| 2006-05-11 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 3. ALL PLANS DESIGNED BY A PROFESSIONAL |
| | ARCHITECT OR ENGINEER, THEN ALL SHEETS |
| | SHALL BE SIGNED, SEALED, & DATED AS |
| | REQUIRED BY FLORIDA STATUTES. SECTION |
| | 106.1. |
| | ***RESPONSE NOTED, BUT THE BOUNDARY |
| | SURVEY, PP1 OF 9 THRU PP9 OF 9, LA-POOL |
| | -1 THRU LA-POOL-4, LA-FW-1 THRU LA-FW-5 |
| | SHEETS HAVE NOT BEEN SIGNED, SEALED, |
| | DATED. RESPONSE INDICATING THE GENERAL |
| | CONTRACTOR SHALL PROVIDE IS NOT PER FS |
| | AND FAC REQUIREMENTS. |
| | |
| | 4. SHT CH A2.1.1 KITCHEN SINK SHALL BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. CLEAR FLOOR SPACE FOR SINK |
| | SHALL BE FORWARD APPROACH. |
| | ***RESPONSE NOTED, BUT A DETAIL FOR THE |
| | SINK HAS NOT BEEN FOUND AND NO RESPONSE |
| | FROM THE ARCHITECT HAS BEEN SUBMITTED. |
| | CLEAR FLOOR SPACE SHOWN ON SHT A2.1.1 IS |
| | NOT APPROVED AS IT IS A PARALLEL |
| | APPROACH. |
| | |
| | 6. SHT P3.1 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ***RESPONSE NOTED, BUT THE CORRESPONDING |
| | LENGTHS ARE NOT SHOWN, AND THE ISOMETRIC |
| | DOES NOT REFLECT THE OFFSETS SHOWN ON |
| | THE FLOOR PLAN FLAT LAYOUT. |
| | |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ***RESPONSE NOTED, BUT NO DELIVERY |
| | PRESSURE IS SHOWN ON THE ISOMETRIC. |
| | |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | *** RESPONSE NOTED, BUT NO VENTING |
| | INFORMATION IS SHOWN ON SHT P3.1. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***RESPONSE NOTED, BUT NO MANUF. |
| | SPECIFICATION SHEETS WERE SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | SHEETS AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ***************NEW COMMENT************** |
| | 1B. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL & FS 533.80(2)(B). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |