| 2005-09-13 00:00:00 | ********** UNSAT ************ |
| | |
| | SAIL CLUB |
| | LOFT BUILDING #2 |
| | |
| | 1)NOTE: PLEASE SEE POSSIBLE COMMENTS |
| | FROM OTHER TRADES FOR CORRIDORS SHOWN ON |
| | PLANS WHICH DO NOT INDICATE ANY MEANS OF |
| | EGRESS LIGHTING. |
| | NFPA-101 7.8.9 |
| | |
| | 2)NOTE: PLEASE COMPLETE CIRCUITING ON |
| | PLANS FOR ALL UNITS AND CORRELATE WITH |
| | PANEL SCHEDULES. |
| | PLEASE SEE IF EVERY UNIT IS IDENTICAL, A |
| | TYPICAL UNIT LAYOUT MAY BE USED. |
| | (SOME ARE NOT THE SAME). |
| | |
| | 3)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003 |
| | THE STATE ADOPTED THE 2002 NEC. |
| | |
| | 4)NOTE: PLEASE SEE 210.52F, 210.11C2, |
| | 220.16WHICH REQUIRES THE MIN OF 1500 |
| | VA FOR THE LAUNDRY/WASHER CIRCUIT. |
| | (1.2 SHOWN). |
| | |
| | 5)NOTE: PLEASE SEE PANEL INDICATES "A" |
| | AND "C" PHASES? PLEASE CLARIFY AS |
| | SERVICE IS SHOWN AS SINGLE PHASE. A&B) |
| | |
| | 6)NOTE: PLEASE ALSO SEE REDLINED PLANS |
| | FOR ADDITIONAL MISSING KITCHEN |
| | COUNTERSPACE RECEPTS MISSING PER |
| | 210.52C3 AND 4. PLEASE SEE AREAS WITH |
| | SEPARATE SPACES. PLEASE SEE PLANS |
| | INDICATE A SW RECEPT WHICH WOULD BE |
| | UNDER THE SINK FOR DISHWASHER/DISPOSAL |
| | (CIR 11/13) THIS COUNTERSPACE WOULD BE |
| | REQUIRED TO HAVE A GFI RECEPT. |
| | |
| | 7)NOTE: PLEASE SEE REDLINED PLANS FOR |
| | SOME MISSING RECEPTS PER 210.52 |
| | PLEASE SEE WALL SPACE OFF KITCHENS. |
| | |
| | 8)NOTE: PLEASE CLARIFY AND ADJUST OCP |
| | SHOWN FOR RANGE. PANEL SCHEDULE |
| | INDICATES A 70A 2P BRKR FOR WHAT WOULD |
| | BE A 50A RECEPT FOR RANGE. |
| | PLEASE SEE 406.2B, 210.21B3,4 |
| | |
| | 9)NOTE: PLEASE SEE MISSING SMOKE |
| | DETECTORS REQUIRED INSIDE AND OUTSIDE |
| | ALL BEDRMS AND ON EACH FLOOR OF DWELLING |
| | UNITS. PLEASE SEE MISSING SD AT 2ND |
| | LEVEL. SD WOULD BE REQUIRED AT FIRST |
| | LEVEL. PLEASE BE SURE TO SEE LOCATION |
| | REQUIRMENTS UNDER2002 NFPA-72 11.8.3.5 |
| | FOR PLACEMENT. 11.5.1.1 |
| | |
| | 10)NOTE:PLEASE SEE MAINS FOR BLDG ARE |
| | BEING SHOWN IN MULTIPLE LOCATIONS. |
| | PLEASE SEE THE MAINS SHALL BE REQUIRED |
| | TO BE GROUPED.230.72 |
| | |
| | 11)NOTE: PLANS INDICATE A ROOM FOR FIRE |
| | PUMP FOT TOWER GENERATOR ROOM FOR TOWER. |
| | PLEASE BE AWARE THIS MAY BE AN ISSUE FOR |
| | TOWER REQUIREMENTS. |
| | THIS IS ONLY A NOTE UNDER THIS PERMIT. |
| | |
| | 12)NOTE: PLEASE SEE MISSING EGRESS LT |
| | CONTROL FOR UNITS WITH GRADE LEVEL |
| | ACCESS. |
| | OR PLEASE SEE EXCEPTIONS PERMITTED OR |
| | ACCEPTABLE TO THE AHJ. |
| | LS 101 7.8 |
| | |
| | 13)NOTE: PLEASE SEE SOME UNITS APPEAR TO |
| | HAVE A "SHIFT" IN THE LAYOUT WHICH |
| | PLACES THE PANELS IN A DOORWAY IN SOME |
| | UNITS. |
| | |
| | 14)NOTE: PLEASE SEE PLANS SEEM TO |
| | INDICATE CIRCUITING FOR INDIVIDUAL |
| | WASHER AND DRYER UNITS, HOWEVER PLANS |
| | ALSO SEEM TO INDICATE A STACK UNIT. |
| | PLEASE VERIFY THIS AS ONE PIECE OF |
| | EQUIPMENT BEING PLUGGED INTO TWO |
| | SEPARATE RECEPTS CONTROLLED BY MORE THAN |
| | ONE BRKR?? |
| | PLEASE VERIFY. |
| | |
| | 15)NOTE: PLEASE SEE SCALE KEY PLAN, |
| | WHICH INDICATES 1" = 600'???? |
| | THIS WOULD MAKE THIS BLDG OVER 3600 FT |
| | LONG. MISPRINT) |
| | |
| | 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | IT IS NOTED THE AIC RATINGS ARE SHOWN |
| | FOR SUB-PANELS. |
| | |
| | |
| | |
| | PLEASE SEE DUE TO THE COMMENTS IN NOTE |
| | #1 AND THE CHANGES IN ELECTRICAL |
| | SERVICE. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | **************************************** |
| | PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED |
| | |
| | SHEET FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD |
| | BE ATTACHED TO EACH OTHER TO COMPOSE OF |
| | ONE SET OF VOIDED SHEETS ONLY AND WILL |
| | BE SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE. |
| | ************************************** |
| | |
| | PLEASE SEE BLDG REVIEW COMMENTS WITH |
| | RESPECT TO PRODUCT NOA'S ATTACHED TO |
| | PLANS. |
| | PLEASE ALSO SEE COMMENTS WITH REPECT TO |
| | PRODUCT APPROVALS. |
| | THIS COMMENT DOES NOT APPLY TO KAMM |
| | CONSULTING ENG. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2005-09-11 00:00:00 | IN ELECTRIC FOR REVIEW. |
| | REVIEWS IN PROGRESS . |