2005-10-06 00:00:00DENIED:2004 FLORIDA BUILDING CODE
 LOFT BUILDING #2
 1.PLEASE PROVIDE SUBMITTALS FOR ALL
 A/C EQUIPMENT, EXHAUST FANS, GAS DRYER,
 GAS RANGE, ETC.
  
 2.ENERGY CALCULATIONS SUBMITTED
 INDICATE 'SINGLE FAMILY' & PLAN SHEET
 LT-2 A0.0.2 THE OCCUPANCY SHOWS R-2,
 MULTI-FAMILY.PLEASE CLARIFY.
  
 3.PLAN SHEET M2.1.1 INDICATES LAUNDRY
 ROOM ON THE 1ST FLOOR.PLEASE PROVIDE
 TOTAL LENGTH OF THE DRYER EXHAUST TO THE
 TERMINATION.
  
 4.PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE DRYER CLOSET.PLEASE SHOW
 CCMPLIANCE WITH CHAPTER 7 OF THE 2004
 FLORIDA MECHANICAL CODE(FMC).
  
 5.PROVIDE INFORMATION FOR THE
 VENTILATION OF THE COMMON CORRIDORS.
  
 6.PLAN SHEET M2.1.2 INDICATES THE
 GARAGE, GENERATOR, WATER AND FIRE PUMP
 AREAS WILL BE SUBMITTED UNDER SEPARATE
 PERMIT AND NOT A PART OF THE SCOPE OF
 WORK UNDER THIS PERMIT.A COMPLETE
 REVIEW FOR THIS BUILDING CAN NOT BE
 ACCOMPLISHED WITHOUT THE PLANS.
  
 7.PLAN SHEET M7.1 HVAC DETAIL
 INDICATES AUXILIARY DRAIN PER PLUMBING
 PLANS & ALSO SHOWS A 'FLOAT SWITCH'.
 PLEASE CLARIFY WHICH METHOD IS TO BE
 USED.PLEASE NOTE, AUXILIARY DRAIN LINE
 TO TERMINATE AT A CONSPICUOUS POINT.
  
 8.PROVIDE OUTSIDE AIR CALCULATIONS IN
 ACCORDANCE WITH 2004 FMC CHAPTER 4.
  
 9.AHU LOCATED IN THE ATTIC SHALL
 COMPLY WITH 2004 FMC 306.3.
  