| 2005-10-13 00:00:00 | ******DENIED****** |
| | |
| | LOFT BUILDING #2 |
| | |
| | 1) PLEASE NOTE THAT A COMPLETE FIRE |
| | REVIEW CANNOT BE COMPLETED AT THIS TIME |
| | WITH LIMITED SCOPE OF WORK UNDER THIS |
| | PERMIT APPLICATION. IT WOULD APPEAR THAT |
| | SEPARATE PERMITS ARE PROPOSED FOR THE |
| | PARKING GARAGE, FIRE PUMP ETC. |
| | |
| | 2) THIS NOTE DOESN'T APPLY TO THE LOFT |
| | UNITS, BUT FOR REFERENCE A HIGHRISE IS |
| | DEFINED AS A BUILDING GREATER THAN 75' |
| | IN HEIGHT. SHT A-1.1.2. |
| | |
| | 3) PLEASE ILLUSTRATE PRESCRIPTIVE |
| | STRENGTH REQUIREMENTS FOR HANDRAILS AND |
| | GUARDS. |
| | |
| | 4) PLEASE CLARIFY THE DOOR SWINGS FROM |
| | THE CORRIDOR TO PROPOSED GARAGE. PLEASE |
| | NOTE THAT DURING IT'S SWING, ANY DOOR IN |
| | A REQUIRED MEANS OF EGRESS SHALL LEAVE |
| | NOT LESS THAN 1/2 THE WIDTH OF AN AISLE, |
| | CORRIDOR, PASSAGEWAY, OR LANDING |
| | UNOBSTRUCTED. |
| | |
| | 5) IN ADDITION TO THE HEIGHT REQUIREMENT |
| | THE ADDRESS NUMBERS SHALL CONTRAST TO |
| | THE BACKGROUND. SHT A.1.1.2. |
| | |
| | 6) CORRIDORS THAT SERVE AS REQUIRED |
| | MEANS OF EGRESS, MUST BE APPROPRIATELY |
| | ILLUMINATED IN ACCORDANCE WITH NFPA 101. |
| | |
| | 7) ILLUMINATED EXIT SIGNS SHALL BE |
| | VISIBLE FROM ALL POINTS OF EXIT ACCESS, |
| | AND MOUNTED AT DISTANCES NOT TO EXCEED |
| | 100'. |
| | |
| | 8) ABC MULTI-PURPOSE RATED FIRE |
| | EXTINGUISHERS ARE REQUIRED. |
| | |
| | 9) PLEASE NOTE THAT SMOKE DETECTORS |
| | APPEAR TO BE MISSING FROM THE BEDROOM |
| | AREAS AND ALL REQUIRED LEVELS OF THE |
| | DWELLING UNIT. |
| | |
| | 10) FIRE HYDRANTS SHALL BE WET PRIOR TO, |
| | DURING AND AFTER CONSTRUCTION. |
| | |
| | 11) EMERGENCY VEHICLEACCESS LANES |
| | SHALL BE MAINTAINED AT A WIDTH OF AT |
| | LEAST 20'. |
| | |
| | 12) PLEASE NOTE THAT ANY COMMENTS FROM |
| | PARKING GARAGE REVIEW MAY IMPACT ASPECTS |
| | OF THIS FIRE REVIEW. |
| | |
| | 13) LOFT UNITS WILL BE PART OF 6 STORY |
| | PARKING GARAGE. NO MENTION OF FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEM. PLEASE |
| | ADVISE. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |