Date Text
2006-05-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 11
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 3. ALL PLANS DESIGNED BY A PROFESSIONAL
 ARCHITECT OR ENGINEER, THEN ALL SHEETS
 SHALL BE SIGNED, SEALED, & DATED AS
 REQUIRED BY FLORIDA STATUTES. SECTION
 106.1.
 ***RESPONSE NOTED, BUT THE BOUNDARY
 SURVEY, PP1 OF 9 THRU PP9 OF 9, LA-POOL
 -1 THRU LA-POOL-4, LA-FW-1 THRU LA-FW-5
 SHEETS HAVE NOT BEEN SIGNED, SEALED,
 DATED. RESPONSE INDICATING THE GENERAL
 CONTRACTOR SHALL PROVIDE IS NOT PER FS
 AND FAC REQUIREMENTS.
  
 4. SHT CH A2.1.1 KITCHEN SINK SHALL BE
 ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. CLEAR FLOOR SPACE FOR SINK
 SHALL BE FORWARD APPROACH.
 ***RESPONSE NOTED, BUT A DETAIL FOR THE
 SINK HAS NOT BEEN FOUND AND NO RESPONSE
 FROM THE ARCHITECT HAS BEEN SUBMITTED.
 CLEAR FLOOR SPACE SHOWN ON SHT A2.1.1 IS
 NOT APPROVED AS IT IS A PARALLEL
 APPROACH.
  
 6. SHT P3.1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT THE CORRESPONDING
 LENGTHS ARE NOT SHOWN, AND THE ISOMETRIC
 DOES NOT REFLECT THE OFFSETS SHOWN ON
 THE FLOOR PLAN FLAT LAYOUT.
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ***RESPONSE NOTED, BUT NO DELIVERY
 PRESSURE IS SHOWN ON THE ISOMETRIC.
  
 F. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 *** RESPONSE NOTED, BUT NO VENTING
 INFORMATION IS SHOWN ON SHT P3.1.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT NO MANUF.
 SPECIFICATION SHEETS WERE SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 SHEETS AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ***************NEW COMMENT**************
 1B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL & FS 533.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]