Plan Review Notes
Plan Review Notes For Permit 05080678
Permit Number 05080678
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-17 00:00:00 
 PERMIT: 05080678
 ADD: 719 EXECUTIVE CENTER DR
 (LOFT# 2)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTES 1-10 TOTALLY IGNORED, NOT IN
 RESPONCE COMMENTS.
  
 1)******IMPORTANT NOTE IGNORED********
 EITHER THE CONTRACTOR OR THE DESIGN
 PROFESSIONAL HAS TO TAKE RESPONSIBILITY
 FOR THIS PROJECT AND COMPLY WITH THIS
 REQUEST, AND REMOVE ALL VOIDED SHEETS
 FROM THE PERMIT DOCUMENTS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)2ND REQUEST,
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
  
  
 3A)2ND REQUEST,109.3.7*THIS PARTICUAL
 TYPE OF BUILDING WILL REQUIRE A RESIDENT
 INSPECTOR NOT A THRESHOLD INSPECTOR.
 FORMS WILL NEED TO BE FILED OUT FOR THE
 RESIDENT INSPECTOR, CONTACT HAROLD
 PISKURA, INSPECTION SERVICES MANAGER @
 (561)805-6711 TO SEET UP AN APPOINTMENT.
  
 **********NOTE**********
 THIS PERMIT WILL BE ONLY FOR THE LOFT
 UNITS. PLANS INDICATE THAT A (6)
 STORY ENCLOSED PARKING GARAGE WILL BE
 BUILT IN THE FUTURE WHICH MAY OR MAY NOT
 HAPPEN.NOTE ALSO UNDER LOFTS A & B
 BUILDING1 OF 7 UNITS? IN EACH BUILDING
 THERE IS 30 UNITS.
  
 B)COMPLIED.
  
 3B) COMPLIED LOFTS NOT A THRESHOLD BLDG.
  
 3C)COMPLIED, NOT A THRESHOLD BLDG.
  
 3D) NOTE:IF THIS BUILDING WILL REQUIRE
 (3) OF ALL DOCUMENTS FOR REVIEW FOR A
 SPECIAL (RESIDENT INSPECTOR).
  
 4) NOTE 2ND REQUEST,
 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) 2ND REQUEST SITE PLAN NEEDS TO BE
 SUBMITTED TO ADDRESSING PERSONEL LILI
 URSA FOR ADDRESSING AS WELL AS NEW PLAT
 MAP FOR THE COMBINATION OF LOTS. LILI
 URSACONTACT NUMBER IS (561)822-1239.
  
 6)2ND REQUEST,
 THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C" AS WELL AS LOFT
 BUILDING "B". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) ENERGY CALC FORMS, STILL HAVE THE
 WRONG CLIMATE ZONE LISTED ON THE FRONT.
  
 8) COMPLIED.
  
 9)NOTE:
 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10)NOTE:
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
  
 11) 110.1.2*/106.1.2* INFORMATION
 REQUIRED FOR ISSUING A CERTIFICATE OF
 OCCUPANCY SEE :
 11A) COMPLIED.
 11B) COMPLIED.
 11C) COMPLIED.
 11D) 2ND REQUEST.THE DESIGN OCCUPANT
 LOAD.
 11E) COMPLIED, NOT REQUIRED.
 11F) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT, NOT
 AT THIS TIME.
  
 12) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 12A) B ZONE.
 12B)COMPLIED.
 12C) COMPLIED.
 12D) COMPLIED.
 12E) COMPLIED.
  
 12F) 2ND REQUEST,NUMBER OF BEDROOMS
  
 12G)2ND REQUEST, NUMBER OF ROOMS
  
 12H) 2ND REQUEST, NUMBER OF BATHROOM
  
 12I)2ND REQUEST,SQ FT LIVING SPACE
 (TOTAL)
  
 12J)2ND REQUEST,SQ FT FOOT PRINT, THIS
 IS A/C AREA AND NON A/C AREA!!!!!
 PROVIDE CALCULATIONS APPROX 19,550 FIRST
 FLOOR. TYPE IIIB ONLY ALLOWS 16.000 SQ
 FT.
  
 12K)2ND REQUEST. SQ FT UNDER ROOFA/C AND
 NON A/C AREA!! (TOTAL)
  
 13) NOTE FOR INFORMATION ONLY. SHEET
 LT-2 A 7.3.1 WINDOWS INDICATES
 THAT THE WINDOWS WILL BE LARGE MISSLE
 IMPACT RESISTANT WINDOWS, JUST A NOTE ON
 THE W. P. B. BUILDING OFFICIALS
 INTERPRETATION ON WINDOWS ON LARGE
 PROJECTS WHERE OWNERS(CONDOS) MAY NOT BE
 PRESENT. TAKEN FROM INFORMATIONAL PACKET
 ***********************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 14)EXEMPT FROM FAIR HOUSING.
  
 15) SHEET LT-2 A.1.1A/ LT-2 A.1.1B:
 15A) COMPLIED.
 15B) COMPLIED.
 15C) COMPLIED.
 15D) COMPLIED.
 15E) COMPLIED.
 15F) COMPLIED.
 15G)NOTE TO BE ADDED TO GARAGE REVIEW.
 NOTE: THAT THE TWO DOORS MENTIONED
 ABOVE THAT WILL APPEAR ON THE PARKING
 GARAGE PLAN DO NOT MEET:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS.THE 18" ON THE LATCH SIDE.
 MINIMUM MANEUVERING CLEARENCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITH IN THE REQUIRED
 CLEARENCES SHALL BE CLEAR & LEVEL.
 15H) NOTE TO BE ADDED TO GARAGE
 REVIEW.THE OTHER ISSUE WITH THIS SAME
 OPENING WILL BE (PARKING GARAGE) TO
 PROVIDE VERTICAL ACCESSIBILITY THROUGH
 THE TWO OPENINGS.11-4.1.2 VERTICAL
 ACCESSIBILITY, NOTHING IN THIS CODE
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, SSTRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE OR
 BELOW THE OCCUPIAABLE GRADE LEVEL.
  
 16) COMPLIED.
  
 17) SHEET LT-2 A2.3.1/ A2.3.1, SECTIONS
 A & B::
 17A) COMPLIED.
  
 17B)2ND REQUEST,DISCREPANCY BETWEEN THE
 A2.3.1A/ A2.3.1B & S-3.1/ S3.2. THE ARCH
 PAGES INDICATE THE WALLS OF THE LOWER
 ROOF LEVEL EXTEND A MINIMUM OF 30" ABOVE
 THE ROOF SURFACES ON BOTH SIDES OF THE
 FIRE WALL, WHEREAS THE STRUCTURAL
 SHEETS-5 DETAIL# 11 IS MISSING THE
 PARAPET. IF THIS IS THE CASE SEE FIGURE
 705.6.1.3 CODE COMMENTARY THAT WILL
 REQUIRE A 1-HOUR RATED ROOF CONSTRUCTION
 INCLUDING ROOF STRUCTURE AND SUPPORTING
 ELEMENTS. A3.2.2 PLANS INDICATES ROOF
 DRAIN WITHIN THE FIRST 10'-0" OF THE
 FIREWALL.705.5.6.1BOTH EXCEPTIONS MUST
 BE MET.
 705.5.6.EXCEPTIONS
 EXCEPTION: WHERE THE FIRE WALL
 TERMINATES AT THE UNDERSIDE OF THE ROOF
 SHEATHING, DECK OR SLAB OF THE LOWER
 ROOF, PROVIDED:
 1.THE LOWER ROOF ASSEMBLY WITHIN 10
 FEET (3048 MM) OF THE WALL HAS NOT LESS
 THAN A 1-HOUR FIRE-RESISTANCE RATING AND
 THE ENTIRE LENGTH AND SPAN OF SUPPORTING
 ELEMENTS FOR THE RATED ROOF ASSEMBLY HAS
 A FIRE-RESISTANCE RATING OF NOT LESS
 THAN 1 HOUR.
 2.OPENINGS IN THE LOWER ROOF SHALL
 NOT BE LOCATED WITHIN 10 FEET (3048 MM)
 OF THE FIRE WALL.
  
 17C) 2ND REQUEST,
 IF THE DESIGNER OF ECORD DECIDES TO
 GO WITH THE OPTION TO HAVE THE 1-HOUR
 FIRE RESISTANCE FOR A MINIMUM OF 10'
 FROM THE FIRE WALL, THEN THERE MAY BE NO
 OPENINGS WITHIN THIS AREA, THUS HAVING
 TO MOVE THE AIR HANDLERS. SEE 705.6.1
 OPTIONS CODE COMMENTARYFIGURE705.61(3)
 .
 17D)2ND REQUEST.
 AIR COMPRESSORS ON ROOF:ARE TO
 MEET THE MINIMUM HEIGHT REQUIREMENTS OF
 TABLE 1509.7.
  
 17E)ATTIC INSULATION: 1203.2.ATTIC
 SPACE. TRUE THIS SPACE IS NOT ATTIC
 SPACE. 1203.1 SEE CODE COMMENTARY ABOUT
 THIS TYPE OF USAGE OR SPACE.EVERY ROOM
 OR SPACE MUST BE PROVIDED WITH
 VENTILATION. THE SELECTION OF NATURAL
 VENTILATION ON A ROOM BY ROOM OR SPACE
 BY SPACE IS THE DESIGNER'S PREROGATIVE.
 INDICATE HOW VENTILATION WILL BE
 ACCOLPLISHED, BY TRANSFER
 GRILLES, ETC?
  
 17F) COMPLIED.
  
  
  
  
  
  
  
 18) SHEET A4.1.1-A4.1.3: LOFTS,A,B & C:
 18A-D)COMPLIED, TRUELY A SECOND STORY.
  
 19) SECOND STORY SLEEPING ROOMS:
 1025.1 GENERAL.
  
 IN ADDITION TO THE MEANS OF EGRESS
 REQUIRED BY THIS CHAPTER, PROVISIONS
 SHALL BE MADE FOR EMERGENCY ESCAPE AND
 RESCUE IN GROUP R AS APPLICABLE IN
 SECTION 101.2 AND GROUP I-1 OCCUPANCIES.
 BASEMENTS AND SLEEPING ROOMS BELOW THE
 FOURTH STORY ABOVE GRADE PLANE SHALL
 HAVE AT LEAST ONE EXTERIOR EMERGENCY
 ESCAPE AND RESCUE OPENING IN ACCORDANCE
 WITH THIS SECTION. WHERE BASEMENTS
 CONTAIN ONE OR MORE SLEEPING ROOMS,
 EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM
 , BUT SHALL NOT BE REQUIRED IN ADJOINING
 AREAS OF THE BASEMENT. SUCH OPENING
 SHALL OPEN DIRECTLY INTO A PUBLIC
 STREET, PUBLIC ALLEY, YARD OR COURT. THE
 EMERGENCY ESCAPE AND RESCUE OPENING
 SHALL BE PERMITTED TO OPEN INTO A SCREEN
 ENCLOSURE, OPEN TO THE ATMOSPHERE, WHERE
 A SCREEN DOOR IS PROVIDED LEADING AWAY
 FROM THE RESIDENCE. SUCH OPENING SHALL
 BE OPERATIONAL FROM THE INSIDE WITHOUT
 THE USE OF SPECIAL KNOWLEDGE, KEYS OR
 TOOLS.
 EXCEPTIONS:
 1.IN OTHER THAN GROUP R-3
 OCCUPANCIES AS APPLICABLE IN SECTION
 101.2 , BUILDINGS EQUIPPED THROUGHOUT
 WITH AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2 .
 2.IN OTHER THAN GROUP R-3
 OCCUPANCIES AS APPLICABLE IN SECTION
 101.2 , SLEEPING ROOMS PROVIDED WITH A
 DOOR TO A FIRE-RESISTANCE-RATED CORRIDOR
 HAVING ACCESS TO TWO REMOTE EXITS IN
 OPPOSITE DIRECTIONS.
  
 20)2ND REQUEST NO RESPONCE.
 PRODUCT APPROVALS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 21) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXT SOLID DOORS
 B) EXT GLAZED DOORS SWING
 C) WINDOWS A7.3.1 NO WINDOW LEGEND,
 PROVIDE FL COVER SHEET
 D) MULLIONS
 E) EXT RAILINGS
 F) LOUVERS
 G) TRUSS ANCHORS
 H) ROOFING ASSEMBLIES
 1) FLAT
 2) CEMENT TILE & TYPE OF INSTALATION
  
 22)COMPLIED, IF WINDOW NOA HAS FL
 COVERSHEET.
  
 23) COMPLIED IF WINDOW REPORT HAS FL
 COVERSHEET..
  
 24)COMPLIED.
  
 25)2ND REQUEST.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 26) NEW NOTE: )GARAGE- SHEET A1.1 CUT
 SECTION FOR
 THE WEST ELEVATION, SEE SPC8.02 DETAIL
 "H". INDICATES A SINGLE FOOTING FOR BOTH
 BUILDINGS THE LOFTS AND PARKING GARAGE.
 THIS WAS A COMMENT TO THE LOFT BUILDING
 ON THE FIRST ROUND OF COMMENTSTHAT THE
 2 BUILDINGS COULD NOT SHARE THE SAME
 FOUNDATION. NO GARENTEE THAT EITHER OR
 BOTH WILL BE BUILT THE SAME TIME. IF
 THIS HOLDS TRUE STRUCTURAL CRACKING MAY
 OCCUR SINCE THE DESIGN LOADS AND
 SETTLING WILL BE DIFFERENT THAN
 CALCULATED, CAUSING CRACKING AND OR IF
 THE OTHER BUILDING ISN'T BUILT ON THE
 SHARED FOOTER THERE WILL BE A DIFFERENCE
 IN THE WAY THE BUILDING WILL SETTLE.
 SEE LOFT BUILDING S-6 DATED 2-14-06
 FOR FOUNDATION DETAIL SHOULD BE NOTED ON
 BOTH SETS OF PLANS THE GARAGE FOOTER AND
 PRECAST WALL HAVE TO BE IN PLACE BEFO
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026