Plan Review Notes
Plan Review Notes For Permit 05080677
Permit Number 05080677
Review Stop E
Sequence Number 2
Notes
Date Text
2006-04-27 00:00:00IN ELEC FOR REVIEW.
 ***** UNSAT2ND REVIEW *****
  
 PLEASE SEE NOTES FROM PREVIOUSREVIEW
 WHICH REMAIN AND NEW NOTES.
  
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW. PLEASE
 ALSO SEE NOTES PERTAINING TO THE REMOVAL
 OF ALL OLD/VOIDED SHEETS AS REQUESTED
 ON PREVIOUS REVIEW.
  
  
  
 SAIL CLUB
 CLUBHOUSE BUILDING.
  
 1)NOTE:NOTE #1 NO, PLEASE SEE NOW THE
 PLANS ARE CHANGED SHOWING ALL EM/ EXT
 LTS CIRCUITED TO THE SAME CIRCUIT WHERE
 ORIGINAL COMMENT WAS TO SEE 700.12 E
 WHICH REQUIRED ALL EM/ EXT LTS CIRCUITED
 TO THE LOCAL LIGHTING IN ANY ONE AREA.
 PLEASE KNOW THE CIRCUITING ON PLANS WAS
 CORRECT AND IT WAS THE PANEL SCHEDULE
 THAT NEEDED TO BE ADJUSTED TO CORRELATE
 WITH THE PLANS WHICH SHOWED THE
 CIRCUITING CORRECT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE EM/ EXT LTS ARE SHOWN
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FOR LIGHITNG IN THAT AREA, HOWEVER
 EM/EXT LTS ARE SHOWN ON A SEPARATE
 CIRCUIT ON PANEL SCHEDULE.
 700.12E.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE PLANS
 SHOULD REFERENCE THE FOLLOWING, 2002
 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
  
  
 ** PREVIOUS NOTE **
 PLEASE SEE PLANS REFERENCE THE 1999 NEC.
 PLEASE SEE AS OF JULY 7TH,2003 THE STATE
 ADOPTED THE 2002 NEC.
 PLEASE SEE COVER SHEETS FOR PROJECT.
  
  
 3)NOTE: NOTE#3, NO, PLEASE SEE WATER
 HEATER IS STILL BEING SHOWN IN STORAGE
 CLOSET?? PLEASE SEE RESPONSE MENTIONS ,
 PLUMBING DESIGNIS CORRECT"?
 PLEASE CLARIFY TYPE OF FIXTURE UNIT
 BEING INSTALLED AND ALL MIN CLEARENCES
 PER SPECS. IS THIS UNIT A OINT OF USE
 UNIT OF SOME KIND?
  
 ** PREVIOUS NOTE **
 PLEASE SEE WATER HEATER MAY NOT
 BE LOCATED IN "STORAGE" AREA/CLOSET.
 PLEASE SEE THIS LOCATION WILL BE PRONE
 TO STORAGE OF COMBUSTIBLES AND CREATE A
 FIRE HAZARD.
 PLEASE SEE 422.17 AND ANY COMMENTS FROM
 FIRE PLAN REVIEW.
  
 4)NOTE: NOTE #4 NO, SEE CIRCUIT FOR
 FRIG.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.8B3 IN KITCHENS
 IN OTHER THAN DWELLING UNITS, WHICH
 REQUIRES ALL 15/20A 125V RECEPTS TO BE
 GFI PROTECTED WHEATHER OR NOT SERVICE
 KITCHEN AREA COUNTERSPACES.
  
 5)NOTE: OK.
  
 6)NOTE: OK.
  
 7)NOTE:NOTE #7 NO, RESPONSE MENTIONS
 TO SEE REVISED PANEL SCHEDULE, HOWEVER
 PANEL SCHEDULE STILL SHOWS "A" AND "C"
 PHASE. PLEASE EXPLAIN.
  
 ** PREVIOUS NOTE **
 PLEASE ALSO SEE SERVICE IS SHOWN
 AS SINGLE PHASE, HOWEVER PANEL SCHEDULE
 INDICATES "A" AND "C" PHASE?
 A& B.
  
 **********************************
 NEW NOTE:
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR ANY OF THE SAME CODE
 COMPLIANT COMMENTS .
 THIS IS ONLY NOTICE GIVEN AT THIS TIME.
  
  
  
 ****************************************
 PLEASE COMPLETELY REMOVE ALL OLD/ VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE ATTACHED TO EACH OTHER TO COMPOSE OF
 ONE SET OF VOIDED SHEETS ONLY AND WILL
 BE SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE.
 **************************************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  