| 2006-04-17 00:00:00 | |
| | PERMIT: 05080678 |
| | ADD: 719 EXECUTIVE CENTER DR |
| | (LOFT# 2) |
| | CONT: THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | CELL:(954)675-4302 |
| | |
| | ARCHITECT: ACI ARCHITECRTURALGROUP |
| | PAUL M. TWITTY |
| | TEL:(561)832-5599 |
| | STRUC ENGINEER: ONM&J |
| | PHILLIP RIZZO |
| | TEL:(561)835-9994 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | NOTES 1-10 TOTALLY IGNORED, NOT IN |
| | RESPONCE COMMENTS. |
| | |
| | 1)******IMPORTANT NOTE IGNORED******** |
| | EITHER THE CONTRACTOR OR THE DESIGN |
| | PROFESSIONAL HAS TO TAKE RESPONSIBILITY |
| | FOR THIS PROJECT AND COMPLY WITH THIS |
| | REQUEST, AND REMOVE ALL VOIDED SHEETS |
| | FROM THE PERMIT DOCUMENTS. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2)2ND REQUEST, |
| | FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | 105.8* PROVIDE NOC RECORDED WITH THE |
| | CLERK OF COURT BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | |
| | |
| | 3A)2ND REQUEST,109.3.7*THIS PARTICUAL |
| | TYPE OF BUILDING WILL REQUIRE A RESIDENT |
| | INSPECTOR NOT A THRESHOLD INSPECTOR. |
| | FORMS WILL NEED TO BE FILED OUT FOR THE |
| | RESIDENT INSPECTOR, CONTACT HAROLD |
| | PISKURA, INSPECTION SERVICES MANAGER @ |
| | (561)805-6711 TO SEET UP AN APPOINTMENT. |
| | |
| | **********NOTE********** |
| | THIS PERMIT WILL BE ONLY FOR THE LOFT |
| | UNITS. PLANS INDICATE THAT A (6) |
| | STORY ENCLOSED PARKING GARAGE WILL BE |
| | BUILT IN THE FUTURE WHICH MAY OR MAY NOT |
| | HAPPEN.NOTE ALSO UNDER LOFTS A & B |
| | BUILDING1 OF 7 UNITS? IN EACH BUILDING |
| | THERE IS 30 UNITS. |
| | |
| | B)COMPLIED. |
| | |
| | 3B) COMPLIED LOFTS NOT A THRESHOLD BLDG. |
| | |
| | 3C)COMPLIED, NOT A THRESHOLD BLDG. |
| | |
| | 3D) NOTE:IF THIS BUILDING WILL REQUIRE |
| | (3) OF ALL DOCUMENTS FOR REVIEW FOR A |
| | SPECIAL (RESIDENT INSPECTOR). |
| | |
| | 4) NOTE 2ND REQUEST, |
| | 106.3.3* PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| | WRITTING BY THE DESIGNER OF RECORD PRIOR |
| | TO SUBMITTAL FOR " JURISDICTIONAL |
| | APPROVAL", (LOCAL PRODUCT APPROVAL). |
| | |
| | 5) 2ND REQUEST SITE PLAN NEEDS TO BE |
| | SUBMITTED TO ADDRESSING PERSONEL LILI |
| | URSA FOR ADDRESSING AS WELL AS NEW PLAT |
| | MAP FOR THE COMBINATION OF LOTS. LILI |
| | URSACONTACT NUMBER IS (561)822-1239. |
| | |
| | 6)2ND REQUEST, |
| | THE SURVEY DOES SHOW 2 SEPERATE LOTS |
| | WHICH APPEAR TO CUT THROUGH BULDING "B" |
| | AND BUILDING "C" AS WELL AS LOFT |
| | BUILDING "B". A UNITY OF TITLE SHALL |
| | BE REQUIRED, TABLE 601 AND 602. |
| | |
| | 7) ENERGY CALC FORMS, STILL HAVE THE |
| | WRONG CLIMATE ZONE LISTED ON THE FRONT. |
| | |
| | 8) COMPLIED. |
| | |
| | 9)NOTE: |
| | 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS |
| | CODE SHALL BE PERMORMED IN A MANNER SO |
| | AS NOT TO ADVERSLY IMPACT THE CONDITION |
| | OF ADJACENT PROPERTY, UNLESS SUCH |
| | ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE |
| | PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| | LIMITED TO THE CONTROL OF DUST, NOISE, |
| | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| | THE STORAGE OF CONSTRUCTION MATERIALS. |
| | NEW CONSTRUCTION ACTIVITY SHALL NOT |
| | ADVERSELY IMPACT HISTORICSURFACE WATER |
| | DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, & MAY REQUIRE SPECIAL |
| | DRAINAGE DESIGNCOMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED |
| | SITES.ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENET, INCLUDING |
| | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, |
| | DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN |
| | EXCESS OF 800SQ FT OF PERMEABLE LAND |
| | AREA ON ANY PARCELL SHALL AS A PERMIT |
| | CONDITION, PROVIDE A PROFESSIONALY |
| | PREPARED DRAINAGE PLAN CLEARLY |
| | INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 10)NOTE: |
| | 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM |
| | HIGHWINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | |
| | 11) 110.1.2*/106.1.2* INFORMATION |
| | REQUIRED FOR ISSUING A CERTIFICATE OF |
| | OCCUPANCY SEE : |
| | 11A) COMPLIED. |
| | 11B) COMPLIED. |
| | 11C) COMPLIED. |
| | 11D) 2ND REQUEST.THE DESIGN OCCUPANT |
| | LOAD. |
| | 11E) COMPLIED, NOT REQUIRED. |
| | 11F) ANY SPECIAL STIPULATIONS & |
| | CONDITIONS OF THE BUILDING PERMIT, NOT |
| | AT THIS TIME. |
| | |
| | 12) ADDITIONAL INFORMATION REQUIRED FOR |
| | RECORD KEEPING PURPOSES 106.1.2*: |
| | 12A) B ZONE. |
| | 12B)COMPLIED. |
| | 12C) COMPLIED. |
| | 12D) COMPLIED. |
| | 12E) COMPLIED. |
| | |
| | 12F) 2ND REQUEST,NUMBER OF BEDROOMS |
| | |
| | 12G)2ND REQUEST, NUMBER OF ROOMS |
| | |
| | 12H) 2ND REQUEST, NUMBER OF BATHROOM |
| | |
| | 12I)2ND REQUEST,SQ FT LIVING SPACE |
| | (TOTAL) |
| | |
| | 12J)2ND REQUEST,SQ FT FOOT PRINT, THIS |
| | IS A/C AREA AND NON A/C AREA!!!!! |
| | PROVIDE CALCULATIONS APPROX 19,550 FIRST |
| | FLOOR. TYPE IIIB ONLY ALLOWS 16.000 SQ |
| | FT. |
| | |
| | 12K)2ND REQUEST. SQ FT UNDER ROOFA/C AND |
| | NON A/C AREA!! (TOTAL) |
| | |
| | 13) NOTE FOR INFORMATION ONLY. SHEET |
| | LT-2 A 7.3.1 WINDOWS INDICATES |
| | THAT THE WINDOWS WILL BE LARGE MISSLE |
| | IMPACT RESISTANT WINDOWS, JUST A NOTE ON |
| | THE W. P. B. BUILDING OFFICIALS |
| | INTERPRETATION ON WINDOWS ON LARGE |
| | PROJECTS WHERE OWNERS(CONDOS) MAY NOT BE |
| | PRESENT. TAKEN FROM INFORMATIONAL PACKET |
| | *********************** |
| | QUESTION# 13) RECOGNIZING SUCH CONCERNS |
| | AS ABSENTEE OWNERS, OR CASES WHERE |
| | LONGER TIME AND EFFORT IS NECESSARY TO |
| | SECURE SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDINGS, WHAT MEASURES ARE BEING |
| | RECOMMENDED OR IMPLEMENTED TO ENSURE |
| | THAT COMPLETE INSTALLATION OR SECURING |
| | IS DONE SUFFICIENTLY IN ADVANCE OF THE |
| | HURRICANE EVENT? |
| | |
| | IN MATTERS FLORIDA BUILDING CODE, 2004 |
| | EDITION, PROVIDES THE ABILITY FOR THE |
| | BUILDING OFFICIAL TO IMPLEMENT |
| | REQUIREMENTS FOR ENSURING STABILITY, |
| | STRENGTH, AND PROPER OPERATION OF |
| | EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ASSURE THE SECURING OF |
| | SHUTTERS ON LARGE OR MULTI-STORY |
| | BUILDING, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY, PRE-STORM PREPARATION |
| | PLANS MUST BE SUBMITTED BY THE PROPERTY |
| | OWNERS OR MANAGING AGENTS FOR REVIEW BY |
| | THE CONSTRUCTION SERVICES DEPARTMENT. |
| | ANY SUCH PLAN SHALL INCLUDE, AT A |
| | MINIMUM, ON-SITE LOCATION OF SHUTTERS, |
| | PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS (SAID PARTIES MUST BE LOCATED |
| | WITHIN PALM BEACH COUNTY), TOTAL NUMBER |
| | OF OPENINGS TO BE PROTECTED AND TOTAL |
| | TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE |
| | ACCOMPLISHED WITHIN TWELVE (12) HOURS OR |
| | LESS OF THE OFFICIAL NOTIFICATION BY THE |
| | NATIONAL WEATHER SERVICE OF A HURRICANE |
| | WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND |
| | THIS STANDARD) ARE NOT INTENDED TO |
| | PROHIBIT THE USE OF ALTERNATIVE |
| | MATERIALS AND METHODS, AND ALLOW THE |
| | BUILDING OFFICIAL TO REVIEW AND APPROVE |
| | ANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY, STRENGTH, EFFECTIVENESS, FIRE |
| | RESISTANCE, DURABILITY AND SAFETY |
| | PRESCRIBED BY CODE. BASED UPON THIS CODE |
| | PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON |
| | A CASE-BY-CASE BASIS AND SHALL REQUIRE |
| | SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING |
| | THE ALTERNATE. |
| | |
| | QUESTION# 14) ARE REMOVABLE STORM PANELS |
| | APPROPRIATE FOR USE ON VERY LARGE, MID |
| | OR HIGH-RISE STRUCTURES? |
| | |
| | NO, EXCEPT ON THE GROUND FLOOR. ON |
| | COMMERCIAL AND MULTI-UNIT RESIDENTIAL |
| | STRUCTURES, ABOVE THE FIRST LEVEL, |
| | IMPACT RESISTANT GLAZING OR PERMANENTLY |
| | AFFIXED PROTECTIVE DEVICES SHALL BE |
| | INSTALLED. PERMANENTLY AFFIXED |
| | PROTECTIVE DEVICES SHALL REQUIRE THE |
| | WRITTEN APPROVAL OF THE BUILDING |
| | OFFICIAL. |
| | |
| | 14)EXEMPT FROM FAIR HOUSING. |
| | |
| | 15) SHEET LT-2 A.1.1A/ LT-2 A.1.1B: |
| | 15A) COMPLIED. |
| | 15B) COMPLIED. |
| | 15C) COMPLIED. |
| | 15D) COMPLIED. |
| | 15E) COMPLIED. |
| | 15F) COMPLIED. |
| | 15G)NOTE TO BE ADDED TO GARAGE REVIEW. |
| | NOTE: THAT THE TWO DOORS MENTIONED |
| | ABOVE THAT WILL APPEAR ON THE PARKING |
| | GARAGE PLAN DO NOT MEET: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS.THE 18" ON THE LATCH SIDE. |
| | MINIMUM MANEUVERING CLEARENCES AT DOORS |
| | THAT ARE NOT AUTOMATIC OR POWER-ASSISTED |
| | SHALL BE AS SHOWN IN FIG. 25. THE FLOOR |
| | OR GROUND AREA WITH IN THE REQUIRED |
| | CLEARENCES SHALL BE CLEAR & LEVEL. |
| | 15H) NOTE TO BE ADDED TO GARAGE |
| | REVIEW.THE OTHER ISSUE WITH THIS SAME |
| | OPENING WILL BE (PARKING GARAGE) TO |
| | PROVIDE VERTICAL ACCESSIBILITY THROUGH |
| | THE TWO OPENINGS.11-4.1.2 VERTICAL |
| | ACCESSIBILITY, NOTHING IN THIS CODE |
| | SHALL BE CONSTRUED TO RELIEVE THE OWNER |
| | OF ANY BUILDING, SSTRUCTURE OR FACILITY |
| | FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE OR |
| | BELOW THE OCCUPIAABLE GRADE LEVEL. |
| | |
| | 16) COMPLIED. |
| | |
| | 17) SHEET LT-2 A2.3.1/ A2.3.1, SECTIONS |
| | A & B:: |
| | 17A) COMPLIED. |
| | |
| | 17B)2ND REQUEST,DISCREPANCY BETWEEN THE |
| | A2.3.1A/ A2.3.1B & S-3.1/ S3.2. THE ARCH |
| | PAGES INDICATE THE WALLS OF THE LOWER |
| | ROOF LEVEL EXTEND A MINIMUM OF 30" ABOVE |
| | THE ROOF SURFACES ON BOTH SIDES OF THE |
| | FIRE WALL, WHEREAS THE STRUCTURAL |
| | SHEETS-5 DETAIL# 11 IS MISSING THE |
| | PARAPET. IF THIS IS THE CASE SEE FIGURE |
| | 705.6.1.3 CODE COMMENTARY THAT WILL |
| | REQUIRE A 1-HOUR RATED ROOF CONSTRUCTION |
| | INCLUDING ROOF STRUCTURE AND SUPPORTING |
| | ELEMENTS. A3.2.2 PLANS INDICATES ROOF |
| | DRAIN WITHIN THE FIRST 10'-0" OF THE |
| | FIREWALL.705.5.6.1BOTH EXCEPTIONS MUST |
| | BE MET. |
| | 705.5.6.EXCEPTIONS |
| | EXCEPTION: WHERE THE FIRE WALL |
| | TERMINATES AT THE UNDERSIDE OF THE ROOF |
| | SHEATHING, DECK OR SLAB OF THE LOWER |
| | ROOF, PROVIDED: |
| | 1.THE LOWER ROOF ASSEMBLY WITHIN 10 |
| | FEET (3048 MM) OF THE WALL HAS NOT LESS |
| | THAN A 1-HOUR FIRE-RESISTANCE RATING AND |
| | THE ENTIRE LENGTH AND SPAN OF SUPPORTING |
| | ELEMENTS FOR THE RATED ROOF ASSEMBLY HAS |
| | A FIRE-RESISTANCE RATING OF NOT LESS |
| | THAN 1 HOUR. |
| | 2.OPENINGS IN THE LOWER ROOF SHALL |
| | NOT BE LOCATED WITHIN 10 FEET (3048 MM) |
| | OF THE FIRE WALL. |
| | |
| | 17C) 2ND REQUEST, |
| | IF THE DESIGNER OF ECORD DECIDES TO |
| | GO WITH THE OPTION TO HAVE THE 1-HOUR |
| | FIRE RESISTANCE FOR A MINIMUM OF 10' |
| | FROM THE FIRE WALL, THEN THERE MAY BE NO |
| | OPENINGS WITHIN THIS AREA, THUS HAVING |
| | TO MOVE THE AIR HANDLERS. SEE 705.6.1 |
| | OPTIONS CODE COMMENTARYFIGURE705.61(3) |
| | . |
| | 17D)2ND REQUEST. |
| | AIR COMPRESSORS ON ROOF:ARE TO |
| | MEET THE MINIMUM HEIGHT REQUIREMENTS OF |
| | TABLE 1509.7. |
| | |
| | 17E)ATTIC INSULATION: 1203.2.ATTIC |
| | SPACE. TRUE THIS SPACE IS NOT ATTIC |
| | SPACE. 1203.1 SEE CODE COMMENTARY ABOUT |
| | THIS TYPE OF USAGE OR SPACE.EVERY ROOM |
| | OR SPACE MUST BE PROVIDED WITH |
| | VENTILATION. THE SELECTION OF NATURAL |
| | VENTILATION ON A ROOM BY ROOM OR SPACE |
| | BY SPACE IS THE DESIGNER'S PREROGATIVE. |
| | INDICATE HOW VENTILATION WILL BE |
| | ACCOLPLISHED, BY TRANSFER |
| | GRILLES, ETC? |
| | |
| | 17F) COMPLIED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 18) SHEET A4.1.1-A4.1.3: LOFTS,A,B & C: |
| | 18A-D)COMPLIED, TRUELY A SECOND STORY. |
| | |
| | 19) SECOND STORY SLEEPING ROOMS: |
| | 1025.1 GENERAL. |
| | |
| | IN ADDITION TO THE MEANS OF EGRESS |
| | REQUIRED BY THIS CHAPTER, PROVISIONS |
| | SHALL BE MADE FOR EMERGENCY ESCAPE AND |
| | RESCUE IN GROUP R AS APPLICABLE IN |
| | SECTION 101.2 AND GROUP I-1 OCCUPANCIES. |
| | BASEMENTS AND SLEEPING ROOMS BELOW THE |
| | FOURTH STORY ABOVE GRADE PLANE SHALL |
| | HAVE AT LEAST ONE EXTERIOR EMERGENCY |
| | ESCAPE AND RESCUE OPENING IN ACCORDANCE |
| | WITH THIS SECTION. WHERE BASEMENTS |
| | CONTAIN ONE OR MORE SLEEPING ROOMS, |
| | EMERGENCY EGRESS AND RESCUE OPENINGS |
| | SHALL BE REQUIRED IN EACH SLEEPING ROOM |
| | , BUT SHALL NOT BE REQUIRED IN ADJOINING |
| | AREAS OF THE BASEMENT. SUCH OPENING |
| | SHALL OPEN DIRECTLY INTO A PUBLIC |
| | STREET, PUBLIC ALLEY, YARD OR COURT. THE |
| | EMERGENCY ESCAPE AND RESCUE OPENING |
| | SHALL BE PERMITTED TO OPEN INTO A SCREEN |
| | ENCLOSURE, OPEN TO THE ATMOSPHERE, WHERE |
| | A SCREEN DOOR IS PROVIDED LEADING AWAY |
| | FROM THE RESIDENCE. SUCH OPENING SHALL |
| | BE OPERATIONAL FROM THE INSIDE WITHOUT |
| | THE USE OF SPECIAL KNOWLEDGE, KEYS OR |
| | TOOLS. |
| | EXCEPTIONS: |
| | 1.IN OTHER THAN GROUP R-3 |
| | OCCUPANCIES AS APPLICABLE IN SECTION |
| | 101.2 , BUILDINGS EQUIPPED THROUGHOUT |
| | WITH AN APPROVED AUTOMATIC SPRINKLER |
| | SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2 . |
| | 2.IN OTHER THAN GROUP R-3 |
| | OCCUPANCIES AS APPLICABLE IN SECTION |
| | 101.2 , SLEEPING ROOMS PROVIDED WITH A |
| | DOOR TO A FIRE-RESISTANCE-RATED CORRIDOR |
| | HAVING ACCESS TO TWO REMOTE EXITS IN |
| | OPPOSITE DIRECTIONS. |
| | |
| | 20)2ND REQUEST NO RESPONCE. |
| | PRODUCT APPROVALS: |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 21) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) EXT SOLID DOORS |
| | B) EXT GLAZED DOORS SWING |
| | C) WINDOWS A7.3.1 NO WINDOW LEGEND, |
| | PROVIDE FL COVER SHEET |
| | D) MULLIONS |
| | E) EXT RAILINGS |
| | F) LOUVERS |
| | G) TRUSS ANCHORS |
| | H) ROOFING ASSEMBLIES |
| | 1) FLAT |
| | 2) CEMENT TILE & TYPE OF INSTALATION |
| | |
| | 22)COMPLIED, IF WINDOW NOA HAS FL |
| | COVERSHEET. |
| | |
| | 23) COMPLIED IF WINDOW REPORT HAS FL |
| | COVERSHEET.. |
| | |
| | 24)COMPLIED. |
| | |
| | 25)2ND REQUEST. |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 26) NEW NOTE: )GARAGE- SHEET A1.1 CUT |
| | SECTION FOR |
| | THE WEST ELEVATION, SEE SPC8.02 DETAIL |
| | "H". INDICATES A SINGLE FOOTING FOR BOTH |
| | BUILDINGS THE LOFTS AND PARKING GARAGE. |
| | THIS WAS A COMMENT TO THE LOFT BUILDING |
| | ON THE FIRST ROUND OF COMMENTSTHAT THE |
| | 2 BUILDINGS COULD NOT SHARE THE SAME |
| | FOUNDATION. NO GARENTEE THAT EITHER OR |
| | BOTH WILL BE BUILT THE SAME TIME. IF |
| | THIS HOLDS TRUE STRUCTURAL CRACKING MAY |
| | OCCUR SINCE THE DESIGN LOADS AND |
| | SETTLING WILL BE DIFFERENT THAN |
| | CALCULATED, CAUSING CRACKING AND OR IF |
| | THE OTHER BUILDING ISN'T BUILT ON THE |
| | SHARED FOOTER THERE WILL BE A DIFFERENCE |
| | IN THE WAY THE BUILDING WILL SETTLE. |
| | SEE LOFT BUILDING S-6 DATED 2-14-06 |
| | FOR FOUNDATION DETAIL SHOULD BE NOTED ON |
| | BOTH SETS OF PLANS THE GARAGE FOOTER AND |
| | PRECAST WALL HAVE TO BE IN PLACE BEFO |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |