Plan Review Notes
Plan Review Notes For Permit 05080678
Permit Number 05080678
Review Stop P
Sequence Number 2
Notes
Date Text
2006-05-13 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. INFORMATIONAL
  
 2. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED, & DATED AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
 ***RESPONSE NOTED, BUT BOUNDRY SURVEY,
 SHTS PP1 OF 9 THRU PP9 OF 9, LA-POOL-1
 THRU LA-POOL-4, LA-FW-1 THRU LA-FW-6 ARE
 NOT SIGNED, SEALED, DATED AS REQUIRED.
  
 3. SHTS LT-2, A2.3.1A, & A2.3.1B. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FOOTAGE DRAINED
 AT EACH ROOF DRAIN, WITH 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS, AND
 ROOF AREA FROM ABOVE SHOWN IN
 CALCULATIONS. SECTION 1106 & 1107 AND
 ALL SUBSECTIONS.
 ***RESPONSE NOTED, BUT NO REFERENCE TO
 CONTRIBUTIONS FROM UPPER ROOFS THAT
 DRAIN ONTO THE ROOF FROM ABOVE IS SHOWN
 IN THE CALCULATIONS.
  
 4. SHEETS FOR ALL UNITS TYPES, IF THERE
 IS AN ELEVATOR IN THE BUILDING,
 (INCLUDING THE PARKING GARAGE), THEN ALL
 UNITS SHALL COMPLY WITH FHA-98
 REQUIREMENTS 1 THRU 7. SUBMIT DETAILS
 FOR BACKING FOR THE WATER CLOSET IN
 POWDER ROOM. SHOW CLEAR FLOOR SPACE FOR
 ALL USABLE FIXTURES. W/C REQUIRES A MIN.
 48" CLEAR FLOOR SPACE. LAV IN POWDER
 SHALL BE A MAX. 34" TO FLOOD RIM LEVEL,
 INDICATE ON PLANS. SEE PAGES 7.33, 7.43.
 LAV SHALL EITHER BE CENTERED ON THE 48"
 LENGTH OF A PARALLEL CLEAR FLOOR SPACE,
 OR A REMOVABLE BASE CABINET WITH 30"
 CLEAR WIDTH FOR FRON APPROACH. SUBMIT
 DETAILS.
 ***NO RESPONSED FROM THE ARCHITECT,
 COMMENT NOT ADDRESSED.
  
 6. SHTS P2.3.1 & P2.3.2 SEE COMMENT #3,
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS REQUIRED. SECTIONS 1106 AND
 1107.
 ***RESPONSE NOTED, BUT NO REFERENCE TO
 UPPER ROOFS. (SEE COMMENT #3)
  
 7. SHT P5.1 SANITARY RISER ISO.
 CLEANOUTS FOR THE W/M SHALL BE INSTALLED
 4' ABOVE THE FLOOR, AND A STANDPIPE IS
 REQUIRED FOR THE W/M. SECTIONS 708.9 AND
 1002.1.
 ***RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED.
  
  
 9. SHT P5.1 THE FOLLOWING INFORMATION IS
 REQUIREMENTS FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT CORRESPONDING
 LENGTHS ARE NOT INDICATED.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ***RESPONSE NOTED, BUT DELIVERY PRESSURE
 NOT SHOWN AS INDICATED.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SECTION 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEETS
 HAVE NOT BEEN SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO RESPONSE, AND VOIDED SHEETS SHALL
 BE REMOVED.
  
 ***************NEW COMMENT**************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL & FS 553.80(2)(B).
  
 REVIEW BY KEN STEVENS