| 2005-10-06 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| | LOFT BUILDING #2 |
| | 1.PLEASE PROVIDE SUBMITTALS FOR ALL |
| | A/C EQUIPMENT, EXHAUST FANS, GAS DRYER, |
| | GAS RANGE, ETC. |
| | |
| | 2.ENERGY CALCULATIONS SUBMITTED |
| | INDICATE 'SINGLE FAMILY' & PLAN SHEET |
| | LT-2 A0.0.2 THE OCCUPANCY SHOWS R-2, |
| | MULTI-FAMILY.PLEASE CLARIFY. |
| | |
| | 3.PLAN SHEET M2.1.1 INDICATES LAUNDRY |
| | ROOM ON THE 1ST FLOOR.PLEASE PROVIDE |
| | TOTAL LENGTH OF THE DRYER EXHAUST TO THE |
| | TERMINATION. |
| | |
| | 4.PROVIDE COMBUSTION AIR CALCULATIONS |
| | FOR THE DRYER CLOSET.PLEASE SHOW |
| | CCMPLIANCE WITH CHAPTER 7 OF THE 2004 |
| | FLORIDA MECHANICAL CODE(FMC). |
| | |
| | 5.PROVIDE INFORMATION FOR THE |
| | VENTILATION OF THE COMMON CORRIDORS. |
| | |
| | 6.PLAN SHEET M2.1.2 INDICATES THE |
| | GARAGE, GENERATOR, WATER AND FIRE PUMP |
| | AREAS WILL BE SUBMITTED UNDER SEPARATE |
| | PERMIT AND NOT A PART OF THE SCOPE OF |
| | WORK UNDER THIS PERMIT.A COMPLETE |
| | REVIEW FOR THIS BUILDING CAN NOT BE |
| | ACCOMPLISHED WITHOUT THE PLANS. |
| | |
| | 7.PLAN SHEET M7.1 HVAC DETAIL |
| | INDICATES AUXILIARY DRAIN PER PLUMBING |
| | PLANS & ALSO SHOWS A 'FLOAT SWITCH'. |
| | PLEASE CLARIFY WHICH METHOD IS TO BE |
| | USED.PLEASE NOTE, AUXILIARY DRAIN LINE |
| | TO TERMINATE AT A CONSPICUOUS POINT. |
| | |
| | 8.PROVIDE OUTSIDE AIR CALCULATIONS IN |
| | ACCORDANCE WITH 2004 FMC CHAPTER 4. |
| | |
| | 9.AHU LOCATED IN THE ATTIC SHALL |
| | COMPLY WITH 2004 FMC 306.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |