Plan Review Notes
Plan Review Notes For Permit 05080678
Permit Number 05080678
Review Stop P
Sequence Number 1
Notes
Date Text
2005-10-20 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS LA-POOL-3 & LA-POOL-4 SEPARATE
 POOL PLANS & PERMIT ARE REQUIRED FOR
 EACH POOL. PLANS SHALL BE ROUTED TO THE
 PALM BEACH COUNTY HEALTH DEPT FOR REVIEW
 AND SHALL BE STAMPED PRIOR TO SUBMITTING
 TO CITY WPB FOR REVIEW. (MIN. 2 SETS OF
 PLANS).
 2. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED, & DATED AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
 3. SHTS LT-2, A2.3.1A, & A2.3.1B. SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS. SHOW SQUARE FOOTAGE DRAINED
 AT EACH ROOF DRAIN, WITH 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS, AND
 ROOF AREA FROM ABOVE SHOWN IN
 CALCULATIONS. SECTION 1106 & 1107 AND
 ALL SUBSECTIONS.
 4. SHEETS FOR ALL UNITS TYPES, IF THERE
 IS AN ELEVATOR IN THE BUILDING,
 (INCLUDING THE PARKING GARAGE), THEN ALL
 UNITS SHALL COMPLY WITH FHA-98
 REQUIREMENTS 1 THRU 7. SUBMIT DETAILS
 FOR BACKING FOR THE WATER CLOSET IN
 POWDER ROOM. SHOW CLEAR FLOOR SPACE FOR
 ALL USABLE FIXTURES. W/C REQUIRES A MIN.
 48" CLEAR FLOOR SPACE. LAV IN POWDER
 SHALL BE A MAX. 34" TO FLOOD RIM LEVEL,
 INDICATE ON PLANS. SEE PAGES 7.33, 7.43.
 LAV SHALL EITHER BE CENTERED ON THE 48"
 LENGTH OF A PARALLEL CLEAR FLOOR SPACE,
 OR A REMOVABLE BASE CABINET WITH 30"
 CLEAR WIDTH FOR FRON APPROACH. SUBMIT
 DETAILS.
 5. SHT P0.1 REFERENCES FBC-2001 CODE.
 PER SHT LT-2 CODE SUMMARY BUILDING HAS
 BEEN DESIGNED ACCORDING TO FBC-2004.
 PLEASE CORRELATE PLUMBING SHEETS WITH
 CODE SUMMARY SHEET.
 6. SHTS P2.3.1 & P2.3.2 SEE COMMENT #3,
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS REQUIRED. SECTIONS 1106 AND
 1107.
 7. SHT P5.1 SANITARY RISER ISO.
 CLEANOUTS FOR THE W/M SHALL BE INSTALLED
 4' ABOVE THE FLOOR, AND A STANDPIPE IS
 REQUIRED FOR THE W/M. SECTIONS 708.9 AND
 1002.1.
 8. SHT P5.1 WATER RISER ISO. WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. (SEE SHT P0.1
 PLUMBING NOTE 13 AND W/M CONNECTION
 DETAIL). PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 9. SHT P5.1 THE FOLLOWING INFORMATION IS
 REQUIREMENTS FOR GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6 AND TABLES 402(1) THRU
 402(33).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1.
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]