Plan Review Notes
Plan Review Notes For Permit 05080678
Permit Number 05080678
Review Stop B
Sequence Number 1
Notes
Date Text
2005-11-22 00:00:00 
 PERMIT: 05080678
 ADD: 719 EXECUTIVE CENTER DR
 (LOFT# 2)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) 105.8* PROVIDE NOC RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
  
  
 3A)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING WILL REQUIRE A RESIDENT
 INSPECTOR NOT A THRESHOLD
 INSPECTOR.FORMS WILL NEED TO BE FILED
 OUT FOR THE RESIDENT INSPECTOR, CONTACT
 HAROLD PISKURA, INSPECTION SERVICES
 MANAGER @ (561)805-6711 TO SEET UP AN
 APPOINTMENT.
  
 **********NOTE**********
 THIS PERMIT WILL BE ONLY FOR THE LOFT
 UNITS. PLANS INDICATE THAT A (6)
 STORY ENCLOSED PARKING GARAGE WILL BE
 BUILT IN THE FUTURE WHICH MAY OR MAY NOT
 HAPPEN. THE PLANS DO NOT INDICATE AS TO
 WHICH BUILDING TYPE THE LOFTS ARE TO BE
 DESIGNED TOO, SEE TABLE 503 FOR
 ALLOWABLE HEIGHT AND AREA OF BUILDINGS.
 THE DESIGNER HAS TWO OPTIONS TO
 DESIGN TOO:
 A) DESIGNING THE LOFTS AS A2 STORY
 AND THEN USING THE 2004 EXISTING
 BUILDING CODE CHAPTER 9 FOR ADDITIONS
 HAVING TO MEET 901.2AN ADDITION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY
 IN THE EXISTING BUILDING TO WHICH AN
 ADDITION IS BEING MADE. HAVING TO
 REDESIGN TO A HIGHER STANDARD.
 B) DESIGN THE LOFTS TO THE CRITERIA
 TABLE 503 FOR THE ALLOWABLE HEIGHT &
 AREA FOR R2 CONSTRUCTION AND CONSTRUCT
 A 4HR FIRE WALL BETWEEN THE 2 BUILDINGS.
 THE DESIGNER WILL THEN NEED TO DESIGN
 THE FOUNDATION FOR "EACH" BUILDING SINCE
 THEY WILL BE A STAND ALONE BUILDING,
 CURRENTLY THEY SHARE A COMMON FOUNDATION
 ALONG THE COMMON WALL
 INDICATED ON THE PLAN. UNDER 2004 FL
 BLDG CODE EXISTING BUILDINGS 901.2 WHERE
 ADDITIONS CAN NOT CREATE NONCONFORMITIES
 THE STRUCTURAL STRENGH, IS BEING
 COMPRAMISED WITH AN OVERSIZED FOOTING IF
 THE 2ND BUILDING ISN'T BUILT DURING THE
 SAME TIME PERIOD, THE LOFTS WILL ONLY
 PARTIALLY SETTLE THEN WHEN THE WEIGHT OF
 THE GARAGE IS ADDED LATER THERE WILL
 HAVE ADDITIOAL SETTLEMENT. WITH NO TIME
 TABLE AS TO WHEN THE GARAGE WILL BE
 BUILT THIS IS ONLY ONE OF MANY CONCERNS,
 OTHER COMMENTS WILL OCCUR LATER IN THIS
 REVIEW ABOUT THIS SITUATION. DEPENDING
 HOW THE DESIGNER ADDRESSES THIS PROBLEM,
 AND IF BOTH STRUCTURES ARE BUILT UNDER
 ONE PERMIT, COMMENTS 3B , 3C & 3DMAY
 OR MAY NOT BE APPLICABLE.
  
 3B) 109.3.6.1* THE ENFORCING AGENCY
 SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A
 STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OR ARCHITECT OF RECORD.
 THE STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED TO THE ENFORCINGAGENCY PRIOR
 TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD
 BUILDING.THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLANS IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3C) 109.3.6.4.4.105.13.4.4 ALL PLANS FOR
 THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTES.
  
 3D) NOTE:IF THIS BUILDING WILL BE A
 THRESHOLD STRUCTURE SUBMIT (3) OF ALL
 DOCUMENTS FOR REVIEW.
  
 4) 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5) SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6) THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C" AS WELL AS LOFT
 BUILDING "B". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
 7) ENERGY CALC FORMS, ARE FOR THE 2001
 CODE REVISE TO THE 2004. THE FORMS ALSO
 INDICATE THEY ARE FOR A SINGLE FAMILY,
 INCORRECT THE UNITS TO BE REVIEWEDARE
 EITHER APARTMENTS OR CONDOS REQUIRING
 THE FORM TO READ MULTIFAMILY.
  
 8) GEOTECHNICAL REPORT THAT WORK WAS
 PREFORMED BY ARDAMAN NEEDS TO BE AN
 ORIGINAL WITH SIGNATURE AND RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 9) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORICSURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11A) THE DESIGNER OF RECORD DOES NOT
 SPECIFY THE MINIMUM BUILDING TYPE THAT
 THE STRUCTURE IS DESIGNED TOO, SEE ALSO
 REQUIREMENTS 110.1.2*/106.1.2*
 INFORMATION REQUIRED FOR ISSUING A
 CERTIFICATE OF OCCUPANCY SEE :
 11B) THE USE AND OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 3.
 11C) TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 6.
 11D) THE DESIGN OCCUPANT LOAD.
 11E) IF AN AUTOMATIC FIRESPRINKLER
 SYSTEM IS PROVIDED, WHETHER THE
 SPRINKLER SYSTEM IS REQUIRED
 11F) ANY SPECIAL STIPULATIONS &
 CONDITIONS OF THE BUILDING PERMIT.
  
 12) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 12A) FLOOD ZONE
 12B) FLOOD ELEVATION (IF A ZONE)
 12C) LOMAR (IF A ZONE)
 12D) NUMBER OF UNITS
 12E) NUMBER OF FLOORS
 12F) NUMBER OF BEDROOMS
 12G) NUMBER OF ROOMS
 12H) NUMBER OF BATHROOM
 12I) SQ FT LIVING SPACE(TOTAL)
 12J) SQ FT FOOT PRINT
 12K) SQ FT UNDER ROOF (TOTAL)
  
 13) SHEET LT-2 A 7.3.1 WINDOWS INDICATES
 THAT THE WINDOWS WILL BE LARGE MISSLE
 IMPACT RESISTANT WINDOWS, JUST A NOTE ON
 THE W. P. B. BUILDING OFFICIALS
 INTERPRETATION ON WINDOWS ON LARGE
 PROJECTS WHERE OWNERS(CONDOS) MAY NOT BE
 PRESENT. TAKEN FROM INFORMATIONAL PACKET
 ***********************
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 14) NOTE,AS PREVIOUSLY STATED DEPENDING
 ON HOW COMMENT# 3 IS ADDRESSED,
 CURRENTLY THE DESIGN OF THE LOFTS IS
 EXEMPT FROM FAIR HOUSING, BUT IF THE
 DESIGNER CONSIDERS THE GARAGE AS AN
 ADDITION AND NOT 2 SEPERATE BUILDINGS
 WHEN THE GARGE IS BUILT WITH AN AS
 INDICATED, ELEVATOR, THE INDIVIDUAL
 DOORSLEADING FROM EACH UNIT WILL
 BECOME THE PRIMARY ENTRACNE AND WILL BE
 REQUIRED TO BE ON AN ACCESSIBLE
 ROUTE.THE FIRST FLOOR OF THE UNIT WOULD
 HAVE TO MEET THE FAIR HOUSING
 REQUIREMENTS AT THAT TIME.
  
 15) SHEET LT-2 A.1.1A/ LT-2 A.1.1B:
 15A) CORRIDOR# 1 & 3 BOTH ARE A DEAD END
 CORRIDOR SEE 1016.3 DEAD ENDS. WILL
 REQUIRE ADDITIONAL EXITS.
 15B) PLANS DO NOT MEET THE REQUIREMENT
 OF EXITS; 1014.1.2 WHERE 2 OR MORE EXITS
 OR EXIT ACCESS DOORS ARE REQUIED, AT
 LEAST 2 OF THE EXIT OR EXIT ACCESS DOORS
 SHALL BE PLACED A DISTANCE APART EQUAL
 TO NOT LESS THAN 1/2 OF THE LENGTH OF
 THE MAX- IMUM OVERALL DIAGONAL DIMENSION
 OF THE BUILDING OR AREA TO BE SERVED.
 15C)1016.5 CORRIDOR CONTINUNITY. FIRE
 RESISTANCE-RATED CORRIDORS SHALL BE
 CONTINIOUS FROM THE POINT OF ENTRY TO AN
 EXIT, AND SHALL NOT BE INTERRUPTED BY
 INTERVENING ROOMS.ONCE THE PARKING
 GARAGE IS IN PLACE YOU WILL BE LEAVING
 ONE BUILDING AND GOING INTO ANOTHER AND
 NOT IN A RATED ENCLOSURE!!!!
 15D) DOOR A/3101 & A/3201 BOTH HAVE THE
 SAME SITUATION, IT APPEARS IN BOTH
 OPENINGS THERE WILL BE TWO DOORS IN
 SERIES, SEE 1008.1.7 . WHEN THERE IS 2
 DOORS IN SERIES A SPACE 48" SHALL BE
 MAINTAINED.EVEN THOUGH PLANS INDICATE
 THE USE OF A MAGNETIC HOLD OPEN, WHEN
 THE ALARM GOES OFF, WHEN A PERSON USING
 A WHEELCHAIR OR ON CRUTHES NEEDS THE
 ACCESSIBILITY THE MOST, IT WILL BE THE
 MOST RESTRICTIVE.
 15E) THE SAME 2 DOORS AS STATED ABOVE,
 DO NOT MEET THE REQUIREMENTS OF
 1005.2. THE PLANS DIMENSION THIS
 PART OF THE CORRIDOR AS 52", THE MINIMUM
 WIDTH WOULD BE 36"+22"=58".
 15F) PLANS DO NOT STATE WHAT TYPE OF
 DOOR HARDWARE WILL BE INSTALLED ON THESE
 DOORS, 1008.1.9.
 15G) NOTE: THAT THE TWO DOORS MENTIONED
 ABOVE THAT WILL APPEAR ON THE PARKING
 GARAGE PLAN DO NOT MEET:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS.THE 18" ON THE LATCH SIDE.
 MINIMUM MANEUVERING CLEARENCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED
 SHALL BE AS SHOWN IN FIG. 25. THE FLOOR
 OR GROUND AREA WITH IN THE REQUIRED
 CLEARENCES SHALL BE CLEAR & LEVEL.
 15H) THE OTHER ISSUE WITH THIS SAME
 OPENING WILL BE (PARKING GARAGE) TO
 PROVIDE VERTICAL ACCESSIBILITY THROUGH
 THE TWO OPENINGS.11-4.1.2 VERTICAL
 ACCESSIBILITY, NOTHING IN THIS CODE
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, SSTRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE OR
 BELOW THE OCCUPIAABLE GRADE LEVEL.
  
 16) SHEET LT-2 A.2.2.1B/ A.2.2.2A'
 STORAGE UNITS # 6 & 7 BOTH HAVE DOORS
 THAT WILL LEAD NOWHERE FOR NOW, NO PLANS
 SUBMITTED FOR FUTURE PARKING GARAGE!!!!!
 16A) ONCE PLANS ARE SUBMITED THE SAME
 SITUATION AS 15D TWO DOORS IN SERIES,
 SEE 1008.1.7.
  
 17) SHEET LT-2 A2.3.1/ A2.3.1, SECTIONS
 A & B::
 17A) PLANS INDICATE IN (3) AREAS ACCESS
 DOORS, SHEET LT-2 A3.2.1 VALIDATES IN
 CROSS SECTION ACCESS DOORS, SHOW
 COMPLIANCE WITH 705.6.1, 1HR RATED WALLS
 FOR GARAGE WITH 3/4 HR OPENING
 PROTECTIVES, ALSO SEE ALTERNATIVES.
 17B) DISCREPANCY BETWEEN THE A2.3.1A/
 A2.3.1B & S-3.1/ S3.2. THE ARCH PAGES
 INDICATE THE WALLS OF THE LOWER ROOF
 LEVEL EXTEND A MINIMUM OF 30" ABOVE THE
 ROOF SURFACES ON BOTH SIDES OF THE FIRE
 WALL, WHEREAS THE STRUCTURAL SHEETS-5
 DETAIL# 11 IS MISSING THE PARAPET.
 IF THIS IS THE CASE SEE FIGURE 705.6.1.3
 CODE COMMENTARY THAT WILL REQUIRE A
 1-HOUR RATED ROOF CONSTRUCTION INCLUDING
 ROOF STRUCTURE AND SUPPORTING ELEMENTS.
 17C) IF THE DESIGNER OF ECORD DECIDES TO
 GO WITH THE OPTION TO HAVE THE 1-HOUR
 FIRE RESISTANCE FOR A MINIMUM OF 10'
 FROM THE FIRE WALL, THEN THERE MAY BE NO
 OPENINGS WITHIN THIS AREA, THUS HAVING
 TO MOVE THE AIR HANDLERS. SEE 705.6.1
 OPTIONS CODE COMMENTARY.
 17D) AIR COMPRESSORS ON ROOF:ARE TO
 MEET THE MINIMUM HEIGHT REQUIREMENTS OF
 TABLE 1509.7.
 17E) ATTIC INSULATION: PLANS INDICATE A
 CLOSED ATTIC NO VENTILATION, SEE 1203.2
 ATTIC VENTILATION AND THE 50 % TO BE IN
 THE UPPER PORTION OF THE ROOF. SEE THE
 ATTACHMENT FROM BCAB FOR REQUIREMENTS
 FOR ENCLOSED ATTICS UNDER ALTERNATE
 MATERIALS & METHODS104.11* (OLD 103.7*.
 17F) ATTIC ACCESS ;PLANS SHALL INDICATE
 WHERE THE ATTIC ACCESS WILL BE 1209.2.
 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30
 INCHES (559 MM BY 762 MM) SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM).
 A 30-INCH (762 MM) MINIMUM CLEAR
 HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
  
 18) SHEET A4.1.1-A4.1.3: LOFTS,A,B & C:
 18A)THE AREA OF THE MEZZANINE TYPE "A"
 IS 62% OF THE TOTAL FLOOR AREA.
 18B) THE AREA OF THE MEZZANINE TYPE "B"
 IS 64% OF THE TOTAL FLOOR AREA.
 18C) THE AREA OF THE MEZZANINE TYPE "C"
 IS 59% OF THE TOTAL FLOOR AREA.
 18D) THE AREA OF THE MEZZANINE TYPE"D"
 IS 55% OF THE TOTAL FLOOR AREA.
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
  
 19) MEZZANINE LEVEL BEDROOMS:
 1025.1 GENERAL.
 IN ADDITION TO THE MEANS OF EGRESS
 REQUIRED BY THIS CHAPTER, PROVISIONS
 SHALL BE MADE FOR EMERGENCY ESCAPE AND
 RESCUE IN GROUP R AS APPLICABLE IN
 SECTION 101.2 AND GROUP I-1 OCCUPANCIES.
 BASEMENTS AND SLEEPING ROOMS BELOW THE
 FOURTH STORY ABOVE GRADE PLANE SHALL
 HAVE AT LEAST ONE EXTERIOR EMERGENCY
 ESCAPE AND RESCUE OPENING IN ACCORDANCE
 WITH THIS SECTION. WHERE BASEMENTS
 CONTAIN ONE OR MORE SLEEPING ROOMS,
 EMERGENCY EGRESS AND RESCUE OPENINGS
 SHALL BE REQUIRED IN EACH SLEEPING ROOM
 , BUT SHALL NOT BE REQUIRED IN ADJOINING
 AREAS OF THE BASEMENT. SUCH OPENING
 SHALL OPEN DIRECTLY INTO A PUBLIC
 STREET, PUBLIC ALLEY, YARD OR COURT. THE
 EMERGENCY ESCAPE AND RESCUE OPENING
 SHALL BE PERMITTED TO OPEN INTO A SCREEN
 ENCLOSURE, OPEN TO THE ATMOSPHERE, WHERE
 A SCREEN DOOR IS PROVIDED LEADING AWAY
 FROM THE RESIDENCE. SUCH OPENING SHALL
 BE OPERATIONAL FROM THE INSIDE WITHOUT
 THE USE OF SPECIAL KNOWLEDGE, KEYS OR
 TOOLS.
 EXCEPTIONS:
 1.IN OTHER THAN GROUP R-3
 OCCUPANCIES AS APPLICABLE IN SECTION
 101.2 , BUILDINGS EQUIPPED THROUGHOUT
 WITH AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2 .
 2.IN OTHER THAN GROUP R-3
 OCCUPANCIES AS APPLICABLE IN SECTION
 101.2 , SLEEPING ROOMS PROVIDED WITH A
 DOOR TO A FIRE-RESISTANCE-RATED CORRIDOR
 HAVING ACCESS TO TWO REMOTE EXITS IN
 OPPOSITE DIRECTIONS.
  
 20) PRODUCT APPROVALS:
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 21) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXT SOLID DOORS
 B) EXT GLAZED DOORS SWING
 C) WINDOWS A7.3.1 NO WINDOW LEGEND
 D) MULLIONS
 E) EXT RAILINGS
 F) LOUVERS
 G) TRUSS ANCHORS
 H) ROOFING ASSEMBLIES
 1) FLAT
 2) CEMENT TILE & TYPE OF INSTALATION
  
 22) 1714.5.5/1714.5.5.1 MULLIONS
 OCCURRING BETWEEN INDIVIDUAL WINDOW AND
 GLASS DOOR ASSEMBLIES. TESTING REPORTS
 ARE REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 23)1714.5.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 24) SHEET S-7 BUILDING ZONE MAP
 DESIGNED BY C.P.P. DOES NOT PROVIDE WHAT
 DESIGN PARAMETERS THAT WERE USED?
 PROVIDE REPORT FROM PROJECT # 05-3164.
 ASCE 7-02 ONCE THIS INFORMATION IS
 RESEARCHED THE SUBMITTED PRODUCT
 APPROVALS WILL BE REVIEWED.
  
 25)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved