Plan Review Notes
Plan Review Notes For Permit 05080677
Permit Number 05080677
Review Stop B
Sequence Number 2
Notes
Date Text
2006-04-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080677
 ADD: 719 EXECUTIVE CENTER DR
 (CLUBHOUSE)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 CELL:(954)675-4302
  
 ARCHITECT: ACI ARCHITECRTURALGROUP
 PAUL M. TWITTY
 TEL:(561)832-5599
 STRUC ENGINEER: ONM&J
 PHILLIP RIZZO
 TEL:(561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
  
 NOTES: 1-10 TOTALLY IGNORED, NOT IN
 RESPONCE COMMENTS.
  
 1)*******IMPORTANT NOTE IGNORED******
 EITHER THE CONTRACTOR OR THE DESIGN
 PROFESSIONAL HAS TO TAKE RESPONSIBILITY
 FORTHIS PROJECT AND COMPLY WITH THIS
 REQUEST, AND REMOVE ALL VOIDED SHETTS
 FROM THE PERMIT DOCUMENTS.
 2ND REQUEST:
 WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)NOTE:105.8* FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)109.3.7*THIS PARTICUAL TYPE OF
 BUILDING "WILL NOT" REQUIRE A SPECIAL
 INSPECTOR, ALTHOUGH THERE WILL BE A
 THRESHOLD INSPECTOR FOR THE MID RISE AND
 HIGH RISE BUILDINGS.WILL THIS INSPECTOR
 ALSO BE INSPECTING THIS BUILDING? IF SO
 THREE (3) SET OF ALL DOCUMENTS WILL NEED
 TO BE SUBMITTED AS IF FOR ATHRESHOLD
 BUILDING.WILL THIS INSPECTOR BE THE SAME
 PERSON AS THE THRESHOLD INSPECTOR? OR
 WILL THERE BE TWO INDIVIDUALS?
 FORMS WILL NEED TO BE FILLED OUT FOR THE
 SPECIAL INSPECTOR, CONTACT HAROLD
 PISKURA, INSPECTION SERVICES MANAGER @
 (561)805-6711 TO SEET UP AN APPOINTMENT.
  
 4)2ND REQUEST COMMENT# 4 PREVIOUS REVIEW
 106.3.3* PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITTING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR " JURISDICTIONAL
 APPROVAL", (LOCAL PRODUCT APPROVAL).
  
 5)2ND REQUEST COMMENT# 5 PREVIOUS REVIEW
 SITE PLAN NEEDS TO BE SUBMITTED TO
 ADDRESSING PERSONEL JOHN HIGGINS FOR
 ADDRESSING AS WELL AS NEW PLAT MAP FOR
 THE COMBINATION OF LOTS. JOHN HIGGINS
 CONTACT NUMBER IS (561)822-1239.
  
 6A)2ND REQUEST COMMENT 6A PREVIOUS
 REVIEW:THERE IS A DISCREPANCY IN THE
 PLANS SINCE THE BOUNDRY SURVEY FOR
 PARCEL# 7, ONLY INDICATES 2 LOTS PARCEL
 1&2.NOTE: FOR TOWNHOUSES EACH UNIT WILL
 REQUIRE INDIVIDUAL PROPERTY CONTROL
 NUMBERS WITH ASSOCIATED PROPERTY LINE.
  
 6B)2ND REQUEST COMMENT6B PREVIOUS REVIEW
 THE SURVEY DOES SHOW 2 SEPERATE LOTS
 WHICH APPEAR TO CUT THROUGH BULDING "B"
 AND BUILDING "C". A UNITY OF TITLE SHALL
 BE REQUIRED, TABLE 601 AND 602.
  
  
 7) ENERGY COMPLIANCE FORMS:
 7A)2ND REQUEST COMMENT 7A FROM THE
 PREVIOUS REVIEW:
 UPDATE FORM TO FORM 400A-04.
  
 8)COMPLIED.
  
 9A)2ND REQUEST : SHEET A3.2.1 WALL
 SECTIONS DO NOT INDICATE WHAT TYPE OF
 TERMITE TREATMENT FOR SOILS WILL BE
 USED, SEE 1816.1.
  
 9B)2ND REQUEST:
 THIS SAME SHEET INDICATES THE USE OF
 A VAPOR BARRIER, MUST BE A MINIMUM OF 6
 MIL TO BE USED WITH CHEMICALLY TREATED
 TERMITE TREATMENT FOR SOILS BENEATH
 SLAB.1806.1.4.NOTE SOILS REPORT
 RECOMMENDS (8.4.2) THE USE OF A HEAVIER
 10MIL POLYOLEFIN.
  
 9C) 2ND REQUEST, TO ADD THIS NOTE TO
 PLANS, 1816.1.6 IF SOIL TREATMENT IS
 USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICAL SOIL TREATMENT
 SHALL BE APPLIED UNDER ALL EXTERIOR
 CONCRETE OR GRADE WITHIN 1 FT OF THE
 PRIMARY STRUCTURE SIDEWALLS.
  
 10) SHEET A6.1.1:
 10A) 1203.2.ATTIC SPACE. TRUE THIS SPACE
 IS NOT ATTIC SPACE. 1203.1 SEE CODE
 COMMENTARY ABOUT THIS TYPE OF USAGE OR
 SPACE.EVERY ROOM OR SPACE MUST BE
 PROVIDED WITH VENTILATION. THE SELECTION
 OF NATURAL VENTILATION ON A ROOM BY ROOM
 OR SPACE BY SPACE IS THE DESIGNER'S
 PREROGATIVE. INDICATE HOW VENTILATION
 WILL BE ACCOLPLISHED, BY TRANSFER
 GRILLES, ETC?
  
 10B) 2ND REQUEST, DETAIL# 8 DOESN'T
 MATCH SHEET A3.2.1OR VARIOUS CUT
 SECTIONS THROUGH THE ROOF SHEATHING, THE
 PLANS REVEAL 2 THICKNESSES OF SHEATHING
 &USE OF 1/2" THICK HIGH DENSITY
 SUBTRATE, PLEAASE CORRECT ALL DETAILS TO
 THE SAME THICKNESS AND COMPLY WITH
 TABLE2304.7(5)
  
 10C) 2ND REQUEST. DETAIL# 8 WAS
 CORRECTED, DETAIL# 9 STILL INDICATES
 HIGH DENSITY SUBSTRATE. TABLE 2304.7(5)
 FOOTNOTE (A) PLYWOOD STRUCTURAL PANELS
 ARE 5-PLY, 5LAYER UNLESS OTHERWISE
 NOTED. CHANGE IN FOOTNOTE NEW YELLOW
 PAGES.
  
 10D) COMPLIED.
  
 10E) BOTH THIS SHEET AND A2.1.1 ARE
 MISSING THE ATTIC ACCESS
  
 10F) THE FLOOR PLAN NOR WALL SECTIONS
 INDICATE ATTIC ACCESS?
  
 10G) NEW COMMENT, DEALS WITH HIP AND
 RIDGE ATTACHMENT, 1507.3.7 ATTACHMENT &
 1507.3.8 APPLICATION BOTH TO BE IN
 ACCORDANCE WITH FRSA/ TRI 07320, THE
 NEWEST STANDARD 08-05.SEE TABLE 11 FOR
 NUMBER OF CLIPS, SPACING AND FASTENERS.
  
  
 11) 2ND REQUEST, A PERMIT APPLICATION
 WILL BE REQUIRED FOR SITE AMENITIES,
 SEPERATE PLANS WILL BE REQUIRED FOR THIS
 PACKAGE. THE PERMITS APPLIED FOR AT THIS
 TIME ARE FOR BUILDINGS ONLY!!!!!!!!!
 PLANS SUBMITTED ALSO INDICATE A BUS
 SHELTER (A6.13)THIS WILL BE STRUCK SINCE
 THE BUS SHELTER SHOULD BE PART OF A SITE
 AMENITIES PACKAGE THAT WOULD BE
 PERMITTED SEPARATELY.
  
 12A) 2ND REQUEST:
 PRODUCT APPROVALS REQUIRE;
 RULE 9B-72- PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE WITH THE ASSOCIATED REPORT. IF
 THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL ON THE CITY FORM
 PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 12B)2ND REQUEST, CONTRACTOR SUBMITTED
 PRODUCT APPROVALS WHICH WILL NOT BE USED
 ON THIS PROJECT, PLEASE REMOVE FROM
 PACKAGE: SBS MODIFIED BITUMEN SYSTEM
 OVER LIGHT WEIGHT CONCRETE DECK..
  
 12C)@ND REQUEST,FL BLD CODE
 1602/COMPONENTS & CLADDING, 1609.6 :
 COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED FRONT ENTRY DOORS
 B) SOLID SWING DOOR
 C) TRUSS ANCHORS
 D) ROOF ASSEMBLIES TILE ROOF
 E) DENSEGLASS SHEATHING
  
 13) SHEET S-3 :
 13A) COMPLIED.
 .
 13B) COMPLIED.
  
 14) 2ND REQUEST NOT ON RESPONCE SHEET.
 1503.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15)2ND REQUEST, WILL CONTINUE TO BE A
 COMMENT UNTIL PAYMENT IS MADE AT PALM
 BEACH COUNTY IMPACT FEE OFFICE.
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026