| 2006-04-27 00:00:00 | ********** UNSAT 2ND REVIEW ************ |
| | |
| | |
| | **PLEASE KNOW, MOST COMMENTS FROM |
| | PREVIOUS REVIEW WERE ADDRESSED, HOWEVER |
| | ONLY A FEW REMAIN ALONG WITH A COUPLE OF |
| | NEW COMMENTS DUE TO SOME CHANGES IN |
| | PLANS AND A NEW COMMENT WITH RESPECT TO |
| | CALCULATIONS WHICH WAS MISSED ON |
| | PREVIOUS REVIEW. |
| | PLEASE SEE NOTE SBELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | ** PLEASE ALSO SEE LAST NOTE, AS ALL |
| | OLD/VOIDED SHEETS WERE LEFT IN SETS WHEN |
| | IT WAS REQUESTED FOR SHEETS TO BE |
| | REMOVED. |
| | |
| | SAIL CLUB |
| | LOFT BUILDING #2 |
| | |
| | 1)NOTE: OK, ADDED FOR INTERIOR CORRIDOR |
| | LTS. |
| | |
| | 2)NOTE: OK. |
| | |
| | 3)NOTE:NOTE #3 NO, PLEASE INDICATE THE |
| | FOLLOWING CURRENT CODES; 2002 NFPA-70, |
| | 2002 NFPA-72, AND 2003 NFPA-101. |
| | |
| | **PREVIOUS NOTE** |
| | PLEASE SEE PLANS REFERENCE THE |
| | 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003 |
| | THE STATE ADOPTED THE 2002 NEC. |
| | |
| | 4)NOTE: OK. |
| | |
| | 5)NOTE:NOTE #5 NO, PLEASE EXPLAIN HOW |
| | THIS IS A AND C PHASE? |
| | THIS SERVICE IS BEING SHOWN AS ONLY A |
| | SINGLE PAHSE TO UNITS.? |
| | |
| | **PREVIOUS NOTE** |
| | PLEASE SEE PANEL INDICATES "A" AND "C" |
| | PHASES? PLEASE CLARIFY AS SERVICE IS |
| | SHOWN AS SINGLE PHASE. A&B) |
| | |
| | 6)NOTE: OK. |
| | |
| | 7)NOTE: OK. |
| | |
| | 8)NOTE: NOTE #8 OK, HOWEVER PLEASE |
| | INDICATE RANGE AS A "GAS RANGE" IF |
| | INDEED SO. PLEASE SEE RESPONSE ONLY |
| | MENTIONS THE OCP ETC WS CORRECTED. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE CLARIFY AND ADJUST OCP SHOWN FOR |
| | RANGE. PANEL SCHEDULE INDICATES A 70A 2P |
| | BRKR FOR WHAT WOULD BE A 50A RECEPT FOR |
| | RANGE. PLEASE SEE 406.2B, 210.21B3,4 |
| | |
| | 9)NOTE: OK. |
| | |
| | 10)NOTE: OK |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE:NOTE #12 NO, ? PLEASE SEE |
| | RESPONSE MENTIONS TO SEE 3.1 "LT SWITCH |
| | CONTROLS EXTERIOR LT", HOWEVER PLEASE |
| | SEE NO E 3.1 WAS SUBMITTED AND UNITS DO |
| | NOT INDICATE A LT SW AT DOOR ARE FOR |
| | MEANS OF EGRESS? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE MISSING EGRESS LT CONTROL FOR |
| | UNITS WITH GRADE LEVEL ACCESS. |
| | OR PLEASE SEE EXCEPTIONS PERMITTED OR |
| | ACCEPTABLE TO THE AHJ. |
| | LS 101 7.8 |
| | |
| | 13)NOTE: OK. |
| | |
| | 14)NOTE: OK. |
| | |
| | 15)NOTE:OK. |
| | |
| | 16)NOTE: OK. |
| | |
| | |
| | |
| | PLEASE SEE DUE TO THE COMMENTS IN NOTE |
| | #1 AND THE CHANGES IN ELECTRICAL |
| | SERVICE. THERE MAY BE FUTURE COMMENTS. |
| | |
| | ********** NEW NOTES *********** |
| | |
| | 1) NOTE: PLEASE SEE SERVICE ENTRANCE |
| | CONDUCTORS FOR "MCSL", WHICH HAVE BEEN |
| | CHANGED. PLEASE SEE MININUM REQUIRED PER |
| | 310.16,240.4. ONLY ONE SET IS BEING |
| | SHOWN FOR 800A SERVICE. |
| | |
| | 2) NOTE: PLEASE SEE DIVERSITY FACTOR ON |
| | METER CENTERS. PLEASE SEE THE # OF UNITS |
| | BEING INDICATED ANDCORRELATE WITH THE |
| | NUMBER OF UNITS ON RISER. |
| | THIS COMMENT WAS NOT ON PREVIOUS PLANS, |
| | HOWEVER WAS ABOUT THE SAME, AS SERVICE |
| | HAS CHANGED SOME. |
| | 215.5 |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | **************************************** |
| | PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE ATTACHED TO EACH OTHER TO COMPOSE OF |
| | ONE SET OF VOIDED SHEETS ONLY AND WILL |
| | BE SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE. |
| | ************************************** |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |