| 2006-05-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1. INFORMATIONAL |
| | |
| | 2. ALL PLANS DESIGNED BY A PROFESSIONAL |
| | ARCHITECT OR ENGINEER, THEN ALL SHEETS |
| | SHALL BE SIGNED, SEALED, & DATED AS |
| | REQUIRED BY FLORIDA STATUTES. SECTION |
| | 106.1. |
| | ***RESPONSE NOTED, BUT BOUNDRY SURVEY, |
| | SHTS PP1 OF 9 THRU PP9 OF 9, LA-POOL-1 |
| | THRU LA-POOL-4, LA-FW-1 THRU LA-FW-6 ARE |
| | NOT SIGNED, SEALED, DATED AS REQUIRED. |
| | |
| | 3. SHTS LT-2, A2.3.1A, & A2.3.1B. SUBMIT |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS. SHOW SQUARE FOOTAGE DRAINED |
| | AT EACH ROOF DRAIN, WITH 1/2 AREA OF ALL |
| | VERTICAL WALLS, INCLUDING PARAPETS, AND |
| | ROOF AREA FROM ABOVE SHOWN IN |
| | CALCULATIONS. SECTION 1106 & 1107 AND |
| | ALL SUBSECTIONS. |
| | ***RESPONSE NOTED, BUT NO REFERENCE TO |
| | CONTRIBUTIONS FROM UPPER ROOFS THAT |
| | DRAIN ONTO THE ROOF FROM ABOVE IS SHOWN |
| | IN THE CALCULATIONS. |
| | |
| | 4. SHEETS FOR ALL UNITS TYPES, IF THERE |
| | IS AN ELEVATOR IN THE BUILDING, |
| | (INCLUDING THE PARKING GARAGE), THEN ALL |
| | UNITS SHALL COMPLY WITH FHA-98 |
| | REQUIREMENTS 1 THRU 7. SUBMIT DETAILS |
| | FOR BACKING FOR THE WATER CLOSET IN |
| | POWDER ROOM. SHOW CLEAR FLOOR SPACE FOR |
| | ALL USABLE FIXTURES. W/C REQUIRES A MIN. |
| | 48" CLEAR FLOOR SPACE. LAV IN POWDER |
| | SHALL BE A MAX. 34" TO FLOOD RIM LEVEL, |
| | INDICATE ON PLANS. SEE PAGES 7.33, 7.43. |
| | LAV SHALL EITHER BE CENTERED ON THE 48" |
| | LENGTH OF A PARALLEL CLEAR FLOOR SPACE, |
| | OR A REMOVABLE BASE CABINET WITH 30" |
| | CLEAR WIDTH FOR FRON APPROACH. SUBMIT |
| | DETAILS. |
| | ***NO RESPONSED FROM THE ARCHITECT, |
| | COMMENT NOT ADDRESSED. |
| | |
| | 6. SHTS P2.3.1 & P2.3.2 SEE COMMENT #3, |
| | CALCULATIONS FOR PRIMARY AND SECONDARY |
| | ROOF DRAINS REQUIRED. SECTIONS 1106 AND |
| | 1107. |
| | ***RESPONSE NOTED, BUT NO REFERENCE TO |
| | UPPER ROOFS. (SEE COMMENT #3) |
| | |
| | 7. SHT P5.1 SANITARY RISER ISO. |
| | CLEANOUTS FOR THE W/M SHALL BE INSTALLED |
| | 4' ABOVE THE FLOOR, AND A STANDPIPE IS |
| | REQUIRED FOR THE W/M. SECTIONS 708.9 AND |
| | 1002.1. |
| | ***RESPONSE NOTED, BUT COMMENT NOT |
| | ADDRESSED. |
| | |
| | |
| | 9. SHT P5.1 THE FOLLOWING INFORMATION IS |
| | REQUIREMENTS FOR GAS PERMIT: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ***RESPONSE NOTED, BUT CORRESPONDING |
| | LENGTHS ARE NOT INDICATED. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ***RESPONSE NOTED, BUT DELIVERY PRESSURE |
| | NOT SHOWN AS INDICATED. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SECTION 402.2. |
| | ***RESPONSE NOTED, BUT MANUF. SHEETS |
| | HAVE NOT BEEN SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | ***NO RESPONSE, AND VOIDED SHEETS SHALL |
| | BE REMOVED. |
| | |
| | ***************NEW COMMENT************** |
| | 1B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL & FS 553.80(2)(B). |
| | |