Plan Review Notes
Plan Review Notes For Permit 05080678
Permit Number 05080678
Review Stop G
Sequence Number 1
Notes
Date Text
2006-05-13 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING PLAN REVIEW:
  
  
 9. SHT P5.1 THE FOLLOWING INFORMATION IS
 REQUIREMENTS FOR GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT CORRESPONDING
 LENGTHS ARE NOT INDICATED.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ***RESPONSE NOTED, BUT DELIVERY PRESSURE
 NOT SHOWN AS INDICATED.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SECTION 402.2.
 ***RESPONSE NOTED, BUT MANUF. SHEETS
 HAVE NOT BEEN SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO RESPONSE, AND VOIDED SHEETS SHALL
 BE REMOVED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved