2005-09-13 00:00:00********** UNSAT ************
  
 SAIL CLUB
 LOFT BUILDING #2
  
 1)NOTE: PLEASE SEE POSSIBLE COMMENTS
 FROM OTHER TRADES FOR CORRIDORS SHOWN ON
 PLANS WHICH DO NOT INDICATE ANY MEANS OF
 EGRESS LIGHTING.
 NFPA-101 7.8.9
  
 2)NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS FOR ALL UNITS AND CORRELATE WITH
 PANEL SCHEDULES.
 PLEASE SEE IF EVERY UNIT IS IDENTICAL, A
 TYPICAL UNIT LAYOUT MAY BE USED.
 (SOME ARE NOT THE SAME).
  
 3)NOTE: PLEASE SEE PLANS REFERENCE THE
 1999 NEC. PLEASE SEE AS OF JULY 7TH,2003
 THE STATE ADOPTED THE 2002 NEC.
  
 4)NOTE: PLEASE SEE 210.52F, 210.11C2,
 220.16WHICH REQUIRES THE MIN OF 1500
 VA FOR THE LAUNDRY/WASHER CIRCUIT.
 (1.2 SHOWN).
  
 5)NOTE: PLEASE SEE PANEL INDICATES "A"
 AND "C" PHASES? PLEASE CLARIFY AS
 SERVICE IS SHOWN AS SINGLE PHASE. A&B)
  
 6)NOTE: PLEASE ALSO SEE REDLINED PLANS
 FOR ADDITIONAL MISSING KITCHEN
 COUNTERSPACE RECEPTS MISSING PER
 210.52C3 AND 4. PLEASE SEE AREAS WITH
 SEPARATE SPACES. PLEASE SEE PLANS
 INDICATE A SW RECEPT WHICH WOULD BE
 UNDER THE SINK FOR DISHWASHER/DISPOSAL
 (CIR 11/13) THIS COUNTERSPACE WOULD BE
 REQUIRED TO HAVE A GFI RECEPT.
  
 7)NOTE: PLEASE SEE REDLINED PLANS FOR
 SOME MISSING RECEPTS PER 210.52
 PLEASE SEE WALL SPACE OFF KITCHENS.
  
 8)NOTE: PLEASE CLARIFY AND ADJUST OCP
 SHOWN FOR RANGE. PANEL SCHEDULE
 INDICATES A 70A 2P BRKR FOR WHAT WOULD
 BE A 50A RECEPT FOR RANGE.
 PLEASE SEE 406.2B, 210.21B3,4
  
 9)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS REQUIRED INSIDE AND OUTSIDE
 ALL BEDRMS AND ON EACH FLOOR OF DWELLING
 UNITS. PLEASE SEE MISSING SD AT 2ND
 LEVEL. SD WOULD BE REQUIRED AT FIRST
 LEVEL. PLEASE BE SURE TO SEE LOCATION
 REQUIRMENTS UNDER2002 NFPA-72 11.8.3.5
 FOR PLACEMENT. 11.5.1.1
  
 10)NOTE:PLEASE SEE MAINS FOR BLDG ARE
 BEING SHOWN IN MULTIPLE LOCATIONS.
 PLEASE SEE THE MAINS SHALL BE REQUIRED
 TO BE GROUPED.230.72
  
 11)NOTE: PLANS INDICATE A ROOM FOR FIRE
 PUMP FOT TOWER GENERATOR ROOM FOR TOWER.
 PLEASE BE AWARE THIS MAY BE AN ISSUE FOR
 TOWER REQUIREMENTS.
 THIS IS ONLY A NOTE UNDER THIS PERMIT.
  
 12)NOTE: PLEASE SEE MISSING EGRESS LT
 CONTROL FOR UNITS WITH GRADE LEVEL
 ACCESS.
 OR PLEASE SEE EXCEPTIONS PERMITTED OR
 ACCEPTABLE TO THE AHJ.
 LS 101 7.8
  
 13)NOTE: PLEASE SEE SOME UNITS APPEAR TO
 HAVE A "SHIFT" IN THE LAYOUT WHICH
 PLACES THE PANELS IN A DOORWAY IN SOME
 UNITS.
  
 14)NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE CIRCUITING FOR INDIVIDUAL
 WASHER AND DRYER UNITS, HOWEVER PLANS
 ALSO SEEM TO INDICATE A STACK UNIT.
 PLEASE VERIFY THIS AS ONE PIECE OF
 EQUIPMENT BEING PLUGGED INTO TWO
 SEPARATE RECEPTS CONTROLLED BY MORE THAN
 ONE BRKR??
 PLEASE VERIFY.
  
 15)NOTE: PLEASE SEE SCALE KEY PLAN,
 WHICH INDICATES 1" = 600'????
 THIS WOULD MAKE THIS BLDG OVER 3600 FT
 LONG. MISPRINT)
  
 16)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 IT IS NOTED THE AIC RATINGS ARE SHOWN
 FOR SUB-PANELS.
  
  
  
 PLEASE SEE DUE TO THE COMMENTS IN NOTE
 #1 AND THE CHANGES IN ELECTRICAL
 SERVICE.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
  
 SHEET FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
 PLEASE SEE BLDG REVIEW COMMENTS WITH
 RESPECT TO PRODUCT NOA'S ATTACHED TO
 PLANS.
 PLEASE ALSO SEE COMMENTS WITH REPECT TO
 PRODUCT APPROVALS.
 THIS COMMENT DOES NOT APPLY TO KAMM
 CONSULTING ENG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
2005-09-11 00:00:00IN ELECTRIC FOR REVIEW.
 REVIEWS IN PROGRESS .