2006-04-26 00:00:00DENIED:LOFT #2 / 2004 FBC
 COMMENT #1 FROM REVIEW DATED 10-06-05:
 REQUEST FOR SUBMITTAL OF GAS APPLIANCES
 WAS NOT ADDRESSED.
  
 COMMENT #3 INDICATES DYRER EXHAUST IS
 "APPROXIMATELY 25 FT,PLEASE NOTE, PER
 2004 FMC 504.6, 25 FT IS THE MAXIMUM
 LENGTH PERMITED.PLEASE VERIFY LENGTH.
  
 COMMENT #5:COMMENT WAS NOT ADDRESSED.
 RESPONSE INDICATES THE CORRIDOR IS NOT A
 REQUIRED EGRESS, ITS ONLY FOR
 CONVENIENCE ONLY.VENTILATION IS STILL
 REQUIRED IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3. THIS MAY NOT BE A
 "REQUIRED" EGRESS BUT IT STILL IS AN
 EGRESS AND WILL BE TREATED AS SUCH.
  
 COMMENT #9 RESPONSE INDICATES DETAIL
 SHOWN IN THE STRUCTURAL & ARCHITECTURAL
 PLANS.PLAN SHEET S-6 AHU LOCATED ABOVE
 THE BATHROOM, BUT DOES NOT INDICATE
 HANGING DETAIL AND ACCESS DOES NOT
 APPEAR TO COMPLY WITH 2004 FMC 306.1 &
 306.3.
  
  
 NEW COMMENTS:
 PLEASE CLARIFY PLAN SHEET A2.3.1A, PLAN
 INDICATES 3 ACCESS DOORS FROM THE GARAGE
 TO THE ROOF OF THE RESIDENTAL UNITS
 WHERE THE CONDENSORS ARE LOCATED.
 PLEASE INDICATE THE HEIGHT OF THE "PARTY
 WALL" ABOVE THE ROOF SURFACE.PER 2004
 FMC 306.5 ACCESS TO EQUIPMENT LOCATED ON
 A ROOF SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES.
  