |
| | BASE FUEL TANK. |
| | PLEASE KNOW, DUE TO THE INFORMATION NOT |
| | BEING SUBMITTED AT THIS TIME, REVIEW FOR |
| | SOME ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE DONE. |
| | UNABLE TO VERIFY CODE COMPLIANCE FOR |
| | MANY ITEMS UNDER NFPA, 20,70,101,110 |
| | ETC. |
| | |
| | 14)NOTE: PLEASE SEE ELECTRICAL RISER |
| | DIAGRAM DOES NOT CONTIAN ANY INFORMATION |
| | FOR FIRE PUMP OR FIRE PUMP CONTROLLER, |
| | SERVICE, SIZING , CONDUCTORS ETC. |
| | PLEASE COMPLETE. |
| | ENCASEMENT IN CONCRETE, OUTSIDE THE |
| | BLDGS, ETC |
| | |
| | 15)NOTE: PLEASE SEE AREA FOR GARAGE |
| | CONTAINING THE LOCATION OF FIRE PUMP AND |
| | GENERATOR WILL BE REQUIRED TO BE |
| | SUBITTED FOR PERMIT AND REVIEW. |
| | PLEASE SEE LOCATIONS FOR FIRE |
| | SEPARATIONS, ACCESS, LIGHTING, ETC CAN |
| | NOT BE REVIEWED AT THIS TIME. |
| | |
| | 16)NOTE: PLEASE VERIFY LOCATION OF |
| | GENERATOR. |
| | PLEASE SEE PLANS SEEM TO INDICATE FIRE |
| | PUMP AND GEN RM LOCATED AT FIRST FLR |
| | LEVEL, HOWEVER RISER SEEMS TO SHOW THESE |
| | AT 2ND FLR LEVEL? |
| | PLEASE CLARIFY. |
| | |
| | 17)NOTE: PLEASE PROVIDE DISCONNECTING |
| | MEANS FOR ALL A/C EQUIPMENT AT ROOF TOP |
| | LEVEL. A"TYPICAL" DETAIL MAY BE GIVEN |
| | FOR THESE.440.11 |
| | PLEASE ALSO INDICATE ALL ROOF TOP GFI |
| | RECEPTS PER 210.63 |
| | PLEASE CORRELATE ALL A/ KW RATINGS AND |
| | LOADS WITH MECHANICNAL PLANS . (KW |
| | RATINGS ETC). |
| | |
| | 18)NOTE: PLEASE SEE FIRE REVIEW NOTES |
| | ALSO: PLEASE PROVIDE A LAYOUT FOR |
| | CENTRAL STATION RM(FIRE COMMAND RM) |
| | SHOWING ALL DEVICES/ PANELS/ STATUS |
| | PANELS ETC. |
| | PLEASE LIST ALL ITEMS AS SPECIFIED IN |
| | NFPA- 101 11.8.5, |
| | |
| | 19)NOTE: PLEASE SEE RECEPTS MISSING PER |
| | 210.52 |
| | SEE REDLINED PLANS. |
| | |
| | 20)NOTE: PLEASE CALRIFY THE "P" LOCATED |
| | NEXT TO SMOKE DETECTORS? |
| | |
| | 21)NOTE: PLEASE VERIFY CIRCUITING OF |
| | LAUNDRY RM/ WASHER CIRCUIT. |
| | PLEASE SEE 210.11C2,210.52F,220.16 |
| | PLEASE ALSO SEE MIN 1500VA. |
| | PLEASE VERIFY LOAD FOR WASHER. |
| | |
| | 22)NOTE:PLEASE PROVIDE NOTE ON PLANS |
| | FOR SMOKE DETECTOR PLACEMENT PER |
| | REQUIREMENTS NFPA -72 11.8.3.5. |
| | |
| | 23): PLEASE PROVIDE NOTE FOR ALL |
| | ELECTRICAL DEVICES TO BE INSTALLED PER |
| | FAIR HOUSING ACT REGULATIONS, (FHAR) 24 |
| | CFR 100.205 |
| | |
| | 24)NOTE: PLEASE SEE 210.52C1 FOR SOME |
| | MISSING KITCHEN COUNTERSPACE RECEPTS. |
| | PLEASE ALSO SEE COUNTERSPACE APPEARS TO |
| | SHOW A DEDICATED CIRCUIT (19) FOR |
| | MICROWAVE WHICH ALSO APPEARS TO BE THE |
| | RECEPT FOR KITCHEN COUNTERSPACE? |
| | IF THE MICROWAVE IS A DEDICATED RECEPT, |
| | THEN AN ADDTIONAL GFI WOULD BE REQUIRED. |
| | 210.8A16. |
| | |
| | 25)NOTE: PLEASE SEE A 70A BRKR IS BEING |
| | SHOWN FOR RANGE?? |
| | PLEASE SEE 210.23,422.11B |
| | 50A RANGE RECEPT, 50A BRKR MAX. |
| | |
| | 26)NOTE: PLEASE SEE PANEL SCHEDULES SEEM |
| | TO SHOW "A" AND "C" PHASE FOR SINLGLE |
| | PHASE SERVICE AND UNITS?? |
| | PLEASE CLARIFY / ADJSUT. |
| | 215.5 |
| | |
| | 27)NOTE: PLEASE LABEL AND /OR CLARIFY |
| | "DINING" AREAS IN ALL UNITS. |
| | UNABLE TO VERIFY CIRCUITING AS DINING |
| | /LIVING ARE SEEMED TO BE COMBINED.' |
| | PLEASE SEE 210.52B1 |
| | |
| | 28)NOTE: PLEASE SEE 210.52D FOR SOME |
| | UNITS MISSING GFI'S WITH IN 3' OF LAV'S. |
| | PLEASE ALSO SEE A GFI MAY NOT PERMITTED |
| | ON THE OTHER SIDE OF A LAV TO MEET |
| | 210.52D (3'). |
| | GFI 'S MAY BE MOVED IN BETWEEN BOTH |
| | LAV'S OR AN ADDITIONALRECEPT MAY BE |
| | ADDED. |
| | |
| | 29)NOTE: PLEASE SEE MISSING RECEPTS IN |
| | HALLWAY AREAS, 10' OR MORE OF CONTINUOUS |
| | WALL. |
| | 210.52H. |
| | |
| | 30)NOTE: PLEASE SEE RISER SEEMS TO |
| | INDICATE A POOL PANEL, HOWEVER NO OTHER |
| | INFORMATION WAS SUBMITTED AND PANEL |
| | COULD NOT LOCATED ON PLANS. |
| | LOADS ETC. |
| | 215.5, 220 |
| | |
| | 31)NOTE: PLEASE VERIFY BATH CIRCUITS |
| | BEING SHOWN WITH ARC FAULT PROTECTION?? |
| | 210.8 REQUIRES GFI PROTECTION FOR BATHS |
| | AND 210.12 ARC FAULT PROTECTION FOR |
| | BEDROOM CIRCUITS? |
| | THIS IS ONLY A NOTE: |
| | |
| | 32)NOTE: PLEASE PLACE NOTE ON "ROOF |
| | PLANS" WHICH WILL REQUIRE ALL LIGHTNING |
| | PROTECTION |
| | |
| | |
| | 33)NOTE: PLEASE IDICATE ON PLANS/RISER |
| | IF GENERATOR WILL BE A "SEPARATELY |
| | DERIVED SYSTEM" OR A " NON SEPARATELY |
| | DERIVEDSYSTEM. |
| | IF SD, PLEASE INCLUDE GROUNDING |
| | ELECTRODE SYSTEM PER 250.30 |
| | |
| | 34)NOTE: PLEASE INDICATE IF PANELS EH2A- |
| | EH12A ARE FEED THRU LUGS OR DOS EACH |
| | PANEL CONTAIN OCP FOE EACH.? |
| | PLEASE ALSO SEE PANELS H5A-9, 12 ETC. |
| | 215.5 |
| | |
| | 35)NOTE: PLEASE PROVIDE PANEL SCHEDULE |
| | FOR PANEL H2AA ON RISER. |
| | 215.5 |
| | |
| | 36) NOTE: PLEASE SEE PANEL H16A |
| | INDICATES H12A AND H12B ON LOAD CALCS?? |
| | RISER APPEARS TO SHOW H16A BEING FED |
| | FROM SBA AND SHOWS H12A FROM H9A ETC. |
| | 215.5 |
| | |
| | 37)NOTE: PLEASE CLARIFY NOTES # 5 AND #6 |
| | ON GROUNDING RISER? |
| | 250.50 |
| | |
| | 38)NOTE: PLEASE SEE RISER DIAGRAM WHICH |
| | SHOWS GENERATOR FEEDING TOWER #3 (THIS |
| | TOWER) AND ALSO SHOWS FEEDING TOWER #1?? |
| | PLEASE SEE ELECTRICAL ROOM PLANS SHOW |
| | FEEDING TOWERS #3 AND #4?? |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 39)NOTE: PLEASE SUBMIT "SPEC BOOKS' FOR |
| | REVIEW OF PROJECT. |
| | THESE WOULD CONTAIN JOBSITE SPECS. |
| | |
| | 40)NOTE: PLEASE BE SURE ALL CONTINUOUS |
| | LOADS ARE SHOWN AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | 41)NOTE: NOTE ADDED AFTER REVIEW OF |
| | TOWER #4, |
| | PLEASE SEE MIN OCP FOR AHU HEAT TO BE |
| | 125%. 424.3B |
| | SHOWS 50A OCP. |
| | |
| | ** PLEASE SEE THAT NO PLANS, PERMIT |
| | APPLICATION ETC WAS SUBMITTED FOR GARAGE |
| | BLDGS. |
| | |
| | ** PLEASE KNOW, MANY OF THE ABOVE ITEMS |
| | ARE "REDLINED" AT LOCATIONS ON PLANS FOR |
| | NOTES. |
| | |
| | ** PLEASE KNOW, A RESPONSE LETTER IN |
| | TYPE WRITTEN FORM WILL HELP IN RESPONSES |
| | TO ELECTRICAL COMMENTS. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | ** PLEASE BE SURE TO "REMOVE" ALL OLD |
| | VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO THE COMPLETED SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | ** PLEASE SEE BLDG REVIEW COMMENTS WHICH |
| | WILL REQUIRE ALL PRODUCT APPROVALS, |
| | SUBMITTALS ETC TO BE DETACHED FROM |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-09-21 00:00:00 | ************ UNSAT ********* |
| | |
| | SAIL CLUB |
| | TOWER #3- 16- STORY |
| | |
| | NOTES TO FOLLOW. |
| 2005-09-16 00:00:00 | REVIEW STARTED. |
| 2005-09-11 00:00:00 | IN ELECTRIC FOR REVIEW. |
| | REVIEWS IN PROGRESS . |